Kamco CLEARFLOW CF90: QUANTUM Скачать руководство пользователя страница 10

 

 

CHEMICAL FLUSHING PROCEDURE USING POWER FLUSH FX2 

 

 

 

 
1. Switch on the Quantum. 
 
2. Whilst re-circulating water through the Quantum 

and the heating system, slowly add 2½ ltr of 
Powerflush FX2 to the Quantum tank (sufficient 
for 10-12 radiator system), and ensure thorough 
distribution around the system. 

 
3. Switch on the boiler, if fitted, and in safe working 

order. Allow the system water to reach 50°C, and 
then switch boiler off. 

NOTE: Even boiler thermostat setting no.1 
could exceed 50°C. 

 
4. Circulate throughout the complete system for 15 

minutes, reversing the flow direction regularly, 
and monitoring the system for leaks. 

 
5. Close off all radiators (one valve only per radiator 

is enough), and allow the full flow to go through 
the coil in the cylinder (if present in the system). 

 
6. Reverse the flow regularly. 
 
7. Divert the full flow to the radiator circuit, in 

preparation to putting the full flow of the Quantum 
through each radiator in turn. 

 
8. Fully open both valves of the nearest radiator, on 

the ground floor, to the Quantum. 

 
9. Flush this radiator, reversing the flow regularly, 

until all cold spots have disappeared, and the 
temperature across the radiator is consistent. 
Close the radiator valves. 

 

Note: If your initial system check identified cold or 
partially blocked radiators, commence the 
individual radiator flushing procedure with the 
worst radiator first, progressing to less 
problematic radiators. This ensures that the 
strongest concentration of chemical is directed at 
the worst areas of the system. 

 
10. Open the valves on the next radiator, and repeat 

the procedure. 

 

11. Work through the rest of the radiators in turn, so 

that you have flushed every radiator individually, 
including upstairs radiators. 

 
12. When you have flushed the last radiator, and 

obtained an even temperature across the 
surface, switch the Quantum into dumping mode, 
as previously. 

 
13. With only this radiator open, and the Quantum 

set to dump, run until the water leaving the dump 
hose is completely clear. Now operate the flow 
reverser and change the valves to dump in the 
opposite direction until clear. When dump water 
is clear, close radiator valve. 

 
14. Go back to the previous radiator that you had 

flushed, ensure both valves are open, and repeat 
the dumping procedure on this one radiator, 
alternating the direction of flow in each direction 
as you dump. Close radiator valve. 

 
15. Work your way back around the house in the 

opposite direction to previously, until you have 
carried out the dumping process on every 
radiator individually. 

 
16. Now with the Quantum still set to dump direct the 

flow through the cylinder coil until it runs clear. 
Dump in the other direction until clear. 

 

Note: You have used an acidic cleaner, and 
therefore a neutralising chemical should be 
circulated throughout the system to ensure that 
no traces of FX2 remain in the system. 
Whilst FX2 contains specific inhibitors so that its 
presence during a power flush presents no 
problems, it is bad practice to leave system water 
acidic over a long period of time. 

 
17. Return the Quantum into normal re-circulation 

mode, re-open all radiator valves, and the 
cylinder coil. 

 
18. Slowly add 100 gm of 

NEUTRALISING 
CRYSTALS to the 
water in the pump 
tank whilst circulating 
throughout the 
system. 

 
19. Circulate throughout the system for ten to fifteen 

minutes. 

 
 

Continued on next page.

Issue: Mar 2008 

Section B  – Using the Quantum for Power Flushing

 Page 

B.7 

© Kamco

Содержание CLEARFLOW CF90: QUANTUM

Страница 1: ...K a m c o...

Страница 2: ...e safe use of the pump How to connect the pump into the heating system step by step guide to the flushing process and which chemicals are best suited for each application Please take time to carefully...

Страница 3: ...items Regularly check power leads for wear or damage use with a residual circuit breaker When handling chemicals wear suitable protective clothing gloves and goggles Use in a well ventilated area PAT...

Страница 4: ...nto the Quantum if it has been connected connection details are in the next section 7 With vented systems it is necessary to cap off or loop together the expansion and cold feed pipes in order to avoi...

Страница 5: ...connected to the pump body see page F 2 Generally the unit should be located in a room with a suitable drain point and near to a convenient mains water supply such as a bathroom or kitchen The cold wa...

Страница 6: ...pump from the system until power flushing is commenced A pair of 0 5 metre long adapter hoses enabling the Quantum to be connected across the 1 1 2 unions are supplied as standard When used these are...

Страница 7: ...Check all hoses and connections for leaks 5 The Quantum has the ability to dump dirty water when the flow is in either direction Change the Quantum into dumping mode as follows remembering that the fl...

Страница 8: ...d more water if necessary Vent all radiators to ensure that there are no air pockets Use a cloth to absorb any liquid expelled as the system water may be discoloured and likely to stain 8 The flushing...

Страница 9: ...E FX2 IN A SYSTEM HYPER FLUSH Use Hyper Flush when The system contains aluminium radiators or heat exchangers You consider the system to have suffered severe internal corrosion and metal wastage The s...

Страница 10: ...e radiators in turn so that you have flushed every radiator individually including upstairs radiators 12 When you have flushed the last radiator and obtained an even temperature across the surface swi...

Страница 11: ...amples show the same colour Note As an alternative an electronic pH meter may be used see page F 11 22 If you have a TDS meter Total Dissolved Solids it is useful to test the water at this stage The r...

Страница 12: ...e system 10 Open the valves on the next radiator and repeat the procedure 11 Work through the rest of the radiators in turn so that you have flushed every radiator individually including upstairs radi...

Страница 13: ...k which will contain a small quantity of inhibitor may be poured into a bucket and added to the F E tank after this has been cleaned Note In a pressurised system the inhibitor may be injected into the...

Отзывы: