background image

this stage is the chemical added so that it can  then work 

specifically to disturb, loosen and dissolve more stubborn 

accumulations of debris.The chemical can then work 

specifically to disturb, loosen, and dissolve more stubborn 

accumulations of debris.

Either remove the tank filler cap or leave it loosely on the tank 

neck if there is some splashing whilst flushing.

Set both valves in the closed position.

Plug the pump into a power supply and switch supply on.

The flow reverser lever has 

two positions, LEFT, and 

RIGHT.

If the lever is to the left, water 

will flow into the heating 

system through the left hand 

side hose, and water will 

return to the tank along the 

right hand hose. Pushing the 

lever to the right reverses the 

direction of flow and return.

The exact direction of flow is not of any great importance until 

you wish to ‘dump’ the system water.

Switch the pump on and make sure that the water level in the 

tank remains at least 10 cm above the minimum mark, adding 

more water if necessary.

Check all hoses and connections for leaks, and repair before 

continuing.

Run the pump for ten minutes, reversing the direction of flow 

regularly by moving the lever from left to right, and vice versa.

When ‘dumping’, 

the water level 

in the tank will 

fall as dirty 

water is diverted 

down the drain, 

and does not 

return into the 

pump tank.

Switch the pump 

on and operate 

the correct 

dump valve 

depending upon 

the direction of 

flow. If the flow 

reverser lever 

is to the left, twist the right-hand dump valve through 180

to show the word ‘dump’, ensuring that the left-hand valve 

remains in the ‘circulation’ position.

If the flow reverser lever is to the right, twist the left-hand dump 

valve through 180

to show the word ‘dump’, ensuring that the 

right-hand valve remains in the ‘circulation’ position. 

Open the orange water inlet valve and adjust to allow fresh 

water to enter the tank at the same rate as water is exiting the 

dump hose. Make sure that the tank water level remains at 

least 10 cm above the minimum mark, and continue dumping 

until the waste water runs relatively clear.
Turn the valve which is in ‘dump’ mode through 180

o

 to restore 

full circulation through the pump and the system. Close the 

water supply inlet valve once the water level in the tank has 

stabilised between minimum and maximum marks.

Bleed all radiators to expel any air.

This stage is carried out once the initial brief circulation and 

discharge of the worst of the debris has been carried out.

Switch the pump on so that water is re-circulating through the 

heating system. Remove the tank filler cap and carefully pour 

either PowerFlush FX2 or Hyper-Flush liquid into the tank.

Keep the pump running for 15 minutes, regularly reversing the 

direction of flow.

With the Clearflow pump still running, close all radiator valves 

to enable the cylinder coil (if present) to be thoroughly flushed, 

reversing the flow regularly.

Next close any diverter / zone valves to direct the flow through 

the heating circuit, in preparation to flush each radiator.

Starting on the ground floor radiators, fully open both radiator 

valves on the nearest radiator. Alternatively, start with the worst 

radiator first, so that the strongest concentration of chemical is 

directed at the worst areas of the system.

Flush the radiator, reversing the flow regularly until it is cleared. 

Once cleared close both valves and move to the next radiator.

Open both radiator valves, and repeat the procedure.

Work through the remaining radiators in turn, until every 

radiator in the system has been flushed individually.

Having flushed each radiator individually, then closed their  

valves, set the pump into dumping mode. With only the last 

radiator valves open, operate the pump until the water leaving 

the dump hose is completely clear. Reverse the direction 

of flow and the isolating / dump valves accordingly so that 

dumping is performed in both directions.

Once the dumped water from both directions is clear, close 

both radiator valves.

Repeat this process on each individual radiator until all have 

been cleared.

If the system has a hot water cylinder, open the diverter valve 

and flush the coil, dumping in both directions.

Finally, flush the boiler, dumping in both directions. 

If you have used PowerFlush FX2 flushing liquid, which is 

acidic, it must be neutralised to prevent long term corrosion.

Set the Clearflow pump to normal recirculation mode then 

open all radiator and diverter valves. With the pump running, 

add 100gm of Neutralising Crystals to the tank. If the water 

foams, add a few drops of Foambreaker antifoam chemical.

Continue circulating in both directions for fifteen minutes, then 

set to dump mode and dump for at least ten minutes to clear 

all chemicals. Check the water leaving the dump hose with pH 

paper. Continue dumping until the paper shows a pH of 7 or 

the same pH reading as the property’s main water supply.

Set the Clearflow to normal re-circulation mode.

The heating system has now been fully flushed and is full of 

fresh clean water. You should now add a good quality corrosion 

inhibitor, such as SystemSafe-DM. First open the dump valve 

to reduce the water level in the tank to 5cm (2”) above the 

minimum line.

Flow 

reverser 

lever

Water 

inlet 

valve

Motor 

switch

Page 3

Commencing the power flush

What happens when dumping

Addition of power flushing chemicals

Dumping the heating system water

Use of stronger power flushing chemicals

On completion of the power flush

Отзывы: