INSTALLATION GUIDE
KALE FANS
www.kalefans.net
2019
Caution
The installation and layout of the circuit wiring must be performed by our professional qualified staff.
Please use the specified device component appointed by our company.
While the fan is running, please don’t cut off the power, otherwise it will cause damage to the fan. It should cut off
the power when the fan is drop-dead halt.
When the fan is in the corotation (inversion) state, please don’t switch the button to the opposite direction directly or
it will cause the mechanical failure.
8. Troubleshooting
Common causes for the malfunctioning operation:
1. The external power supply of the control box is not valid.
2. Open the master switch, and then turn on the three gears control switch, if the fan can still not work, please check
whether the speed knob is of the MIN state. Otherwise, please contract KaLe Environmental Technology(Shanghai)Corp.
Non-professional staffs do not open the electrical control box! For repair or adjustment, KaLe Environmental
Technology(Shanghai)Corp. will send you our trained professionals or engineers.
If you find the equipment is damaged or has abnormal sound, please stop running as soon as possible, cut off power
supply, and contact our service department.
Notes: Equipment damages due to the improper use are not covered by the warranty. Personal injuries and equipment
damages for your failure to comply with the contents of this manual, the Company will not bear any responsibilities.
8.1 Explanation of error codes
-15-
No. Description
Warning Alarm
Trip
Lock
Error
Cause of Problem
2
Live zero error
X
X
Signal on terminal 53 or 60 is less than 50% of value set in
6-10 Terminal 53 Low Voltage
,
6-12 Terminal 53 Low Current
and
6-22 Terminal 54 Low Current
.
4
Mains phase loss
1)
X
X
X
Missing phase on supply side, or too high voltage imbalance. Check
supply voltage.
7
DC over voltage
1)
X
X
Intermediate circuit voltage exceeds limit.
8
DC under voltage
1)
X
X
Intermediate circuit voltage drops below “voltage warning low” limit.
9
Inverter overloaded
X
X
More than 100% load for too long.
10
Motor ETR over temperature
X
X
Motor is too hot due to more than 100% load for too long.
11
Motor thermistor over
temperature
X
X
Thermistor or thermistor connection is disconnected.
12
Torque limit
X
Torque exceeds value set in either par. 4-16 or 4-17.
13
Over Current
X
X
X
Inverter peak current limit is exceeded.
14
Earth fault
X
X
X
Discharge from output phases to ground.
16
Short Circuit
X
X
Short-circuit in motor or on motor terminals.
17
Control word timeout
X
X
No communication to frequency converter.
25
Brake resistor short-circuited
X
X
Brake resistor is short-circuited, thus brake function is disconnected.
27
Brake chopper short-circuited
X
X
Brake transistor is short-circuited, thus brake function is discon-
nected.
28
Brake check
X
Brake resistor is not connected/working
29
Power board over temp
X
X
X
Heat-sink cut-out temperature has been reached.
30
Motor phase U missing
X
X
Motor phase U is missing. Check the phase.