Indoor Unit 

Installation

 Page 10 

Cut off the roof beam.
Strengthen the point at which the cut was 

made. Consolidate the roof beam.

Fig. 4.6

Fig. 4.7

Original concrete bricks   

Use an embedding screw bolt, crock, and stick

harness. (See Fig.4.6)

Steel roof beam structure

Install and use the supporting steel angle.

(See Fig.4.7)

Fig. 4.4

Wood

Place the wood mounting across the roof beam,

then install the hanging screw bolts.(See Fig.4.4) 

Wood mounting

Roof beam

Hanging screw bolts

Ceiling 

Fig. 4.5

New concrete bricks 

Inlay or embed the screw bolts. (See Fig. 4.5)

(Blade shape insertion)

(Slide insertion)

Steel bar

Embedding screw bolt

(Pipe hanging and embedding screw bolt) 

Hanging screw bolt

Hanging 

bolts

Supporting

 angle steel

Fig. 4.9

Screw nut 

Washer

Hanging screw bolt

Overhang part

Shockproof cushion

NOTE:

 Confirm the minimum drain tilt is 1/100 

or more.

 CAUTION

The unit body must be completely aligned with

the hole. Ensure that the unit and the hole are

the same size before moving on.

2. Install and fit pipes and wires after you have

finished installing the main body.When 

choosing where to start, determine the 

direction of the pipes to be drawn out.

Especially in cases where there is a ceiling

involved, align the refrigerant pipes, drain

pipes, and indoor and outdoor lines with their

connection points before mounting the unit.

3.

 

Install hanging screw bolts.

4. After you select an installation location,align

the refrigerant pipes, drain pipes, as well as

indoor and outdoor wires with their 

connection points before mounting the unit.

5. Drill 4 holes 10cm (4”) deep at the ceiling 

hook positions in the internal ceiling. Be sure 

to hold the drill at a 90° angle to the ceiling.  

6. Secure the bolt using the washers and nuts

provided.

7. Install the four suspension bolts.
8. Mount the indoor unit with at least two

people to lift and secure it. Insert suspension

bolts into the unit’s hanging holes. Fasten

them using the washers and nuts provided.

(See Fig. 4.8).   

9. Mount the indoor unit onto the hanging 

screw bolts with a block. Position the indoor 

unit flat using a level indicator to prevent 

leaks. (See Fig. 4.9).   

Fig. 4.8

Содержание KTI-18HWF 32

Страница 1: ...ITIONER Installation Manual Middle Static Pressure Duct Type IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for f...

Страница 2: ...door Unit Installation 13 a Outdoor Unit Installation Instructions 13 b Outdoor Unit Types and Specifications 14 c Notes on Drilling Hole in Wall 15 Drainpipe Installation 16 Table of Contents Install...

Страница 3: ...ructions 20 Wiring 22 a Outdoor Unit Wiring 22 b Indoor Unit Wiring 23 c Power Specifications 25 Air Evacuation 27 a Evacuation Instructions 27 b Note on Adding Refrigerant 28 Test Run 29 MC MC 7 8 9...

Страница 4: ...the outdoor unit Transfer connector 9 52 12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ from appliance to appliance To meet different pipe size requirements...

Страница 5: ...upervision of the person competent in the use of flammable refrigerants Appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation...

Страница 6: ...uld be read carefully WARNING CAUTION Explanation of symbols displayed on the indoor unit or outdoor unia applicable to the unit adopts R32 R290 Refrigerant only WARNING Appliance shall be installed o...

Страница 7: ...7 Install the indoor unit Page 8 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 16 Evacuate the refrigeration system Page 27 Connect the wires Page 22 Connect the refri...

Страница 8: ...Enough room exists for installation and maintenance Enough room exists for the connecting pipe and drainpipe The ceiling is horizontal and its structure can sustain the weight of the indoor unit The...

Страница 9: ...er Electric control box Table 4 1 unit mm inch MODEL Btu h Outline dimension A B C 18K 210 8 3 674 26 5 880 34 6 24K 249 9 8 774 30 5 1100 43 3 30K 36K 249 9 8 774 30 5 1360 53 5 36K 60K 300 11 8 874...

Страница 10: ...same size before moving on 2 Install and fit pipes and wires after you have finished installing the main body When choosing where to start determine the direction of the pipes to be drawn out Especial...

Страница 11: ...ording to the size of the air inlet 5 Refer to the following static pressure guidelines when installing the indoor unit Change the fan motor static pressure according to external duct static pressure...

Страница 12: ...ner you have purchased may be slightly different in design though similar in shape Step 5 Fresh air duct installation Dimension Duct joint for fresh air 125mm 4 92 160mm 6 3 MODLE 18 60 Step 6 Motor a...

Страница 13: ...between the outdoor and indoor unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit is locat...

Страница 14: ...ig 5 8 Fig 5 9 Fig 5 6 Fig 5 5 A B D W H W H Fig 5 4 Outdoor Unit Dimensions W x H x D Mounting Dimensions Distance A Distance B 760x590x285 29 9x23 2x11 2 530 20 85 290 11 4 810x558x310 31 9x22x12 2...

Страница 15: ...he protective wall cuff in the hole This protects the edges of the hole and will help seal it when you finish the installation process Fig 5 11 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or...

Страница 16: ...late all piping to prevent condensation which could lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause a water level switch malfunction In HEAT mode the ou...

Страница 17: ...about 12mm 0 5 This will ensure proper water drainage See Fig 6 5 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it once you finish installation Wall...

Страница 18: ...after completing the installation work Notes On Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and outdoor units me...

Страница 19: ...raps in the rising gas piping can prevent this CAUTION The indoor unit is installed higher than the outdoor unit If the outdoor unit is installed higher than the indoor unit It is recommended that ver...

Страница 20: ...t seal of refrigerant piping connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all bu...

Страница 21: ...m the unit Fig 7 10 CAUTION Ensure to wrap insulation around the piping Direct contact with the bare piping may result in burns or frostbite Make sure the pipe is properly connected Over tightening ma...

Страница 22: ...ctrical shock Ensure that main power supply connection is made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an e...

Страница 23: ...electrical or metal parts 6 Reinstall the cover of the electric control box Indoor Unit Wiring 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of the s...

Страница 24: ...will then start the fan for airflow automatic adjustment ON will flash during when the fan is on during automatic airflow adjustment After 3 to 6 minutes the air conditioning unit stops operating onc...

Страница 25: ...ASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase 208 240V 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32 25 50 40 70 55 70 60 MODEL Btu h 36K 37K 60K 36K 37K 60K POWER PHASE 3 Phase 3...

Страница 26: ...OWER indoor PHASE 1 Phase 1 Phase 1 Phase 1 Phase 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 15 10 15 10 15 10 15 10 POWER outdoor PHASE 3 Phase 3 Phase 3 Phase 3 Phase 380 420V 380 42...

Страница 27: ...e of the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6...

Страница 28: ...as the standard pipe length is 5m 16 The additional refrigerant to be charged can be calculated using the following formula Liquid Side Diameter R32 Total pipe length standard pipe length x 12g 0 13oZ...

Страница 29: ...d correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the d...

Страница 30: ...is appliance you have the following options Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old applia...

Страница 31: ...ossible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly...

Страница 32: ...ties are advised Initial safety checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking that there no live electrical components and wi...

Страница 33: ...shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This proc...

Страница 34: ...not exceed the maximum working pressure of the cylinder even temporarily j When the cylinders have been filled correctly and the process completed make sure that the cylinders and the equipment are re...

Страница 35: ...are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associa...

Страница 36: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Page 36 QSBPT2I 053AEN R32 I...

Отзывы: