F20
IGBT Power Device
Overheat Alarm
1. Check the fans are running or not.
2. Check the installation distance and space.
3. If they are OK, please replace a new compressor driver board.
4. Leave enough distance and space to make heat pump have a good transfer
heating condition.
5. Clean air to fin heat exchanger.
F22
AC input over current
protection alarm
Only in single phase unit. Restart the unit.
1. Check if there is electric leakage.
2. If still have the failure, replace a new drive board.
F23
EEPROM Fault Alarm
1. Check the connection;
2. Replace a new driver board;
F24
Destroyed EEPROM
Activation Ban Alarm
F25
LP 15V Under load Fault
1. Check the power supply is stable or not, and restart unit.
2. If the problem still on, please replace a new drive board.
F26
IGBT Power Device
Overheat Fault
1. Check the fans are running or not;
2. Check the installation distance and space;
3. Leave enough distance and space to make heat pump have a good transfer
heating condition;
4. Clean the finned heat exchanger.
5. If they are OK, please replace a new driver board;
F031
DC Fan Motor 1 Failure
1. Turn off the unit and check the connection.
2. Restart and check if the motor is running normal or the error happens again.
3. Replace a new fan motor.
F032
DC Fan Motor 2 Failure
Pp1
Exhaust Pressure Sensor
Fault
1. Detect the exhaust pressure sensor connection
2. If the connection is OK, please replace a new one.
Pp2
Suction Pressure Sensor
Fault
1. Detect the suction pressure sensor connection
2. If the connection is OK, please replace a new one.
TP
Low Ambient Temp.
Protection
Ambient temp ≤-30
1 Check the ambient temp
2. When ambient temp ≥-28°C, the fault will disappear.
P01
Water Inlet Temp. Sensor
Fault
1. Detect the connection.
2. Measure the resistance of sensor, if lower than 100Ω or higher than 500kΩ,
please replace a new one.
P02
Water Outlet Temp.
Sensor Fault
P04
Ambient Temp. Sensor
Fault
P17
Water Outlet Temp.
Sensor Fault
P032
Hot Water Tank Temp.
Sensor Fault
P42
Room Temp. Sensor Fault
P101
EVI Inlet Temp. Sensor
Fault
P102
EVI Outlet Temp. Sensor
Fault
P153
Coil Temp. Sensor Fault
P181
Exhaust Temp. Sensor
Fault
P182
Exhaust Over Temp.
(Exhaust temp.) ≥C05
default 110
1. Measure the resistance of sensor, if lower than 100Ω or higher than 500kΩ,
please replace a new one.
2. Check the unit find if it has refrigerant leakage.
P191
Antifreeze Temp. Sensor
Fault
1. Detect the connection
2. Measure the resistance of sensor, if lower than 100Ω or higher than 500kΩ,
please replace a new one.