26

F20

IGBT Power Device 
Overheat Alarm

1. Check the fans are running or not.

 

2. Check the installation distance and space.

 

3. If they are OK, please replace a new compressor driver board.

 

4. Leave enough distance and space to make heat pump have a good transfer 

heating condition. 

5. Clean air to fin heat exchanger.

F22

AC input over current 
protection alarm

Only in single phase unit. Restart the unit.

 

1. Check if there is electric leakage.

 

2. If still have the failure, replace a new drive board.

F23

EEPROM Fault Alarm

1. Check the connection;

 

2. Replace a new driver board;

F24

Destroyed EEPROM 
Activation Ban Alarm

F25

LP 15V Under load Fault

1. Check the power supply is stable or not, and restart unit.

 

2. If the problem still on, please replace a new drive board.

F26

IGBT Power Device 
Overheat Fault

1. Check the fans are running or not;

 

2. Check the installation distance and space;

 

3. Leave enough distance and space to make heat pump have a good transfer 

heating condition; 

4. Clean the finned heat exchanger.

 

5. If they are OK, please replace a new driver board;

F031

DC Fan Motor 1 Failure

1. Turn off the unit and check the connection.

 

2. Restart and check if the motor is running normal or the error happens again.

 

3. Replace a new fan motor.

F032

DC Fan Motor 2 Failure

Pp1

Exhaust Pressure Sensor 

Fault

1. Detect the exhaust pressure sensor connection

 

2. If the connection is OK, please replace a new one.

Pp2

Suction Pressure Sensor 
Fault

1. Detect the suction pressure sensor connection

 

2. If the connection is OK, please replace a new one.

TP

Low Ambient Temp. 
Protection

Ambient temp ≤-30

1 Check the ambient temp

 

2. When ambient temp ≥-28°C, the fault will disappear.

P01

Water Inlet Temp. Sensor 
Fault

1. Detect the connection.

 

2. Measure the resistance of sensor, if lower than 100Ω or higher than 500kΩ, 

please replace a new one.

P02

Water Outlet Temp. 

Sensor Fault

P04

Ambient Temp. Sensor 
Fault

P17

Water Outlet Temp. 

Sensor Fault

P032

Hot Water Tank Temp. 

Sensor Fault

P42

Room Temp. Sensor Fault

P101

EVI Inlet Temp. Sensor 
Fault

P102

EVI Outlet Temp. Sensor 

Fault

P153

Coil Temp. Sensor Fault

P181

Exhaust Temp. Sensor 

Fault

P182

Exhaust Over Temp.

(Exhaust temp.)  ≥C05 
default 110

1. Measure the resistance of sensor, if lower than 100Ω or higher than 500kΩ, 

please replace a new one. 

2. Check the unit find if it has refrigerant leakage.

P191

Antifreeze Temp. Sensor 

Fault

1. Detect the connection

 

2. Measure the resistance of sensor, if lower than 100Ω or higher than 500kΩ, 

please replace a new one.

Содержание KHX-14PY3

Страница 1: ...OWNER SMANUAL AIR TO WATER HEAT PUMP EN R290...

Страница 2: ......

Страница 3: ...ENNY TYPU SPLIT Instrukcja obs ugi Dzi kujemy za wyb r naszego produktu Dla zapewnienia prawid owej obs ugi zapoznaj si z instrukcj i przechowuj j do wykorzystania w przysz o ci W przypadku zagubienia...

Страница 4: ...Content 1 Preface 5 2 Safety Instructions 6 3 Features 9 4 Unit Dimension mm 10 5 Parameters 11 6 Display Operation Guide 12 7 Failure List Troubleshooting 23...

Страница 5: ...tions are adhered to at all times to keep the warranty The unit can only be opened or repaired by a qualified installer or an authorized dealer Maintenance and operation must be carried out according...

Страница 6: ...der stand the following information correctly Mark Notes Icon Notes Mark Meaning A wrong operation may lead to death or grievous injury on people A wrong operation may lead to harm to people or loss o...

Страница 7: ...rong or strange smells the power supply needs to be shut off to stop the unit Continue running may cause short circuit or fire Move and Repair Meaning Entrust When the heat pump needs to be moved or i...

Страница 8: ...ANNOT be installed near the flammable gas Once there is any leakage of the gas fire may occur Fix the unit Make sure that the basement of the heat pump is strong enough to avoid any decline or fall do...

Страница 9: ...pump Centralized controlling system can control several units by PC 3 2 Nice Appearance The heat pump is designed with beautiful looking The monoblock one has the water pump included which is very ea...

Страница 10: ...nsion mm 4 1 Models KHX 14PY3 4 2 Models KHX 16PY3 Power line Power line Signal line Signal line Water outlet 1 Water outlet 1 238 363 928 458 540 500 125 1287 1250 975 216 Water inlet 1 Water inlet 1...

Страница 11: ...put Range kW 1 27 4 65 1 90 7 10 Hot Water Current Input Range A 2 4 8 21 3 4 12 5 Max Power Input kW 5 3 9 Max Current Input A 10 5 15 8 Water Flow m3 h 1 7 2 9 Refrigerant Proper Input kg R290 0 85k...

Страница 12: ...12 6 Display Operation Guide 6 1 Main Interface Display and Function 1 Power on Interface 2 Starting up Interface 13 12 11 10 9 8 7 14 15 6 5 4 3 2 1...

Страница 13: ...er tapping this icon 9 is defrosting icon It will display in the defrosting process of the unit 10 is timing mute icon which displays only when activated 11 is timing switch which displays only when a...

Страница 14: ...OFF 1 In shutting down interface on off key is in white status press on off key can start up the machine 2 Instartingupinterface on offkeyisinbluestatus presson offkey canshut downthemachine 6 2 1 Mo...

Страница 15: ...ll not be displayed b If the machine model you purchased has no hot water function the key of hot water mode function will not be displayed In the main interface there are five modes that can be selec...

Страница 16: ...interface to return to the main interface The function setting interface is shown in the figure below Take hot water heating mode for example 1 Tapping 1 the wire controller back to main interface 2...

Страница 17: ...2 Factory parameter Click the key and enter the password to enter the factory parameter settings and status parameters interface 3 Curve key Click this key to view the temperature curve 4 Adjust brig...

Страница 18: ...has been locked the pop up keyboard is shown as following When entering the page of system time setting the system time will be initialized to the time at the moment when the system time setting butt...

Страница 19: ...to enable or disable the mute timer off function 2 The mute timer on setting point select from 0 00 23 59 The mute timer off settingpoint select from 0 00 23 59 3 The status of mute timer on Enable B...

Страница 20: ...ion records the water inlet temperature water outlet temperature tank water temperature and ambient temperature 2 Temperature data is collected and saved every five minutes Timekeeping is made from th...

Страница 21: ...y bar can be dragged or clicked to adjust the brightness of the screen with power down memory 2 Press the back key to return to the previous level and save the brightness setting value 3 The screen ha...

Страница 22: ...to return to the main interface The status interface is shown in the figure below 1 Fault code 2 Fault name 3 Occurrence time of the fault Day an month hour minute second Note Ifthecurrenttemperaturei...

Страница 23: ...the display whether shown locked icon Check the cable Reconnect the power cable and check if it works Heating effect is not good The compressor running low frequency The fan is not running or speed is...

Страница 24: ...Anti freezing Protection Ambient temp 0 C water inlet 2 C It is the protection in winter Once the water temperature up to 15 oC or the ambient temp is higher than 1 oC the error code disappears E032...

Страница 25: ...lure between DSP and PFC Only in single phase unit 1 Check the inverter board connection 2 If no problem replace a new compressor driver board F11 Communication Fault between DSP and Com munication bo...

Страница 26: ...art and check if the motor is running normal or the error happens again 3 Replace a new fan motor F032 DC Fan Motor 2 Failure Pp1 Exhaust Pressure Sensor Fault 1 Detect the exhaust pressure sensor con...

Страница 27: ...V 202109HH01 NOTES...

Страница 28: ...kaisai com...

Отзывы: