background image

25

F01

Compressor activation 
failure

Restart the unit.

 

1. Check the changing process of EEV step, high pressure, low pressure, inlet/outlet 

water temp. 

2. Check the connection of U/V/W between compressor and compressor driver 

board. 

3. Check the compressor resistance.

 

4. Check compressor driver board.

F03

PFC Fault

Restart the unit.

 

1. Check the power supply connection and voltage supply is stable or not. 
2. Replace a new compressor driver board.

F05

DC Bus Over voltage

1. Check the voltage between DCP-IN and DCN-IN, if lower than 300V, the unit will 

get this protection. 

2. Check the input voltage of R/S/T on compressor driver board, if lower than 210V, 

the unit will get this protection. 

3. If they are OK, please replace a new compressor driver board.

F06

DC Bus Under voltage

1. Check the voltage between DCP-IN and DCN-IN, if lower than 300V, it will get this 

protection; 

2. Check the input voltage of R/S/T on compressor driver board, if lower than 210V, 

it will get this protection; 

3. If they are OK, please replace a new compressor driver board

F07

AC Input Under voltage

1. Measure the input voltage of R/S/T of driver board, if lower than 300V, it will get 

this protection. 

2. If it’s OK, replace a new compressor driver board.

F08

AC Input Over current

Only in single phase unit. Restart the unit. Check if there is electric leakage. If not, 

replace a new drive board.

F09

Input voltage sampling 
fault

1. Make sure power supply not lower than 300V or higher than 500V;

 

2. If it’s OK, please replace a new compressor driver board.

F10

Communication Failure 
between DSP and PFC

Only in single phase unit.

 

1. Check the inverter board connection.

 

2. If no problem, replace a new compressor driver board.

F11

Communication Fault 
between DSP and Com-
munication board

1. Please check the inverter board connection.

 

2. If no problem, please replace a new compressor driver board

F12

Communication failure 

between PCB and driver 

board

1. Check the connection between main control board and compressor driver board. 
All of 12V-12V, GND-GND, A-A, B-B should be closed.

 

2. If they are closed, turn on the power, then measure the voltage between 12V and 
GND on compressor driver board, if higher than 15V or lower than 7V, please replace 

a new one compressor driver board.

F13

IPM Overheat Stop

1. Check the fans are running or not.

 

2. Check the installation distance and space.

 

3. Leave enough distance and space to make heat pump have a good transfer 

heating condition. 

4. Clean the finned heat exchanger.

 

5. If they are OK, replace a new compressor driver board.

F15

Input voltage Lacking 
Phase

1. Check the phase of power supply R/S/T to compressor driver board.

 

2. If it’s OK, replace a new compressor driver board.

F16

Compressor weak magne-
tic protection alarm

1. Check the refrigeration system.

 

2. If it’s OK, replace a new compressor driver board.

F17

Temperature fault of drive 
board

1. Check the connection of heat sink temp. sensor.

 

2. Check the resistance of heat sink temp. sensor.

 

3. If they are OK, please replace a new heat sink and heat sink temp. sensor.

F18

IPM Current Sampling 
Fault

1. Check ambient temp. and inlet/outlet water temp.

 

2. Check high/low pressure and discharge temp. and suction temp.

 

3. Check EEV step.

 

4. Check the compressor frequency and current.

 

5. If they are OK, replace a new compressor driver board.

Содержание KHX-14PY3

Страница 1: ...OWNER SMANUAL AIR TO WATER HEAT PUMP EN R290...

Страница 2: ......

Страница 3: ...ENNY TYPU SPLIT Instrukcja obs ugi Dzi kujemy za wyb r naszego produktu Dla zapewnienia prawid owej obs ugi zapoznaj si z instrukcj i przechowuj j do wykorzystania w przysz o ci W przypadku zagubienia...

Страница 4: ...Content 1 Preface 5 2 Safety Instructions 6 3 Features 9 4 Unit Dimension mm 10 5 Parameters 11 6 Display Operation Guide 12 7 Failure List Troubleshooting 23...

Страница 5: ...tions are adhered to at all times to keep the warranty The unit can only be opened or repaired by a qualified installer or an authorized dealer Maintenance and operation must be carried out according...

Страница 6: ...der stand the following information correctly Mark Notes Icon Notes Mark Meaning A wrong operation may lead to death or grievous injury on people A wrong operation may lead to harm to people or loss o...

Страница 7: ...rong or strange smells the power supply needs to be shut off to stop the unit Continue running may cause short circuit or fire Move and Repair Meaning Entrust When the heat pump needs to be moved or i...

Страница 8: ...ANNOT be installed near the flammable gas Once there is any leakage of the gas fire may occur Fix the unit Make sure that the basement of the heat pump is strong enough to avoid any decline or fall do...

Страница 9: ...pump Centralized controlling system can control several units by PC 3 2 Nice Appearance The heat pump is designed with beautiful looking The monoblock one has the water pump included which is very ea...

Страница 10: ...nsion mm 4 1 Models KHX 14PY3 4 2 Models KHX 16PY3 Power line Power line Signal line Signal line Water outlet 1 Water outlet 1 238 363 928 458 540 500 125 1287 1250 975 216 Water inlet 1 Water inlet 1...

Страница 11: ...put Range kW 1 27 4 65 1 90 7 10 Hot Water Current Input Range A 2 4 8 21 3 4 12 5 Max Power Input kW 5 3 9 Max Current Input A 10 5 15 8 Water Flow m3 h 1 7 2 9 Refrigerant Proper Input kg R290 0 85k...

Страница 12: ...12 6 Display Operation Guide 6 1 Main Interface Display and Function 1 Power on Interface 2 Starting up Interface 13 12 11 10 9 8 7 14 15 6 5 4 3 2 1...

Страница 13: ...er tapping this icon 9 is defrosting icon It will display in the defrosting process of the unit 10 is timing mute icon which displays only when activated 11 is timing switch which displays only when a...

Страница 14: ...OFF 1 In shutting down interface on off key is in white status press on off key can start up the machine 2 Instartingupinterface on offkeyisinbluestatus presson offkey canshut downthemachine 6 2 1 Mo...

Страница 15: ...ll not be displayed b If the machine model you purchased has no hot water function the key of hot water mode function will not be displayed In the main interface there are five modes that can be selec...

Страница 16: ...interface to return to the main interface The function setting interface is shown in the figure below Take hot water heating mode for example 1 Tapping 1 the wire controller back to main interface 2...

Страница 17: ...2 Factory parameter Click the key and enter the password to enter the factory parameter settings and status parameters interface 3 Curve key Click this key to view the temperature curve 4 Adjust brig...

Страница 18: ...has been locked the pop up keyboard is shown as following When entering the page of system time setting the system time will be initialized to the time at the moment when the system time setting butt...

Страница 19: ...to enable or disable the mute timer off function 2 The mute timer on setting point select from 0 00 23 59 The mute timer off settingpoint select from 0 00 23 59 3 The status of mute timer on Enable B...

Страница 20: ...ion records the water inlet temperature water outlet temperature tank water temperature and ambient temperature 2 Temperature data is collected and saved every five minutes Timekeeping is made from th...

Страница 21: ...y bar can be dragged or clicked to adjust the brightness of the screen with power down memory 2 Press the back key to return to the previous level and save the brightness setting value 3 The screen ha...

Страница 22: ...to return to the main interface The status interface is shown in the figure below 1 Fault code 2 Fault name 3 Occurrence time of the fault Day an month hour minute second Note Ifthecurrenttemperaturei...

Страница 23: ...the display whether shown locked icon Check the cable Reconnect the power cable and check if it works Heating effect is not good The compressor running low frequency The fan is not running or speed is...

Страница 24: ...Anti freezing Protection Ambient temp 0 C water inlet 2 C It is the protection in winter Once the water temperature up to 15 oC or the ambient temp is higher than 1 oC the error code disappears E032...

Страница 25: ...lure between DSP and PFC Only in single phase unit 1 Check the inverter board connection 2 If no problem replace a new compressor driver board F11 Communication Fault between DSP and Com munication bo...

Страница 26: ...art and check if the motor is running normal or the error happens again 3 Replace a new fan motor F032 DC Fan Motor 2 Failure Pp1 Exhaust Pressure Sensor Fault 1 Detect the exhaust pressure sensor con...

Страница 27: ...V 202109HH01 NOTES...

Страница 28: ...kaisai com...

Отзывы: