59
9.2.5 Open circuit or short circuit of temperature sensor diagnosis and solution
(E4/E5/F1/F2/F3)
Check the connections
between temperature
sensor and PCB. Are
the connections good?
Correct the connections.
No
Yes
Yes
Replace indoor or outdoor PCB.
Replace the sensor and
c h e c k i f t h e p r o b l e m
happen again?
Check the resistance value
of the sensor via table1
and table 2, is it normal?
No