9.2.3 Zero crossing detection error diagnosis and solution(E2)
Check if the connections and
power supply is normal?
Correct the connections. Turn on the
unit when the power supply is good.
No
Yes
Indoor main PCB is
defective. Replace indoor
main PCB.
9.2.4 Fan speed has been out of control diagnosis and solution (E3/F5)
Shut off the power supply
and turn it on 5 seconds
later. Is it still displaying
the error code?
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.
No
Yes
Check whether the main PCB is
normal through index 2?
Yes
Yes
Check whether the fan
motor is normal through
index 1?
Yes
Replace the fan
motor
Replace the
main PCB.
The
malfunction is
solved?
No
No
If the
malfunction is
still existing,
replace the
main PCB
No
Содержание KFU-09HRDN1-QRC8W
Страница 1: ...12F INVERTER SERIES Service Manual 2013 12FSI A 1310...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit KFU 09HRDN1 QRC8W KFU 09HRDN1 QRC8GW...
Страница 14: ...14 KFU 24HRDN1 QRC8GW...
Страница 15: ...15 5 2 Outdoor Unit KOB 09HFN1 QRC8W KOB 09HFN1 QRD0GW...
Страница 16: ...16 KOB 12HFN1 QRC8W KOC 18HFN1 QRC4W...
Страница 17: ...17 KOB1 12HFN1 QRD0GW KOZ 18HFN1 QRD0GW KOC1 18HFN1 QRC8GW...
Страница 18: ...18 KOF 24HFN1 QRC8W KOF 24HFN1 QRD0GW KOF 24HFN1 QRC8GW...
Страница 28: ...28 5 Disconnect the charge hose from the vacuum pump...
Страница 30: ...30 Be sure to check for gas leakage...