10.3.3.10 IPM module protection (ODU P6) 

 

 

Check whether the voltage range 
of P-N on IPM module is normal? 

  

 

No 

DC277-356V for 18-28KBtu/h; 

DC277-410V for  36-42KBtu/h 

 

Check whether the input 
power supply is correct? 

208-230V, 1N, 60Hz 

 

Regulate it to correct, then 

No 

check whether the system 

can work normally? 

 

Yes 

 
 

Yes 

No 

 

Check whether the connecting 

line between main board and 

  

No 

the IPM module is connected 

tightly 

 

Connect it tightly, 

check ok or not? 

 

 

Check whether the 

power supply line is 

  

No 

connected correctly and 

tightly 

 
 
 

Connect it correctly 

and tightly, check ok 

or not? 

 

Yes 

No 

 

Yes 

No

 

 

Check whether the connecting 

  

 

 

  

 

line of the compressor is 

 

 

No 

connected correctly or tightly 

 

Connect it well, check 

ok or not? 

 

 

Check whether the lines       

  

 
 

 

Connect it tightly, 

in E-part box are 

connected tightly 

No 

check ok or not? 

 

Yes 

No 

 

 

Replace the IPM module, 

check whether the system can 

work normally? 

 
 
 

No 

 

Yes 

No 

 

 

Check whether the bridge rectifiers are 

normal? Use the multimeter to measure 

the resistance between each two 

terminals, check whether there is the 

condition that value of resistance is 0 

No 

 
 

Check if the outdoor fan 

runs properly or the outdoor 

unit ventilation is good. 

 
 

 

No 

 
 
 
 

Replace the main board; check 

whether the system can work 

normally? 

 
 

Yes 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Yes 

Yes 

 

Yes 

 

 

Check  whether  the  connecting  line  of 
every  reactor  is  normal?  If  the  line  is 
broken, the resistance of the two ports is 

models  except  for K4OA-36HFN1- 

Q,K4OD-28HFN 

K5OC-36HF

 

Check  whether  the  PFC module 
broken   (for   K4OA-36HFN,K4OD- 

No 

28HFN, 

K5OC-36HFN1,K50D- 

42HFN) 

 

 

No 

 

 

 

Yes 

Replace the compressor, check 

whether the system can work 

normally? 

 

Yes 

 

Trouble is solved 

Replace the bridge rectifiers 

IPM module protection 

Replace the connecting line or 

reactor or replace the PFC 

module(for K4OC-36HRFN 

K50D-42HFN 

Check whether the resistance of 
the fan motor is normal. If not, 
replace  the  fan  motor. 

For 

other 

models,  r

efer  to  the 

solution  of  fan  speed  has 
been 

out 

of 

control 

malfunction  .  F  i  nd  out  the 
cause and have it solved. 

Содержание K2OC-18HFN32

Страница 1: ...SERVICE MANUAL R32 SUPER DC INVERTER MULTI TYPE K2OC 18HFN32 K3OE 27HFN32 K4OB 36HFN32 K5OD 42HFN32 DC MULTI OUTDOOR UNITS...

Страница 2: ...t for installation 14 8 2 Connecting the cables 14 8 3 Pipe length and the elevation 14 8 4 Installation for the first time 15 8 5 Adding the refrigerant after running the system for many years 18 8 6...

Страница 3: ...formation of Outdoor Units Model name Dimension mm Compressor K2OC 18HFN32 800x333x554 KSM135D23UFZ K3OE 27HFN32 845x363x702 KTF235D22UMT K4OB 36HFN32 946x410x810 KTF310D43UMT K5OD 42HFN32 946x410x810...

Страница 4: ...t cabinet Valve protection cover Discharge pipe temperature protection 2 Features the heating efficiency at operation mode It protects the valves and prevents water from dripping Power relay control L...

Страница 5: ...4 3 Dimensions A D B Model Unit mm W D H W1 A B K2OC 18HFN32 800 333 554 860 514 340 K3OE 27HFN32 845 363 702 923 540 350 K4OB 36HFN32 946 410 810 1034 673 403 K5OD 42HFN32 946 410 810 1034 673 403...

Страница 6: ...o r C o m p re s s o r T 5 D is c h a rg e te m p s e n s o r C O O L I N G H E A T I N G 4 2 Refrigeration circuit drawing of inverter 1 drive 3 type E X V A C A P I L L A R Y A L I Q U I D V A L V E...

Страница 7: ...h a rg e te m p s e n s o r C O O L IN G H E A T IN G 4 4 Refrigeration circuit drawing of inverter 1 drive 5 type IN D O O R O U T D O O R E X V A C A P I L L A R Y A L I Q U I D V A L V E A E X V B...

Страница 8: ...7 5 Wiring diagram K2OC 18HFN32...

Страница 9: ...8 Note S 1 S 2 areusedinothertypeofmodels Theydon tneedtobeconnectedinmultimodels K3OE 27HFN32...

Страница 10: ...9 K4OB 36HFN32...

Страница 11: ...10 K5OD 42HFN32...

Страница 12: ...7 9 24 9 9 18 12 12 18 7 7 7 9 7 7 12 12 7 9 12 1 8 9 9 12 18 1 2 7 12 12 1 2 7 7 1 2 7 12 1 2 9 9 24 12 12 24 7 7 7 12 7 7 12 18 7 9 18 1 8 9 12 12 1 2 1 8 7 18 12 1 8 7 7 1 8 7 12 1 8 9 12 1 2 12 1...

Страница 13: ...18 18 7 9 9 7 18 18 9 12 24 9 12 7 9 12 9 9 9 9 18 18 Four Unit 7 7 7 7 7 7 9 18 7 9 9 12 7 12 12 12 9 9 12 12 7 7 7 9 7 7 9 24 7 9 9 18 7 12 12 18 9 9 12 18 7 7 7 12 7 7 12 12 7 9 9 24 7 12 12 24 9 9...

Страница 14: ...Unit 7 7 7 7 7 7 7 7 9 18 7 7 9 9 24 7 9 9 12 12 9 9 9 12 12 7 7 7 7 9 7 7 7 9 24 7 7 9 12 18 7 9 9 12 18 9 9 9 12 18 7 7 7 7 12 7 7 7 12 18 7 7 12 12 12 7 9 12 12 12 9 9 12 12 12 7 7 7 7 18 7 7 7 18...

Страница 15: ...14 Microphone H 7 Sound Levels Outdoor Unit 1 0m Note H 0 5 height of outdoor unit Model Noise Power dB A Noise level dB A K2OC 18HFN32 56 53 K3OE 27HFN32 65 59 K4OB 36HFN32 68 63 K5OD 42HFN32 71 62...

Страница 16: ...the side panel of the unit Please refer to the nameplate before selecting the cable fuse and switch 8 3 Pipe length and the elevation Maximum piping length and height difference 1 drive 2 1 drive 3 1...

Страница 17: ...iquid 6 35 1 4 5 Gas 9 52 3 8 4 12 7 1 2 1 8 4 Installation for the first time Air and moisture in the refrigerant system have undesirable effects as below Pressure in the system rises Operating curre...

Страница 18: ...please check if there are some leakage points Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump Confirm that the gauge needle does not move approximately...

Страница 19: ...harge set to purge the air be careful of the liquid refrigerant 3 Put the charging cylinder onto the electronic scale and record the weight 4 Operate the air conditioner at the cooling mode 5 Open the...

Страница 20: ...careful of the liquid refrigerant 3 Put the charging cylinder onto the electronic scale and record the weight 4 Operate the air conditioner at the cooling mode 5 Open the valves Low side on the charge...

Страница 21: ...rvice port 3 Air purging of the charge hose Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly 4 Set the 2 way valve to t...

Страница 22: ...pumping 50 minutes please check if there are some leakage points Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump Confirm that the gauge needle does not...

Страница 23: ...position 2 Connect the vacuum pump to 3 way valve s service port 3 Evacuation for approximately one hour Confirm that the compound meter indicates 0 1Mpa 4 Close the valve Low side on the charge set t...

Страница 24: ...charge set and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant or can be charged with a little at a time approximately 150g each time...

Страница 25: ...y function In standby the LED displays In compressor operation the LED display the running frequency In defrosting mode The LED displays dF or alternative displays between running frequency and dF eac...

Страница 26: ...A evaporator outlet temperature T2BA If the temperature is lower than 9 the digital display shows 9 If the temperature is higher than 70 the digital display shows 70 If the indoor unit is not connecte...

Страница 27: ...y T2 Bit3 Frequency limit caused by T3 Bit2 Frequency limit caused by T5 Bit1 Frequency limit caused by current Bit0 Frequency limit caused by voltage 43 Average value of T2 Sum T2 value of all indoor...

Страница 28: ...urrent limit is same as range of T4 limited frequency Cooling mode T4 C o o lZ o n e 1 Heating mode T4 9 5 5 Indoor outdoor units communication protection If the indoor units cannot receive the feedba...

Страница 29: ...equency for setting time and then resume to former frequency 2 The EXV will keep 300p while the indoor units will keep the current running mode If the outdoor ambient is higher than setting frequency...

Страница 30: ...Water level alarm EE X 8 Overcurrent protection For some units F0 O 1 Open or short circuit of T4 temperature sensor F1 O 2 Open or short circuit of T3 temperature sensor F2 O 3 Open or short circuit...

Страница 31: ...or PCB and display board Eb Overload current protection F0 Outdoor ambient temperature sensor T4 open circuit or short circuit F1 Condenser coil temperature sensor T3 open circuit or short circuit F2...

Страница 32: ...r of sensor is defective F3 No C Indoor unit coil outlet temperature sensor or connector of sensor is defective F4 No D Indoor unit coil outlet temperature sensor or connector of sensor is defective F...

Страница 33: ...it 10 3 1 1 Indoor EEPROM malfunction Yes EEPROM An electrically erasable programmable read only memory whose contents can be erased and reprogrammed using a pulsed voltage Power off then restart the...

Страница 34: ...the all indoor units Is IPM powerLED oroperating LED lamp No On Refer PIC2 Yes Power on by remote controller IIs it still displaying the error code after 3 minutes Is main board lampon ReferPIC3 Is t...

Страница 35: ...34 Pic 1 check the voltage of N to S Vs is it moving alternately between positive value and negative value Pic 2 IPM or outdoor main PCB Pic 2 IPM or outdoor main PCB Power Self Check Operating...

Страница 36: ...35 PIC3 Main board LED when power on and unit standby PIC 4 check point button Press 1 time for check how many indoor units are connected...

Страница 37: ...e replaced 2 Indoor DC fan motor control chip is inside fan motor Power on and when the unit is in standby measure the voltage of pin1 pin3 pin4 pin3 in fan motor connector If the value of the voltage...

Страница 38: ...r Signal Voltage 1 Red Vs Vm 280V 380V 2 3 Black GND 0V 4 White Vcc 14 17 5V 5 Yellow Vsp 0 5 6V 6 Blue FG 14 17 5V For other types NO Color Signal Voltage 1 Red Vs Vm 192V 380V 2 3 Black GND 0V 4 Whi...

Страница 39: ...No Yes Yes Yes Repllace the iindoor maiin PCB Repllace the water pump If mallfunctiion iisstiill ll not sollved Checktheconnectiions between temperature sensor and PCB Are the connectiionsgood Yes Is...

Страница 40: ...ecting line between main board and the PFC No module IPM module is connected tightly 10 3 1 7 Communication error between the indoor PCB and display board Yes Yes Yes Replace the Display board Replace...

Страница 41: ...dule protection 10 3 3 For the outdoor unit 10 3 3 1 Outdoor EEPROM malfunction ODU E0 Yes EEPROM An electrically erasable programmable read only memory whose contents can be erased and reprogrammed u...

Страница 42: ...board and the main board is it connected good Yes No Yes Reconnect and retry Is error still display No No Replace IPM board and then check whether the system can run normally Yes No Replace outdoor m...

Страница 43: ...Replace bridge rectifiers and then check whether the system can run normally Yes Yes No Replace IPM board and then check whether the system can run normally Yes No Trouble is solved Replace outdoor ma...

Страница 44: ...showing in below table the PCB must have problems and need to be replaced DC motor voltage input and output NO Color Signal Voltage 1 Red Vs Vm 140V 380V 2 3 Black GND 0V 4 White Vcc 13 5 16 5V 5 Yell...

Страница 45: ...eck iifthe outdoor uniit ventiillatiion iis good NO Yes Check iifthe outdoor fan runs properlly No Yes Check whether the heat exchanger iis diirty Yes No Repllace outdoor maiin board No Check whether...

Страница 46: ...normall the vallue iis o o o No Yes Check whether theoutdoor ambiient temperature iistoo llow Yes Low pressure protection Check whether valve core ofhighpressurevalveis opened No Yes Check iifthe iind...

Страница 47: ...refrigerant to blow pipe vacuumize and charge the refrigerant again Judge 1 Check whether the input current of the power supply wire is higher than max protection current value Yes Check whether the r...

Страница 48: ...temp sensor and PCB accordiing to wiiriing diiagrams No Temperatureprotectionof compressor discharge Correct the wiiriing connectiion Stop lleakiing and add refriigerant 10 3 3 8 Temperature protecti...

Страница 49: ...ix 1 No Yes Check whetther tthe outtdoor ambiientt ttemperatture iis hiigher tthan 50 Yes No Checkiiftheoutdoor uniit ventiillatiion iis good No Yes Check iifthe outdoor fan runs properlly No Yes Chec...

Страница 50: ...No Check whether the bridge rectifiers are normal Use the multimeter to measure the resistance between each two terminals check whether there is the condition that value of resistance is 0 No Check i...

Страница 51: ...nit get warm Potential causes Faulty EXV Wire and piping connected in reverse Check of EXV please refer to part 5 in 10 4 Trouble Criterion Of Main Parts Automatic correction of wiring piping error Pr...

Страница 52: ...e the resistance value with a tester Temperature Sensors Room temperature T1 sensor Indoor coil temperature T2 sensor Outdoor coil temperature T3 sensor Outdoor ambient temperature T4 sensor Compresso...

Страница 53: ...1 34105 116 0 40060 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 37956 1 37 1988 39 5 39689 79 1 21330 119 0 36954 0 35 2024 40 5 17519 80 1 17393 120 0 35982 1 33...

Страница 54: ...9 5 234 9 35 35 78 75 8 084 115 2 422 4 222 8 36 34 32 76 7 82 116 2 357 3 211 4 37 32 94 77 7 566 117 2 294 2 200 7 38 31 62 78 7 321 118 2 233 1 190 5 39 30 36 79 7 086 119 2 174 0 180 9 40 29 15 80...

Страница 55: ...54 2 Compressor checking Measure the resistance value of each winding by using the tester Position Resistance Value KSM135D23UFZ KTF235D22UMT KTF310D43UMT Blue Red 1 72 20 0 75 20 0 65 20...

Страница 56: ...tester Normal resistance value Red Black Several M Red Black Several M P N U N U V V W W Red 4 4 way valve 1 Power on use a digital tester to measure the voltage when the unit operates in cooling it...

Страница 57: ...56 5 EXV check Disconnect the connectors Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange 6 5 4 3 2 1 Red Brown Blue Orange Yellow White...

Отзывы: