If you will install the unit on a wall-mounted 

bracket 

, do the following:

 CAUTION

Before installing a wall-mounted unit, make 

sure that the wall is made of solid brick, 

concrete, or of similarly strong material. 

The

 

wall must be able to support at least four 

times the weight of the unit.

1. 

Mark the position of bracket holes based on 

dimensions in the Unit Mounting Dimensions 

chart.

2. 

Pre-drill the holes for the expansion bolts.

3. 

Clean dust and debris away from holes.

4. 

Place a washer and nut on the end of each 

expansion bolt.

5. 

Thread expansion bolts through holes in 

mounting brackets, put mounting brackets 

in position, and hammer expansion bolts into 

the wall.

6. 

Check that the mounting brackets are level.

7. 

Carefully lift unit and place its mounting feet 

on brackets.

8. 

Bolt the unit firmly to the brackets.

TO REDUCE VIBRATIONS OF WALL-
MOUNTED UNIT

If allowed, you can install the wall-mounted 

unit with rubber gaskets to reduce vibrations 

and noise.

Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by 

an electrical wiring cover on the side of the unit. 

A comprehensive wiring diagram is printed on 

the inside of the wiring cover.

BEFORE PERFORMING 
ELECTRICAL WORK, 

 

READ THESE REGULATIONS

1. 

All wiring must comply with local and 

national electrical codes, and must be 

installed by a licensed electrician.

2. 

All electrical connections must be made 

according to the Electrical Connection 

Diagram located on the side panels of the 

indoor and outdoor units.

3. 

If there is a serious safety issue with the 

power supply, stop work immediately. Explain 

your reasoning to the client, and refuse 

to install the unit until the safety issue is 

properly resolved.

4. 

Power voltage should be within 90-110% of 

rated voltage. Insufficient power supply can 

cause electrical shock or fire.

5. 

If connecting power to fixed wiring, install a 

surge protector and main power switch with 

a capacity of 1.5 times the maximum current 

of the unit.

6. 

If connecting power to fixed wiring, a switch 

or circuit breaker that disconnects all poles 

and has a contact separation of at least 1/8in 

(3mm) must be incorporated in the fixed 

wiring. The qualified technician must use an 

approved circuit breaker or switch.

7. 

Only connect the unit to an individual branch 

circuit outlet. Do not connect another 

appliance to that outlet. 

8. 

Make sure to properly ground the air 

conditioner.

9. 

Every wire must be firmly connected. Loose 

wiring can cause the terminal to overheat, 

resulting in product malfunction and possible 

fire.

10. 

Do not

 let wires touch or rest against 

refrigerant tubing, the compressor, or any 

moving parts within the unit.

11. 

If the unit has an auxiliary electric heater, it 

must be installed at least 1 meter (40in) away 

from any combustible materials.

Outdoor Unit 

Installation

Содержание Forest Series

Страница 1: ...arefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference SPLIT TYPE ROOM AIR CONDITIONER Installation Manual Forest Series All Model Nu...

Страница 2: ...4 Prepare refrigerant piping 14 5 Connect drain hose 15 6 Connect signal cable 17 7 Wrap piping and cables 18 8 Mount indoor unit 18 Outdoor Unit Installation 20 8 1 Select installation location 20 2...

Страница 3: ...e 25 2 Remove burrs 26 3 Flare pipe ends 26 4 Connect pipes 27 Air Evacuation 29 1 Evacuation Instructions 29 2 Note on Adding Refrigerant 30 Electrical and Gas Leak Checks 31 Test Run 32 European Dis...

Страница 4: ...ge electrical shock or fire 2 Installation must be performed according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installa...

Страница 5: ...e unit it may cause fire Do not operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit 1 The product...

Страница 6: ...0 Remote controller holder Dry battery AAA LR03 Seal Drain joint Mounting plate 1 Accessories The air conditioning system comes with the following accessories Use all of the installation parts and acc...

Страница 7: ...ll be installed operated and stored in a room with a floor area larger than 4m Appliance shall not be installed in an unvertilated space if that space is smaller than 4m For R290 refrigerant models th...

Страница 8: ...mary Indoor Unit 2 Installation Overview Select Installation Location Page 11 Attach Mounting Plate Page 12 Drill Wall Hole Page 12 Determine Wall Hole Position Page 12 1 2 3 4 12cm 4 75in 2 3m 90 55i...

Страница 9: ...stallation Overview Mount Indoor Unit Page 18 STEP 8 Wrap Piping and Cable not applicable for some locations in the US Page 18 Connect Piping Page 25 Connect Wiring Page 17 Prepare Drain Hose Page 14...

Страница 10: ...ed in accordance with the requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal...

Страница 11: ...Strong enough to support the weight of the unit A location at least one meter from all other electrical devices e g TV radio computer DO NOT install unit in the following locations Near any source of...

Страница 12: ...ameter holes in the wall and insert the sleeve anchors provided Then secure the mounting plate to the wall by tightening the screws directly into the clip anchors Step 3 Drill wall hole for connective...

Страница 13: ...8in 45mm 1 7in 101 6mm 4in 183 6mm 7 2in 123 6mm 4 86in 715mm 28in 805mm 31 7in 117 5mm 4 62in 115 6mm 4 55in 233 1mm 9 17in 398mm 15 67in 398mm 15 98in Left rear wall hole 65mm 2 5in Right rear wall...

Страница 14: ...rs if the plastic panel is too difficult to remove by hand 3 Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6in of the refrigerant piping This serves two purposes To...

Страница 15: ...ve the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly NOTE ON DRAIN HOSE PLACEMENT Make sure to arrange the drain hose according to...

Страница 16: ...tch with a capacity of 1 5 times the maximum current of the unit 6 If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1...

Страница 17: ...ions of the fuse 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of signal cable to reveal about 40mm 1 57in of the wires inside b Strip the insulation...

Страница 18: ...do not intertwine or cross the signal cable with any other wiring 2 Using adhesive vinyl tape attach the drain hose to the underside of the refrigerant pipes 3 Using insulation tape wrap the signal w...

Страница 19: ...tructions 4 Keep pipe connection point exposed to perform the leak test refer to Electrical Checks and Leak Checks section of this manual 5 After the leak test wrap the connection point with insulatio...

Страница 20: ...tial requirements shown in Installation Space Requirements Fig 4 1 Good air circulation and ventilation Firm and solid the location can support the unit and will not vibrate Noise from the unit will n...

Страница 21: ...of outdoor unit If the drain joint comes with a rubber seal see Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain...

Страница 22: ...ting feet Prepare the installation base of the unit according to the dimensions below A W B D Air inlet Air outlet Air inlet A W B D Air inlet Air outlet Air inlet Fig 4 5 Outdoor Unit Installation WH...

Страница 23: ...al codes and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor u...

Страница 24: ...below the terminal block and place it to the side 4 Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal 5 After che...

Страница 25: ...them properly This will ensure efficient operation and minimize the need for future maintenance For R32 R290 refrigerant models the pipe connection points must be placed outside of room 1 Measure the...

Страница 26: ...to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction because you can...

Страница 27: ...t See Fig 5 7 Indoor unit tubing Flare nut Pipe 2 Tighten the flare nut as tightly as possible by hand 3 Using a spanner grip the nut on the unit tubing 4 While firmly gripping the nut on the unit tub...

Страница 28: ...a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNER TO GRIP MAIN BODY OF VALVE Torque from tightening the flare nut can snap off other parts...

Страница 29: ...rigerant Piping Connection section of this manual Check to make sure all wiring is connected properly Evacuation Instructions Before using the manifold gauge and vacuum pump read their operation manua...

Страница 30: ...e port high pressure low pressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against th...

Страница 31: ...the unit immediately and call a licensed electrician to find and resolve the cause of the leakage Note This may not be required for some locations in the US Gas Leak Checks There are two different me...

Страница 32: ...oller to turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function...

Страница 33: ...ng remote control return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process I...

Страница 34: ...ptions Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The manufacturer w...

Страница 35: ...ire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable ref...

Страница 36: ...ties are advised Initial safety checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking that there no live electrical components and wi...

Страница 37: ...shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This proc...

Страница 38: ...not exceed the maximum working pressure of the cylinder even temporarily j When the cylinders have been filled correctly and the process completed make sure that the cylinders and the equipment are re...

Страница 39: ...are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associa...

Страница 40: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details CS397I AF R32...