20
For Console:
In heating mode, indoor fan can be selected as high, medium, low and auto. The anti-cold- wind function has
the priority.
When the compressor is running, the indoor fan is controlled as below:
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
Auto fan action in heating mode:
-1.0
-2.0
-3.0
-4.0
0.0
T1-Ts+¦ ¤
T
L
(H+-L)*0.4+L
(H+-L)*0.6+L
-5.0
-6.0
-6.5
H+
(H+-L)*0.8+L
(H+-L)*0.6+L
(H+-L)*0.2+L
For other models:
Indoor Fan can be set at HIGH/MED/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Auto wind in heating mode
-3.5
T1-Ts-
¦ ¤
T
-4
High
Low
-5
Medium
-4.5