Technical Specification
1 --- 2
Mains voltage
460 V 3---phase
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Full load current FLA
19.6 A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Frequency
60 Hz
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended main disconnect fuses
(Dual element or time---delay)
30 A
. . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended power supply cable (CU multi---stranded)
cross ---section
8 AWG
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum dual element time -- delay fuses are selected according to
2002 N.E.C. Article 240 -- 6, 430 -- 52 and Tables 430 -- 52, 430 -- 148 &
150.
Select multi-- strand copper core wire at 40
C ambient temperature
according to 2002 N.E.C. 110 -- 14(c), 220 -- 3, 310 -- 15, Table 310 -- 16,
430 -- 6, 430 -- 22, 430 -- 24 and Tables 430 -- 148 & 150.
For electrical power supply please refer to chapter 2.3 and 6.3
1.5
Set Point of the Safety Relief Valve
110 psig Compressor Unit --- Activating pressure
140 psig
. . . . . . . .
125 psig Compressor Unit --- Activating pressure
155 psig
. . . . . . . .
145 psig Compressor Unit --- Activating pressure
175 psig
. . . . . . . .
190 psig Compressor Unit --- Activating pressure
230 psig
. . . . . . . .
1.6
Installation Requirements
Max. height above sea level of the place of installation
3000 ft.
. .
(for all heights above please contact authorized KAESER distributor)
Min. ambient temperature
40
E
F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Max. ambient temperature
105
E
F
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Min. cooling air/inlet air temperature
40
E
F
. . . . . . . . . . . . . . . . . . . .
Max. cooling air/inlet air temperature
105
E
F
. . . . . . . . . . . . . . . . . . .
Air inlet opening
5.4 sq.ft.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust air for solution A (see chapter 6.1):
Forced ventilation with exhaust ventilator
2350 cfm at static pressure of
. . . . . . . . . . . . . .
0.4 inches water column
Exhaust air for solution B (see chapter 6.1):
Exhaust air used for space heating:
Heating duct w x h
14” x 20”
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7
Oil Capacities
Total oil capacities
3.17 gal
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
After oil change or after long period of storage
Quantity required for prelubrication of the airend
0.5 quart
. . . . . . . . .
(Refer to chapter 7.8.1)
Attention!
Содержание SK 19
Страница 10: ...Technical Specification 1 6 ...
Страница 19: ...Construction and Operation 5 15 ...
Страница 20: ...Construction and Operation 5 16 ...
Страница 64: ...Appendix 11 60 11 Appendix 11 1 Wiring Diagram ...
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ...Appendix 11 77 11 2 Spare Parts List ...
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ......