ACCESSING PARAMETER MENU:

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

+

SET

SET

Push the SET button 
during 3 seconds.

SET

Return time 
                   

( r - t )

return time from error
      00,5 – 99,9 (sec.)

Locking Counter 
                     

(L - C)

[oto, (001–010 pieces)]
oto: function is disabled

Locking Time
                    

(L – t )

001 – 060 (minutes)

          

quit

    Return from 
    VOLTAGE Menu

    Return from 
    CURENT Menu

Over Voltage

                     ( o – U)

       phase - phase
          390 - 460 (V)
oFF:function is disabled

Under Voltage

                     ( u – U)

phase - phase
        300 - 370 (V)
oFF:function is disabled

Unbalance 

for Voltage

                       ( unb )

          0,05 – 0,40 
          (5% - 40% )
oFF:function is disabled

Delay Time

 

for Voltage

                    ( t - 1)

     00,1 – 99,9  (sec.)  

Delay Time

 

for Frequency

                    ( t - 2)

     00,1 – 99,9  (sec.)  

Over Frequency

( o – F )

[(u-F) + 0,4] ≤...≤ 70 Hz
oFF:function is disabled

Under Frequency

( u – F )

40 Hz  ≤...≤  [(o-F) – 0,4]
oFF:function is disabled

            Accessing 
             

Voltage

            Parameter

            Accessing 
             

Current

            Parameter

Current transformer
       Primer value
          Ct       Ct
        000      001
        005  –  000   A
       ( 5 – 1000 ) A

Over Current

                     ( o – C)

oFF:function is disabled

Hysteresis Value

( hYS )

00.3(3%) – 0.50 (50%)

  Delay Time

 

  for Current 

( d - t)

         

     (0,1 – 60 sec.)

Start Delay Time

 

                    ( Sdt )

        (0,1 – 60 sec.)

oFF:function is disabled

Very Over Current 
      Coefficient
                      (VOC)

VOC = 2,1 - 6,0

oFF:function is disabled

Under Current

                     ( u – C)

oFF:function is disabled

Unbalance 

for Current

( unb )

  0,05 – 0,40  (5% - 40%)
oFF:function is disabled

Over Current 
  Coefficient
                      (OC)

OC = 1,1 - 2,0

oFF:function is disabled

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

SET

Lock :

 

Locking function for 
currents.

on  :

 function is inabled

oFF:

 function is disabled

+