Umax

Umin

Under Voltage

Over Voltage

L1,L2,L3

Normal

Normal

Over and Under Voltage :  (o-U),(u-U)

Under voltage (u-U)   it can adjusted between Umin= (300 – 370 V).
Over voltage    (o-U) it can adjusted between   Umax=(390 – 460 V).
If the voltage drops below the adjusted under voltage limit, when 

u-U 

shows

 

on the screen and device switch off its output contact end of the  

t-1 time Normal LED  turned on .In this case 

u-U 

warn appears on the 

screen.
If the voltage exceed the adjusted over voltage limit, Normal LED 
turned off and output relay switch off. In this case 

o-U

 

warn

 

appers on

 

its screen.
Hysteresis is 6 V.

I(A)

Re

t

t

Sdt 

d-t

r-t 

d-t

r-t 

o-C

u-C

%hYS

%hYS

2.6 Asymmetric Current Protection:

It can be set by the user between 5% and 40%. It controls the 
asymmetric that may occur in the current of the three phases. That 
may occur when one of the phases' voltage is low and the other one
is high. That may cause asymmetric current in the motor's bobbin. 
This way the motor's bobbin is protected. Furthermore it protects the 
motor from missing phase or a possible unplugged or cut wiring.
If  the unbalance between the phases' current exceeds the adjusted 
value the switch off occurs after t-1 delay.
If the current unbalance exceed the adjusted value, Normal LED 
turned off and output relay switch off. In this case 

ubC

 

warn

 

appears 

on

 

its screen.

This function can be disable if 

ubC

 value = 000 (oFF)

Over and Under Current :  (o-C),(u-C)

Under Current (u-C)   
Over Current   (o-C)  
When the current of the protected system goes below the adjusted 
value it switches off its output contact after 

d-t 

delay.

Normal LED turn off  and relay switch off its contact .In this case 

u-C

 

warn appears

 

on display.

When any current passing through any phase of the protected system 
exceeds the adjusted value the device switches off its output contacts 
after a proper time (

d-t

).Normal LED turn off  and relay switch off its 

contact .In this case 

o-C

 

warn appears

 

on display.

NOTE: 

Under current protection set value with its hysteresis must not 

overlap with over current protection set value with its hysteresis or, the 
under current protection set value must not be higher than the over 
current protection set value.

VOC

OC

r-t 

r-t 

Re

t

t

t-2

(o-F)

(u-F)

r-t

t-2

r-t

55 Hz

45 Hz

Under Frequency

Over Frequency

L1,L2,L3

Normal

Normal

f(Hz)

Start delay time: Sd-t 

It can be set between 1 and 60 seconds.It is used to prevent the switch 
off from occurance because of the motor's inrush current.
This function can be disable if Sd-t value = 000 (oFF)

Return Time : r-t

it shows the delay time that device will wait to switch on its output relay 
when failure ends after a switch off. It can be set between 0,5 and 99,9 
seconds.

Very Over Current Coefficient : VOC (

Current Very Sudden Switch 

Off Protection)
It can be set by the user between 2,1 and 6. 
When the current value exceeds the adjusted value within the start 
delay time, the device switches off, its output contact immediately.
Very Over Current value = (o – C) x (VOC)
This function can be disable if VOC = 000 (oFF)

Over Current Coefficient : OC (

Current Sudden Switch Off Protection)

It can be set by the user between 1,1 and 2. 
When the current value exceeds the adjusted value without the start 
delay time, the device switches off, its output contact immediately.
Over Current value = (o – C) x (OC)
This function can be disable if OC = 000 (oFF)

Over  and/or Under Frequency Protection : ( 40 – 70 Hz )

Under Frequency be able to set between

(u-F)

  = 40 Hz ...[(o-F) -0,4] 

Over Frequency  be able to set between 

(o-F)

  =[(u-F) + 0,4]...70 Hz 

If required , it can be set  only under frequency or only over frequency 
protection  as well as both of protection can be disabled.
If  o-F = 55 Hz   and    u-F = oFF   set, device works as over 
frequency protector only. (if system frequency above  55 Hz, under 
screen displays  

o-F

  warning and end  of  time t-2 relay switch off  its 

output contact )
if  o-F = oFF  and  u-F = 45 Hz  set , device works as under 
frequency protector only . (if system frequency below  45 Hz, under 
screen displays  

u-F

 warning  and end of  time 

t-2

  relay switch off its 

out contact.)
if o-F = oFF   and  u-F = oFF  set, frequency protection is disabled. 

LOCKING FUNCTION : 

It can be controlled by two parameters. Locking time and 
Locking counter. If  the number of opening reaches the adjusted 
locking counter withing the adjusted locking time then device 
switch off  its contact and locks its functions until the user 
pressed  

Reset 

button. 

If  the locking counter is adjusted to 

oto

 then this function is 

disable and device never locks itself.

L-t : Locking Time 

( 001 – 060 min. )

It is well know the frequently occurring faults may damage 
system. For that the device when number of faults reaches the 
adjusted locking number within this locking time. This way the 
system is protected and user has chance to investigate the 
problem. 

L-C : Locking Counter 

( oto , 001 – 010 piece  )

The number of faults allowed within the period L-t. If number of 
faults exceeds this adjusted counter value device locks itself.
In this case (

- - -

) warn

 

appears on

 

its screen. User must press 

Reset button then the fault passes in order to unlock the device. 
If 

L- C

 is set to 

oto

 then this property  is disabled. 

 

V

Re

t

t

(o-U)

(u-U)

r-t

Over Voltage
   1. Error

L1,L2,L3

Normal

Normal

L- C (number of lock)    = 2 piece
L- t   (lock time)

 

 = 3 min.

 if select ;

t-1

t-1

r-t

Pushed to  Reset button
and Lock have reseted.

Locked occurred 

< 3 minutes

Over Voltage
   2. Error