3.8 Locking Period:
Auto/tdLy :
While operating in
automatic mode, if a failure repeats
within a specified period the device will
be locked.
To reset and remove the problem SET
button must be pushed until the reset
led turns off. This option helps the operator to estimate how frequent the
alarms occurs. This period can be set between 1 and 60 minutes.
Increase
Decrease
S
3.8
Locking
Time
Increase
Decrease
S
3.9
Locking
Counts
3.9 Locking Counter:
Auto/Cntr :
While operating in
automatic mode, within the locking
period, it shows after how many
alarms the device will be locked. To
reset and remove the problem SET
button must be pushed until the reset
led turns off. This option helps the
operator to estimate how frequent the
alarms occurs. It can be set between
2 and 10, or Inf (infinite).
“ - ” slides pressing
SET button
Selecting
Value
Digit slides
pressing SET
button
Old Password
New
Password Approved
New Password
Rejected
3.10 Password Menu:
If the entry was made by entering the
correct password, this menu will show
on.
If you want to change the current
passowrd push the SET button. Your
password will be ask again. Enter you
password as it has been explained in
section 3.1. After entering your
password the device will ask you to
enter the new password. After entering
the password you will have to confirm
the password entiering it again. If your
old password is correct and the new
password enteries match the message
“neu pass yes” will show and the
password will be changed. If your old
password is wrong or the new
password entries do not match the the
message “neu pass no” will show and
the old password will stay avaliable.
S
S
S
“ - ” slides pressing
SET button
Selecting
Value
Digit slides
pressing SET
button
New Password
Entry (first entry)
S
S
“ - ” slides pressing
SET button
Selecting
Value
Digit slides
pressing SET
button
New Password Entry
(second entry)
S
S
DP-01-
96
®
Digital Protector & Multimeter
Current & Voltage Protection
3.11 Factory Settings Menu
To restore the factory setting or to
remove any unwanted changes
made before.
When you reach rtrn dFLt SET if
you press SET button the device
will ask for your password.
If the password entry is correct the
device will reset its memory and
restore the factory settings with the
message “ rtrn dFLt yES “ showing
on the screen for 3 seconds.
In case of wrong entry the factory
settings will not be restored and the
message “ rtrn dFLt no “ message
will appear on the screen for 3
seconds
.
TECHNICAL INFORMATIONS
Rated Voltage (Un)
: 220Vac
Operating Range
: (0,8-1,1) x Un
Frequency
: 50/60 Hz
Supply Power Consumption
: < 8VA
Measurement Inputs
Power Consumption
: < 1VA
Voltage Measurement Range
: (Phase-Neutral ) 30 - 300 Vac, 45-90 Hz
: (Phase-Phase) 30 - 600 Vac, 45-90 Hz
Current Measurement Range
: (for seconder current)
50 mA - 6 Amp AC
Display Ranges
: 0 - 999,9 kV
: 0 - 999,9 M (W)
: (CosΦ) 0,00 -1,00 ind. and kap.
Minimum Measurement
Values
: 50 mA , 25 V
Measurement Sensitivity
: %1±1 digit
Voltage Transformer Ratio
: 1 ............1000
Current Transformer Ratio
: 5/5..........10000/5 A
Display
: 4 Digit LED display
Relay Contact Current : max. 3A / 240Vac
Device Protection Class
: IP 20
Connector Protection Class
: IP 00
Operating Temperature
: - 5 °C .... + 50 °C
Operating Humidity
: %15 ...... %95 (without condensation)
Connection Type
: To the Front Panel Tap
Dimensions
: 96 x 96 x 80 mm
Password approved
Factory setting are
restored
Password Rejected
The old setting lasts
“ - “ slides pressing
SET button
Selecting
Value
Digit slides
pressing SET
button
Old Password
S
S
S
The Factory Settings that are stored in the device's memory
are given below;
Ct ( Current transformer ratio )
: 5/5 A
oSEt ( Over current set value )
: 4 A
uSEt ( Under current set value )
: 2 A
hyS ( hysteresis )
: % 10
Cuur/USt ( Sudden switch off multiplier ): (oSEt) x 3
t-1 ( Start delay time )
: 20 sn
t-2 ( Over-under current delay )
: 5 sn
Asy/Cuur ( Asymmetric current )
: % 25
t-4 ( Asymmetric current alarm delay ) : 2 sn
Set/UuSt ( Over voltage set value )
: 240 V
Set/UaLt ( Under Voltage set value )
: 195 V
Asy/VOLt ( Asymmetric voltage )
: % 15
t-3 ( Voltage alarms delay )
: 5 sn
Protection Program
: Prog 3 (full protection)
rSEt/CtrL ( reset selection )
: 0 ( automatic reset)
t-on ( power-on time )
: 5 seconds
Auto/tdLy ( Locking Period)
: 10 minutes
Auto/Cntr ( Locking counter )
: 5 times
Alarms
: All active
ALr/out value
:“0000” Individual relays
N
L3
L2
L1
L1
N
Current Direction
L1
L2
L3
N
X/5 A
k3
l3
X/5 A
X/5 A
k2
l2
I1
k1
Auxiliary Supply
Un : 230 Vac, 50 Hz
ΔUn : (0.8 – 1.1)xUn
Voltage Inputs
Current Inputs
DP-
01
-
96
Supply Power Consumption
: < 6 VA
Measurement Power Consumption
: < 1 VA
Voltage Measurement Range
: (Phase-Neutral)30-300 VAC, 45-90 Hz
(Phase-Phase) 30-600 VAC, 45-90 Hz
Current Measurement Range
: 50mA – 6 Amp. AC
Measurement Category
: CAT III
Equipment Protection Class
: Double Insulation - class II ( )
2 A
2 A
2 A
2 A
Connection :
C
u
rre
n
t
vo
lt
co
m
Output Contacts
Max. 3A / 240Vac