3.8 Locking Period:

Auto/tdLy :

 While operating in 

automatic mode, if a failure repeats 
within a specified period the device will 
be locked.
To reset and remove the problem SET 
button must be pushed until the reset 
led turns off. This option helps the operator to estimate how frequent the 
alarms occurs. This period can be set between 1 and 60 minutes.

Increase

Decrease

S

3.8 
Locking     
     Time

Increase

Decrease

S

3.9 
Locking     
     Counts

3.9 Locking Counter:

Auto/Cntr :

 While operating in 

automatic mode, within the locking 
period, it shows after how many 
alarms the device will be locked. To 
reset and remove the problem SET 
button must be pushed until the reset 
led turns off. This option helps the 
operator to estimate how frequent the 
alarms occurs. It can be set between 
2 and 10, or Inf (infinite).

 “ - ” slides pressing 
SET button

Selecting 
Value

Digit  slides 
pressing SET 
button

Old Password

New 
Password Approved

New Password 
Rejected

3.10 Password Menu:

If the entry was made by entering the 
correct password, this menu will show 
on.
If you want to change the current 
passowrd push the SET button. Your 
password will be ask again. Enter you 
password as it has been explained in 
section 3.1. After entering your 
password the device will ask you to 
enter the new password. After entering 
the password you will have to confirm 
the password entiering it again. If your 
old password is correct and the new 
password enteries match the message 
“neu pass yes” will show and the 
password will be changed. If your old 
password is wrong or the new 
password entries do not match the the 
message “neu pass no” will show and 
the old password will stay avaliable.

S

S

S

“ - ” slides pressing 
SET button

Selecting 
Value

Digit  slides 
pressing SET 
button

New Password 
Entry (first entry)

S

S

“ - ” slides pressing 
SET button

Selecting 
Value

Digit  slides 
pressing SET 
button

New Password Entry 
(second entry)

S

S

DP-01-

96

®

Digital Protector & Multimeter

Current & Voltage Protection

3.11 Factory Settings Menu

To restore the factory setting or to 
remove any unwanted changes 
made before.
When you reach rtrn dFLt SET if
you press SET button the device 
will ask for your password.
If the password entry is correct the
device will reset its memory and 
restore the factory settings with the 
message “ rtrn dFLt yES “ showing
on the screen for 3 seconds.
In case of wrong entry the factory
settings will not be restored and the 
message “ rtrn dFLt no “ message 
will appear on the screen for 3 
seconds

.

TECHNICAL INFORMATIONS

Rated Voltage  (Un)

 : 220Vac

Operating Range

 : (0,8-1,1) x Un

Frequency 

 

: 50/60 Hz

Supply Power Consumption

 : < 8VA

Measurement Inputs 
Power Consumption    

: < 1VA

Voltage Measurement Range

 : (Phase-Neutral ) 30 - 300 Vac, 45-90 Hz

 

 : (Phase-Phase) 30 - 600 Vac, 45-90 Hz

Current Measurement Range

 : (for seconder current)

 

    50 mA - 6 Amp AC

Display Ranges

 : 0 - 999,9 kV
 : 0 - 999,9 M (W)
 : (CosΦ) 0,00 -1,00 ind. and kap.

Minimum Measurement
Values 

 : 50 mA , 25 V

Measurement Sensitivity

 : %1±1 digit

Voltage Transformer Ratio

 : 1 ............1000

Current Transformer Ratio

 : 5/5..........10000/5 A

Display 

 

 : 4 Digit LED display

Relay Contact Current                     : max. 3A / 240Vac
Device Protection Class 

 : IP 20

Connector Protection Class

 : IP 00

Operating Temperature 

 : - 5 °C .... + 50 °C

Operating Humidity 

                    : %15 ...... %95 (without condensation)

Connection Type 

 : To the Front Panel Tap 

Dimensions 

 : 96 x 96 x 80 mm

Password approved 
Factory setting are 
restored

Password Rejected 
The old setting lasts

“ - “ slides pressing 
SET button

Selecting 
Value

Digit slides 
pressing SET 
button

Old Password

S

S

S

The Factory Settings that are stored in the device's memory 
are given below;

Ct ( Current transformer ratio )

: 5/5 A

oSEt ( Over current set value )

: 4 A

uSEt ( Under current set value )

: 2 A

hyS ( hysteresis )

: % 10

Cuur/USt ( Sudden switch off multiplier ): (oSEt) x 3
t-1 ( Start delay time )

: 20 sn

t-2 ( Over-under current delay )

: 5 sn

Asy/Cuur ( Asymmetric current )

: % 25

t-4 ( Asymmetric current alarm delay ) : 2 sn
Set/UuSt ( Over voltage set value )

: 240 V

Set/UaLt ( Under Voltage set value )

: 195 V

Asy/VOLt ( Asymmetric voltage )

: % 15

t-3 ( Voltage alarms delay )

: 5 sn

Protection Program

: Prog 3 (full protection)

rSEt/CtrL ( reset selection )

: 0 ( automatic reset)

t-on ( power-on time )

: 5 seconds

Auto/tdLy ( Locking Period)

: 10 minutes

Auto/Cntr ( Locking counter )

: 5 times

Alarms

: All active

ALr/out value

:“0000” Individual relays

N

L3

L2

L1

L1

N

Current  Direction

L1

L2

L3

N

X/5 A

k3

l3

X/5 A

X/5 A

k2

l2

I1

k1

Auxiliary Supply

Un    :  230 Vac, 50 Hz
ΔUn : (0.8 – 1.1)xUn

Voltage Inputs

Current Inputs

DP-

01

-

96    

Supply Power Consumption

: < 6 VA

Measurement Power Consumption

: < 1 VA

Voltage Measurement Range

: (Phase-Neutral)30-300 VAC, 45-90 Hz
  (Phase-Phase)  30-600 VAC, 45-90 Hz

Current Measurement Range

:  50mA – 6 Amp. AC

Measurement Category

: CAT III

Equipment Protection Class

: Double Insulation -  class II (           )

  

2 A

2 A

2 A

2 A

Connection :

C

u

rre

n

t

vo

lt

co

m

Output Contacts

      Max. 3A / 240Vac