2.7 Under Current Protection:

It can be set by the user between x 0.1 and 
x 1 of the current transformer value.
It works only on full protection mode (Prg2).
When the current of the protected motor 
goes below the adjusted value it switches
off its output contact after t2 delay.
It goes active after the start delay ends.
After a switch off of an under current 
alarm, while automatic reset is selected, if 
the current value returns to the normal value 
or zero value then switch on occurs after a 
proper period (T-on). If manual reset is 
selected, the switch off will continue until
the operator pushes the reset button. 
Pressing the set button for 3 seconds 
resets the device.

NOTE: 

Under current protection set value 

with its hysteresis must not overlap with 
over current protection set value with 
its hysteresis or, the under current 
protection set value must not be higher 
than the over current protection set value.
Otherwise, (LinE ovEr Eror) message will
appear on the screen and the output 
contact will be switched off. In this case 
you should check the over and the under 
current set values.

hyS

oSEt

hyS

uSEt

hyS

oSEt

hyS

uSEt

hyS

oSEt

hyS

uSEt

3. Password Inquiry and Menu Entry 

3.1 Password Inquiry

If you push the SET button, the password inquiry menu shows up. Using the 
direction buttons, the authorized operator can increase or decrease the digit 
value to reach the required value, then pushes SET button to move to the next 
digit. After inputing the last digit, pushing the SET button approves the 
password. The “ - “ on the middle screen makes  the digit follow up easier. This 
way the user knows how many digits he already input. 
After the password approval, the user gets “Accepted” or “Rejected” message on 
the screen for 3 seconds. After that the program main menu shows up, In case 
of wrong password entry, the user can move through the menu but can not make 
any changes in the program settings.

Pushing the down button shows the menus under the main menu that are in 
order:protection program selection, alarm control menu, current setting menu, 
voltage settings menu, reset settings menu, power on timing settings, 
password menu, failure lock timing settings (in the automatic mode), failue 
lock counter settings (in the automatic mode), and factory settings.

Viewing Menus:

Because the device is password protected, in case of wrong password entry, 
the password and the factory settings menus are not shown, the other menus 
are shown but not changeable. Only correct password entry shows all menus 
and gives the abilitiy of changing the device settigs.

Buttons Use:

The user can move through the menus using the direction buttons (up – down). 
When he reaches the required settings he gains access to change the setting 
by pressing the SET button, the shown value then blinks. Uses the direction 
buttons to change the values,  and pushes the SET button again to store the 
changes. The blinking values stops blinking then. The user can go to the upper 
menu seeking the quit command using the direction buttons and then pushing 
the SET button.

hyS

oSEt

hyS

uSEt

(Over current hysteresis)

(Over current set value)

(Under current hysteresis)
(Under current set value)

hyS

oSEt

hyS

(Over current hysteresis)

(Over current set value)

(Under current hysteresis)

(Under current set value)

hyS

oSEt

hyS

uSEt

(Over current hysteresis)

(Over current set value)

(Under current hysteresis)

(Under current set value)

Current

It increases or decreases
the value of the password

S

Enter

S

When the set button is pushed, the password
at the bottom screen puts the digit value in 
the digit division “-” and it slides the digit line
to the left digit

       Accepted 

       rejected 

S

3.5 Voltage 
Settings Menu

S

S

Increase

Decrease

S

S

3.4 Current 
Settings Menu

3.3 To Alarm 
Control Menu 

S

Increase

Decrease

Increase

Decrease

3.11 Factory       
       Settings

3.10  To 
Password 
Menu

S

S

S

Exit

3.2Protection  
      Program   
      selection

3.6 Reset  
      
Selection 

  

 

3.7 
Power-on
       Time

Increase

Decrease

S

3.8 Lock    
           
Time    

  

Increase

Decrease

S

3.9 Lock    
           
Time

MAIN MENU:

Digital Protector & Multimeter

Current & Voltage Protection

DP-01-

96

®