Delay Timing:
The system can be configured to invoke a delay so that relay trigger activation (i.e., equipment shutoff) will
not occur until the specified time period has elapsed. DSW1 switches 1 through 4 establish the desired delay.
The listing below provides definitions for several available delay settings. (Consult the full user manual for
detailed settings and options.)
DSW1:
-------
1 2 3 4
-------
1 min: 1 0 1 0
2 min: 0 1 1 0
5 min: 1 1 1 0
10 min: 0 0 0 1
Notes:
1) A '
0
' digit means the specified DIP switch is "off". '
1
' means the switch is "on".
2) You may also optionally configure a post-shutoff reactivation delay using switches 1, 2, 3, 4 at
DSW2. Desired delay values follow the same convention as described for DSW1.
Terminal Block Wiring Connections:
The controller provides screw terminal connections for wiring purposes:
1) +12VDC power in/out
2) Ground
3) Reserved
4) Wired Sensor #1
5) Wired Sensor #2
6) Wired Sensor #3
7) Wired Sensor #4
8) Wired Sensor return
9) Wired Sensor return
10) Wired Sensor return
11) Wired Sensor return
12) Relay - COM
13) Relay - N/C
14) Relay - N/O
Notes: 1) For wired-sensor applications, any unused sensor inputs should be disabled with a short jumper
wire to the appropriate return.
2) Please consult the user manual for complete wiring explanations. (See website link above.)
3)
WARNING
:
For wireless applications, avoid contacting the antenna and/or mounting bracket with
any grounded object such as the HVAC chassis, water heater, laundry equipment, or metal wall
studs. Inadvertent contact may result in electrical failure including damage to the power converter.
Customer equipment may also be subjected to blown fuses and/or tripped circuit breaker.
4) If you encounter any issues during or after the install, please contact Kadtronix technical support
(321-757-9280) for on-site assistance. Please do not return the product without authorization -
proper troubleshooting and/or problem resolution may be impossible once the unit has been
removed from service.