Kaden Installation Manual |
17
Rows of series installation
Table 5.2 The relations between H, A and L are as follows.
L
A
L ≤ H
L ≤ 1/2H
250mm or more
1/2H < L ≤ H
300mm or more
L > H
Can not be installed
Fig. 5.8
3000mm or more
A
H
L
600mm or more
250mm
or more
250mm
or more
1500mm or more
Drain joint installation
If the drain joint comes with a rubber seal
(See Fig. 5.9 A)
,
do the following:
1. Fit the rubber seal on the end of the drain joint that will
connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of
the unit.
3. Rotate the drain joint 90° until it clicks in place facing the
front of the unit.
4. Connect a drain hose extension (not included) to the drain
joint to redirect water from the unit during heating mode.
Fig. 5.9
If the drain joint doesn’t come with a rubber seal
(See Fig. 5.9 B)
,
do the following:
5. Insert the drain joint into the hole in the base pan of the
unit. The drain joint will click in place.
6. Connect a drain hose extension (not included) to the drain
joint to redirect water from the unit during heating mode.
Notes on drilling hole in wall
You must drill a hole in the wall for the refrigerant piping,
and the signal cable that will connect the indoor and
outdoor units.
1. Determine the location of the wall hole based on the
location of the outdoor unit.
2. Using a 65mm core drill, drill a hole in the wall.
3. Place the protective wall cuff in the hole. This protects
the edges of the hole and will help seal it when you
finish the installation process.
NOTE:
When drilling the wall hole, make sure to avoid
wires, plumbing, and other sensitive components.
Base pan hole
of outdoor unit
Seal
Drain joint
Seal
A
B