![Kaco blueplanet hybrid 10.0 TL3 Скачать руководство пользователя страница 26](http://html2.mh-extra.com/html/kaco/blueplanet-hybrid-10-0-tl3/blueplanet-hybrid-10-0-tl3_operating-instructions-manual_3472024026.webp)
EN
blueplanet hybrid 10.0 TL3
Page 26
7.3.2
AC cable fitting assembly
Description of the individual parts of the AC connector (Fig. 13: AC connector)
1.
Cable fitting
2.
Seal
3.
Housing
4.
Contact carrier
Fig. 13: AC connector
Preparation for mounting the connector according to Fig. 14
1.
Slide the cable fitting over the cable.
2.
Only for 1410656
: Choose a seal that fits your cable diameter.
3.
Slide the housing with the seal over the cable.
4.
Strip the cable by 50 mm.
5.
Then shorten wires N and L1, L2, L3 by 8 mm.
6.
Strip the wires by 12 mm.
7.
With flexible wires, we recommend the use of wire sleeves conforming to DIN 46228 that are pressed together
using crimping pliers CRIMPFOX 6 (1212034).
Fig. 14: Cable stripping dimensions
Connecting wires
o
Connect the wires to the contact carrier (Fig. 15).
o
The assignment depends on the marking on the contact carrier.
o
Connect the screws on the contact carrier with 1 Nm (: Placing the wires
o
Push the contact carrier into the housing until it audibly engages (Fig. 17).
o
Tighten the cable fitting with an open-ended spanner [ W_30
/
6.5 Nm] (: Interconnection Fig. 18).
Authorised elec-