Interfaces
Ethernet connection type
RJ45
Torque for cable fitting
5 (M25) 2.5 (M16) Nm
7.4
Connecting the device to the power grid
7.4.1
Configuring the AC connection plug
1
2
3
4
Fig. 11:
AC connection plug
0,47 In
(12mm)
1,97 In
(50mm)
0,31 In
(8mm)
6
5
50 mm
12 mm
8 mm
Fig. 12:
Strip the insulation from the
cable
L3
L2
N
PE
L1
L3
L2
N
PE
L1
Fig. 13:
Connect wires to the contact
carrier
1 Nm
1 Nm
Fig. 14:
Tighten screws on the housing
30
6,5 Nm
Fig. 15:
Tighten the cable screw fitting
CLICK !
CLICK !
Fig. 16:
Press contact carrier into the
housing
Key
1
Cable fitting
4
Contact carrier
2
Seal
5
Line
3
Housing
6
Cable lengths
↻
Connection area opened.
1 Slide the cable fitting over the cable.
2 Select seal according to cable diameter used.
3 Slide the housing and seal over the cable.
4 Remove the insulation from the cable. [
sl. 50 mm
]
5 Shorten the wires N, L1 by 8 mm if a single-phase connection is present or shorten the wires N, L1, L2, L3 by the same
length in case of a 3-phase connection.
6 Strip the wires N, L1 in case of a single-phase connection or N, L1, L2, L3 in case of a 3-phase connection by 12 mm.
7 Flexible wires must be fitted with wire sleeves in accordance with DIN 46228.
8 Insert wires into the contacts in accordance with the markings on the contact carrier.
9 Tighten screws on contact carrier. [ S_2/ 1 Nm]
10 Press contact carriers into the housing with an audible "click".
11 Secure the housing with a screwdriver [ W_29] and tighten the cable screw fitting. [ W_29/ 6.5 Nm]
»
Make the electrical connections.
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3