Country-
spec. Set-
tings
Me-
nu
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Núm. de pu. de apoyo
2 - 10
AVISO: The maximum number of configurable nodes depends on the
selected grid type.
F
Specify the number of nodes for the Q(U) characteristic curve.
4
1
2
3
4
1. punto de apoyo …
10. punto de apoyo
Voltage | Reactive
power | Excitation
0 - max. voltage in
continuous operation
F
Enter the voltage of the node in volts.
0-100% [% S
max
]
F
Set the reactive power of the node as a percentage of the maximum
power.
Over-excited | un-
der-excited
F
If a reactive power not equal to 1 is selected: Select the type of pha-
se shift.
4
1
2
3
4
Det. isla ampl.
AVISO: Grid operators require shutdown of the device with standalone
grid detection.
F
Further parameterisation is possible via the web interface.
BE CH-NS
CY DE-NS
DK JP-50HZ
JP-60HZ
LU-NS TW
UD
4
1
2
3
4
Error de la red
AVISO: Display of grid faults.
F
To show the last 5 grid fault messages, press the
Show button.
4
1
2
3
4
Advanced features
F
Further parameterisation is possible via the web interface
4
1
2
3
4
Información
Open the menu: Press the right arrow button or the OK button.
4
1
2
3
4
Tipo inversor
Displays the type designation of the device. If feed-in power is actively
limited: display maximum power in kW.
4
1
2
3
4
Versión SW
Displays the installed software version.
4
1
2
3
4
N° serie
Displays the serial number of the device.
4
1
2
3
4
Vis. país
Displays the selected country setting. Optional: Displays the grid type if
a grid type has been selected.
4
1
2
3
4
Fabricante
The display shows information about the device manufacturer.
9.4.2
Configuration via web user interface
AVISO
In addition to the parameters in the chapterMenu [Ver capítulo 9.4.1
Página 38], additional parameters
are available and accessible via the web user interface. To do so, enable
Remote config
in
Network
under
Webserver
and enter the device IP address into your browser.
4
1
2
3
4
Operating settings
AVISO: Options for advanced setting of the operating parameters.
4
1
2
3
4
CC Tensión inicial
The device begins feed-in as soon as this DC voltage is present.
F
Set the starting voltage.
4
1
2
3
4
Reg. tensión const.
AVISO: Option to disable the MPP seek mode in order to operate the
device with a constant DC voltage.
1 Activate or disable the constant voltage controller.
2 Set value for constant voltage controller.
Kaco blueplanet 29.0TL3
Página 48
ES