KACO blue-
planet
87.0TL3
KACO blue-
planet
92.0TL3
KACO blue-
planet 110TL3
KACO blue-
planet 125TL3
KACO blue-
planet 137TL3
KACO blue-
planet 150TL3
Short circuit current continu-
ous [ms] (max output fault
current)
134 A
Inrush current
5 A [RMS (20ms)]
Rated frequency
50/60 Hz
Frequency range
45 - 65 Hz
Reactive power
0-100 % Snom
cos phi
1 - 0.3 ind/cap
Number of feed-in phases
3
Distortion factor (THD)
< 3 %
< 3 %
< 3 %
< 3 %
2.8 %
< 3 %
Max. voltage range (up to
100 s)
475 V
500 V
600 V
750 V
825 V
AC overvoltage protection
Base
4.2
General data
KACO blue-
planet
87.0TL3
KACO blue-
planet
92.0TL3
KACO blue-
planet 110TL3
KACO blue-
planet 125TL3
KACO blue-
planet 137TL3
KACO blue-
planet 150TL3
General electrical data
Max. efficiency
99.0 %
98.8 %
99.1 %
99.2 %
European efficiency
98.6 %
98.5 %
98.8 %
99.0 %
Self consumption: Standby
< 10 W
Feed-in from
> 200 W
Transformer unit
no
Protection class / over volt-
age category
I / III
Grid monitoring
Country-specific
Distribution system
TN-C system, TT system, Solid grounded wye
General data
Display
LEDs
Control elements / operating
control
Button / web server
Menu language
EN; DE; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
Interfaces
2 x Ethernet, USB, 2x RS485 (1x reserved for string combiner com.), optional
Fault signal relay
yes (integrated switch)
DC switch / AC switch
no / yes (XL version) / no
Cooling
temp. regulated fan, max air throughput 364 m³/h
Number of fans
3x outside, 1x inside
Noise emission
<60 db(A)
Housing material
AL
H x W x D
28,30 inch x 28,30 inch x 18,11 inch
Weight
172 Ib
Certification
Overview: see homepage, download area
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 13
EN-US