background image

6

Saflok SR

TM 

Series RFID Reader Installation Guide - PK3670_T_08_15

3-  Schematic Diagram

SCHEMATIC DIAGRAM

SR RFID READER AND

REMOTE CONTROL UNIT (RCU)

ELECTRIFIED

LOCKING DEVICE

ELECTRIFIED

LOCKING DEVICE

POWER SUPPLY

12 - 24 VOLTS

CONTROLLER ENCLOSURE

DOUBLE GANG BOX

(LOW VOLTAGE)

USE NORMALLY OPEN FOR ELECTRIC STRIKES

USE NORMALLY CLOSED FOR ELECTRO MAGNETS

NORMALLY CLOSED (BLACK)

NORMALLY OPEN (BLUE)

COMMON (RED)

DRY CONTACT OUTPUT

POWER INPUT

AC OR DC

12 - 24 VOLTS

(15 METER MAXIMUM)

SHIELDED CABLE

3 x 22 AWG TWISTED PAIR

SR RFID READER

(BACK VIEW)

MODULE

INTERFACE

RCU PCB

-6V

+6V

TX+

TX-
RX+
RX-

RF PCB (OPTIONAL)

2

1

3
4
5
6

Power Leads

The SR RFID RCU requires 12-24 volts AC or DC input. Two wire leads (white insulation) are provided for supplying 

power to the controller. Ensure that voltage going to the controller does not exceed 24 volts. 

Any 110 VAC power supplies necessary for rectification shall be in separate rated enclosures.

Relay Leads

Three wire leads (red, black, and blue) are provided for switching power to the electrified locking device attached to 

the gate, door, doorframe, etc. 

 

•  The red lead is common. It is always connected.

 

•  The black lead is normally closed (NC). It is used for electric lock devices like electromagnets. 

 

•  The blue lead is normally open (NO). It is used for electric lock devices like electric strikes.

Regulatory Compliance:

This device complies with Part 15 of the FCC Rules,.

 Operation is subject to the following two conditions: (1) this device may not cause 

harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.  

Any changes or modifications of this product, not approved by manufacturer will void the user’s authority to operate the equipment.

This device complies with Industry Canada license-exempt RSS standard(s).

 Operation is subject to the following two conditions: (1) 

this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired 

operation of the device.”

Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence.

 L'exploitation 

est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout 

brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

FCC ID: SAPMESSENGEREM 

IC: 7078A-A28990

Contains transmitter module with FCC # SAPMESSENGER2GHZ and IC # 7078A-A28780

Содержание Saflok SR Series

Страница 1: ...INSTALLATION GUIDE Saflok SRTM Series RFID RCU ECU ...

Страница 2: ...his confidential information contained herein may result in legal action by Computerized Security Systems dba SAFLOK and its parent company Made in North America 2015 Kaba Lodging Systems All trademarks and registered trademarks are the property of their respective owners SR1 Reader and Controller Box Ideal for Surface mount or mounting on aluminum door frame SR2 Reader and Controller Box Intended...

Страница 3: ...ve Amps at 250VAC or 5 AMPS at 30VDC Typically the NO set of contacts are used so that the ECU will work like the elevator call button to complete the circuit to call the elevator to the specific floor Important Review your local Fire Electrical and Building Codes before installing this product Be sure to investigate the switching current and voltages present at the existing elevator buttons and d...

Страница 4: ...4 Saflok SRTM Series RFID Reader Installation Guide PK3670_T_08_15 NONE Controller BOM ...

Страница 5: ...hing the SR1 back plate 2 Position the controller box on the opposite side of the wall within 15 meters of the reader 3 Run the appropriate wires to the controller enclosure and SR reader enclosure in accordance with the schematic diagram on the following page For connecting the reader to the controller 3 twisted pair x 22 AWG CMP cable is recommended Belden 6542FE or equivalent Ensure compliance ...

Страница 6: ...r electric lock devices like electromagnets The blue lead is normally open NO It is used for electric lock devices like electric strikes Regulatory Compliance This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may ...

Страница 7: ...Services Support Saflok 1 800 999 6213 1 248 837 3700 General Information www kabalodging com Online Consumable Orders www saflokstore com To access all of our easy steps please visit our Support Website www kabalodgingsupport com ...

Отзывы: