RAC Model 3.5 with KIM Swipe Reader

2

1. Shut off the electrical power to the AC line to be connected to the control panel.

2. Set AC input switch S1 on the Power Supply (C) for the electrical voltage used in your country. North

American applications require 115VAC, 60Hz; European applications require 230VAC, 50Hz. Insert
appropriate fuse in F1 fuse clips:for North America, use 600mA, 5mm fuse, fast blow. For Europe,
use 315mA, 5mm fuse, fast blow.

3. Install the control panel in the desired location, using the Installation Kit.

4. Install the KIM Swipe Reader Assembly (B) in the desired location.  

Refer to appropriate fitting

instructions for chrome reader or black reader, in Section 3.3 on page 3. 

A Dual Reader installa-

tion has one Egress (exit) reader (B1) and one Ingress (entry) reader (B2).

5. Connect the AC line to terminal TB1 on the Power Supply (C) (see Table 5 on page 6).

6. Connect the shielded cable from the KIM Swipe Reader Assembly (B) to terminal block JP3 on the

Controller (A). For connections, see Table 1. 

For Dual Reader installations, connect the Egress

reader (B1) to Controller #1 (A1) and the Ingress reader (B2) to Controller #2 (A2).

7. If the Control Panel is not being interfaced to a fire alarm panel, go to step 8. Remove the jumper

from terminal TB5 on the Power Supply (C) and complete the fire panel installation.

8. If an additional Remote Programming Interface (D) is not being installed, go to step 9. Run a twisted

2 pair stranded conductor, 22 AWG shielded cable from the Remote Programming Interface (D) to 
terminal block J4 on the Controller (A). For connections, see Table 2. 

For Dual Reader installations,

connect the Remote Programming Interface (RPI) (D) to Controller #1 (A1).

9. Install the 2 conductor 18 AWG shielded cable from the control panel to the location of the electric

strike (G) or electromagnetic lock (E).

10. Connect the cable shield to the chassis ground connection at terminal TB6 on the Power Supply (C).

11. Install the diode across the terminals of the electromagnetic lock (E) or, using the butt connectors

provided in the Installation Kit, install the diode across the two wires of the electric strike (G). 

Do not

reverse diode polarity.

Note:  This step is not necessary if installing an HES 7000 Series electric strike

or Rutherford Controls 83xx series electromagnetic lock

12. Mount the electric strike (G) or electromagnetic lock (E) in the desired location and connect as per

manufacturers’ instructions.

13. Run a 2 conductor, 22 AWG, stranded cable from the tamper switch to premises alarm system. Using

quick disconnects on tamper switch terminals, connect tamper in series with instant (24hr) zone to
create an audible alarm or trouble signal upon opening the access control panel.

14. Double-check all connections, including the cable shields.

Note:  The AC failure contacts, TB3 on the Power Supply (C), are dry relay out-

puts that will change state when the AC power is shut off. If required, this
can be connected to a separate alarm panel. Terminals available are
Common, Normally Open, and Normally Closed (30VDC @ 1Amp max).

15. Configure DIP switches S2 on the Controller (A) to the desired relay activation time. See Table 6 and

Figure 3. 

Do not use CFG #16 because this setting is used only for reinstalling the controller.

For Dual Reader Installations, set the DIP switches on Controller #1 (A1) and Controller #2
(A2).

16. Turn on the AC power. The green LED on the front of the control panel will light. LEDs D26 and D27

will start flashing alternately. See Table 3 for LED descriptions.

17. Position bypass switch S3 on the Controller (A) down for normal mode. When power is supplied to

the unit, the indicator light beside the switch should be OFF for normal mode and ON for bypass
mode.

Note:  On the 8-relay configuration, there is one bypass switch per relay on the

expansion board. Set each switch according to whether you wish to
bypass the associated relay.

Содержание 3.5

Страница 1: ...INSTALLATION GUIDE Remote Access Controller Model 3 5 with KIM Swipe Reader Solitaire 710 II 710 System 700 Generation E 760 PK2918 ...

Страница 2: ...ccessories 9 Drilling Templates 11 Disclaimer Please read and follow all directions carefully These instructions are designed for use by maintenance professionals or lock installers who are familiar with common safety practices and competent to perform the steps described Kaba Ilco is not responsible for damage or malfunction due to incorrect installation however arising Carefully inspect windows ...

Страница 3: ...ontrol panel should be securely screwed to the wall using the four mounting holes If possible the control panel should be mounted at a workable height with clearance to open the door com pletely Notes Access to control panel is restricted to service personnel only A certified electrician must connect the AC power to the Control Panel in accordance with applicable local standards Kaba Ilco is not r...

Страница 4: ...e cable shield to the chassis ground connection at terminal TB6 on the Power Supply C 11 Install the diode across the terminals of the electromagnetic lock E or using the butt connectors provided in the Installation Kit install the diode across the two wires of the electric strike G Do not reverse diode polarity Note This step is not necessary if installing an HES 7000 Series electric strike or Ru...

Страница 5: ...emplate for the Satin Chrome KIM Swipe Reader located at the end of this booklet mark the holes for the cable and screws 2 Wearing safety glasses drill the holes in the wall Enlarge the upper part of the cable hole 3 Tap the plugs into the wall then tighten the screws fully Undo the screws one turn leaving a small gap between the screw head and the wall 4 Fish the cable to the control panel and ma...

Страница 6: ...tromagnetic Lock Electric Strike Note 1 Due to Hanchett Entry Systems HES modifying their 7000 series electric strikes and Rutherford Controls modifying their 83xx series electromagnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit ...

Страница 7: ...eir 7000 series electric strikes and Rutherford Controls modifying their 83xx series electromagnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit Dual Reader Access Controller Assembly Electromagnetic Lock Electric Strike ...

Страница 8: ...ccess Delay DIP Switch Settings S2 CFG 4 3 2 1 SEC 1 ON ON ON ON 8 2 ON ON ON OFF 1 3 ON ON OFF ON 3 4 ON ON OFF OFF 5 5 ON OFF ON ON 10 6 ON OFF ON OFF 15 7 ON OFF OFF ON 20 8 ON OFF OFF OFF 25 9 OFF ON ON ON 30 10 OFF ON ON OFF 35 11 OFF ON OFF ON 40 12 OFF ON OFF OFF 50 13 OFF OFF ON ON 60 14 OFF OFF ON OFF 90 15 OFF OFF OFF ON 120 16 OFF OFF OFF OFF REINIT Example of S2 Settings Delay times ca...

Страница 9: ...nnector programming port P1 on the controller PCB in the control panel Refer to Figure 1 or Figure 2 for the positions of the J1 and P1 connectors Refer to Figure 4 or Figure 5 below for an illustration 2 For step by step programming instructions refer to chapter 5 of the Kaba Ilco Lodging Access Control System Reference Manual version 6 5 or higher Note When programming the RAC you do not swipe t...

Страница 10: ...nce back up batteries should be replaced every 2 to 3 years and tested every 6 months by removing main AC power 4 4 Power Failure In the event of an electrical failure the system will revert to standby status for a period of 4 hours if the optional battery is installed If the electrical power is restored within three days the system will recover automatically and should require no additional progr...

Страница 11: ...ng their 7000 series electric strikes and Rutherford Controls modifying their 83xx series electro magnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit NOTE 1 Due to Hanchett Entry Systems HES modifying their 7000 series electric strikes and Rutherford Controls modifying their 83xx series electro magnetic locks to include an on board d...

Страница 12: ...with Timer NOTE 1 Due to Hanchett Entry Systems HES and Rutherford Controls modifying their electro magnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit For electric strikes it is still necessary to install the diode from the installation kit ...

Страница 13: ...Installation Guide 11 Notes Drilling Templates for KIM Swipe Readers SATIN CHROME BLACK Drill 0 25 hole for cable 6 x 0 5 12 7 mm screw x4 4 x 0 125 3 175 mm hole 1 3 33 mm Back Panel of Reader ...

Страница 14: ...ntréal QC H4P 2G7 Technical Support 1 800 906 4526 Customer Service T 1 877 468 3555 F 514 735 6589 General Information www kabalodging com Online Consumable Orders www keycard com To access all of our easy steps please visit our Support Website http connect kabalodging com ...

Отзывы: