                                  FIRE DAMPERS / SHUTTER TYPE 

K-VENTIL ventilation equipment 

                                                  [email protected] | +356 79667970 | www.kventil.com

 

maximum of 1 in.(25mm) from corners.A minumum of 4 attachments (2 on each side of the 
blade channel) pers ide (16 per damper) are required. 
One of the methods of attachment shown below must be used. 

 

-

 

tack or spot welds ( sleeves thicker than 16 Ga  shall not be provided with spot 
welds ).

 

-

 

10 sheet metal screws

 

-

 

1/4 in. (6mm) bolts and nuts

 

-

 

3/16 in. (4.7mm) steel pop rivets

 

 
 

 

 

 
 

 

Securing Fire Damper and Sleeves to Wall Openings 

 
The fire damper must be installed such that the centerline of the blades are mounted in the 
plane of the wall.Fire damper and sleeve assemblies must be installed in wall openings using 
retaining angles on each side of the wall as described below: 
 

-

 

Retaining angles for 1½ hour rated dampers with a height 36 in.(914mm) or less must 

be a minumum of 16 ga. (1.5mm).The leg of the retaining angle on the damper sleeve 
shall be a minumum of 2 in. (51mm).The leg of the retaining angle on the wall shall 
be long enough to cover the annular space and overlap the wall by a minumum of 1 

Содержание FD-10

Страница 1: ...FIRE DAMPERS SHUTTERTYPE K VENTIL ventilation equipment export kventil com 356 79667970 www kventil com...

Страница 2: ...ess than 3 hours This damper installed vertically in HVAC systems that automatically shut down in the event of fire Construction Frame Roll formed galvanized steel Blades Low profile roll formed galva...

Страница 3: ...vens are galvanized steel and are available in 1 0mm 1 5mm thicknesses and lengths up to 914mm C dimension specifies location of damper within the sleeven Minimum is 102mm Maximum is L less 102mm whic...

Страница 4: ...FIRE DAMPERS SHUTTERTYPE K VENTIL ventilation equipment export kventil com 356 79667970 www kventil com FD DFD 10 TRANSITIONS AND SIZE LIMITATIONS Transition Details...

Страница 5: ...inimum sleeve gauges Maximum sleeve thickness is 10 gauge 3 5mm Sleeve inside dimensions must equal damper out side dimensions Sleeves shall extend a maximum of 6in 152mm beyond the wall opening on ea...

Страница 6: ...mm steel pop rivets Securing Fire Damper and Sleeves to Wall Openings The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall Fire damper and slee...

Страница 7: ...ucts to Fire Damper Sleeves Any duct connection other than breakaway is considered rigid The connections shown are considered breakaway Factory furnished duct collars on type R and CR fire dampers are...

Страница 8: ...ORDER PARAMETERS FD 10 F00 01 L1200 N 1000X700 FD 10 Static Fire Damper 74 C Fusible links N Neck Size DFD 10 Dynamic Fire Damper 74 C Fusible links D Neck Diameter L Requested Product Length F00 No F...

Отзывы: