                                  FIRE DAMPERS / SHUTTER TYPE 

K-VENTIL ventilation equipment 

                                                  [email protected] | +356 79667970 | www.kventil.com

 

 
 
Factory Sleeven Option 

 
Fire dampers are available in factory fornisted sleeven. Sleevens are galvanized steel and are 
available in 1,0mm – 1,5mm thicknesses and lengths up to 914mm. “C” dimension specifies 
location of damper within the sleeven. Minimum is 102mm; Maximum is “L” less 102mm, 
which allows for mounting angle installation and duct connection at each end of sleeve. If 
“C” dimension is not specified, it will be provided as one half of “L” dimension (damper 
centered in sleeve). 

                                                      

 

          

                 

 

                           

 

Содержание FD-10

Страница 1: ...FIRE DAMPERS SHUTTERTYPE K VENTIL ventilation equipment export kventil com 356 79667970 www kventil com...

Страница 2: ...ess than 3 hours This damper installed vertically in HVAC systems that automatically shut down in the event of fire Construction Frame Roll formed galvanized steel Blades Low profile roll formed galva...

Страница 3: ...vens are galvanized steel and are available in 1 0mm 1 5mm thicknesses and lengths up to 914mm C dimension specifies location of damper within the sleeven Minimum is 102mm Maximum is L less 102mm whic...

Страница 4: ...FIRE DAMPERS SHUTTERTYPE K VENTIL ventilation equipment export kventil com 356 79667970 www kventil com FD DFD 10 TRANSITIONS AND SIZE LIMITATIONS Transition Details...

Страница 5: ...inimum sleeve gauges Maximum sleeve thickness is 10 gauge 3 5mm Sleeve inside dimensions must equal damper out side dimensions Sleeves shall extend a maximum of 6in 152mm beyond the wall opening on ea...

Страница 6: ...mm steel pop rivets Securing Fire Damper and Sleeves to Wall Openings The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall Fire damper and slee...

Страница 7: ...ucts to Fire Damper Sleeves Any duct connection other than breakaway is considered rigid The connections shown are considered breakaway Factory furnished duct collars on type R and CR fire dampers are...

Страница 8: ...ORDER PARAMETERS FD 10 F00 01 L1200 N 1000X700 FD 10 Static Fire Damper 74 C Fusible links N Neck Size DFD 10 Dynamic Fire Damper 74 C Fusible links D Neck Diameter L Requested Product Length F00 No F...