49
No.
Object function
Name
Data type
Flags
166
Setpoint
Air condition
2byte
C,R,W,T
This communication object is used to read out the setpoint, modify the temperature setpoint or send out the
setpoint on the bus according to the parameter setting. In the default parameter settings, the setpoint can only be read
out.
167
Air Condition on/off
Air condition
1bit
C,T
The communication object is visible with ―1bit‖ in the parameter ―object type for control air condition‖, which
is used to send out a telegram with air-condition on/off.
Telegram value:
1——air condition on
0——air condition off
When the object sends a telegram ―off‖, other button can be operated, but no telegrams are sent. To facilitate
control air condition, the TFT will record temperature, speed and swing icons state for each mode, so when switch
the modes, it may appear that the display setpoint is inconsistent with the actual setpoint.
167
IR command number
Air condition
1byte
C,T
The communication object is visible with ―1byte‖ in the parameter ―object type for control air condition‖, which
is used to send out a telegram with control command of air-condition, the telegram values corresponds to different
commands are set via the parameters.
168
Mode heating/cooling
Air condition
1bit
C,T
The communication object will be visible with ―1bit‖ in the parameter ―object type for control air condition‖,
which is used to send out a telegram with switching to the heating mode or the cooling mode.
Telegram value:
1——heating mode
0——cooling mode
169
Mode auto/dry
Air condition
1bit
C,T
The communication object will be visible with ―1bit‖ in the parameter ―object type for control air condition‖,
which is used to send out a telegram with switching to the auto mode or the dry mode.
Telegram value:
1——auto mode
0——dry mode
170
Switchover high/medium speed
Air condition
1bit
C,T
The communication object will be visible with ―1bit‖ in the parameter ―object type for control air condition‖,
which is used to send out a telegram with high fan speed or medium speed.
Telegram value:
1——high fan speed
0——medium fan speed
171
Switch to low speed
Air condition
1bit
C,T
The communication object will be visible with ―1bit‖ in the parameter ―object type for control air condition‖,
which is used to send out a telegram with low fan speed.
Telegram value: