JVA SMS Gateway User Manual 

10 

Troubleshooting 

The JVA SMS Gateway is designed to work straight out of the box with little set up or configuration.  
The only crucial step is to ensure the unit has good mobile reception and an activated SIM card with 
credit.  Refer to the troubleshooting table below for more information. 

Fault 

Likely Cause 

Remedy 

No lights are on 

Power is not connected 
Power wires are reversed 

Check power connections 
Check voltage at power 
connections with a multimeter 

KPB light not flashing 

Keypad bus is not 
connected 
 

Check the keypad bus DATA and 
GND connections 
 

Error light flashing 

SIM card not inserted, not 
activated, or PIN locked  

Confirm SIM is activated by 
inserting into a mobile phone and 
sending and receiving texts 

Unit does not respond to 
SMS 

Poor signal strength 

Check antenna connection 
Move antenna mounting place 

Unit responds to SMS 
commands but does not 
reply 

Insufficient or expired 
credit 

Check the SIM card has credit 
available 

Unit does not control 
energisers 

Another keypad or keypad 
device is connected with 
keypad ID 6 

Disconnect the other keypad, or 
change its ID to something other 
than 3 or 6 

 

Master energiser did not 
see device at start-up 

Reset the master energiser 

 

Energiser malfunction 
 

Confirm a JVA keypad can control 
the energiser using the same 
connections 

 

Group configured 
incorrectly 

If there is more than one 
energiser, ensure one is 
configured as master (device ID 1) 
and the others have unique device 
IDs of 2 or more 

If the unit is still not working correctly, contact your nearest JVA distributor for technical support. 

Содержание PTE0319

Страница 1: ...www jva fence com au JVA SMS Gateway User Manual PTE0319...

Страница 2: ...y country Simply insert a valid topped up SIM card from your preferred carrier and you are ready to remotely control and monitor your energisers from anywhere in the world Features Works with entire J...

Страница 3: ...3 Antenna 4 Power and Keypad Bus 4 SIM card 4 Installation 5 Energiser Configuration 5 Operation 6 SMS Commands 6 PIN 6 Querying the Status 6 Querying the GSM signal 7 Report List 7 Controlling Energi...

Страница 4: ...circuit between the input terminals it will register the input as being On Just like the inputs on all JVA Z series devices the input can also be triggered by PLC or alarm panels by connecting the ri...

Страница 5: ...nnected devices Connect the DATA and GND terminals to the respective terminals of all connected devices The SMS Gateway requires 12V dc to operate This power may be supplied from the keypad bus of a c...

Страница 6: ...t side down with the notched corner to the lower right Clip the circuit board into the case back Connect the antenna Mount the antenna away from high voltage and mains power cables vertically if possi...

Страница 7: ...e unit will reply and inform everyone on the report list of the new PIN If you forget the PIN a factory reset must be performed See the section Factory Reset for more information Querying the Status T...

Страница 8: ...is supplied the sending number is removed If the parameter is supplied it can be either the number you wish to remove or the position of the number in the report list If entering a number it must be i...

Страница 9: ...seconds issue a status command 1234 s The unit will reply with a summary of all connected energisers Next add your number to the report list Send 1234 a The unit will reply with your number has been...

Страница 10: ...given index or the specified number from the report list 1234 r 1234 remove 1 1234 r 61412345678 61412345678 has been removed from the report list 1234 r 2 1234 remove 041 234 5678 Number not found in...

Страница 11: ...ting into a mobile phone and sending and receiving texts Unit does not respond to SMS Poor signal strength Check antenna connection Move antenna mounting place Unit responds to SMS commands but does n...

Страница 12: ...then re apply J4 This will reset the PIN to default clear the report list and clear the memory of seen devices JVA Distributors If you have any questions or need further assistance please email us at...

Отзывы: