14. REMOVING MALFUNCTIONS

Description of 

malfunction

Possible causes of malfunction

Measures of prevention/removal

Fan won’t work

Incorrect connection to power supply

Check for proper connection to power supply.

Locked impeller

Remove cause of locking

Damaged motor

Report at JUWENT service department

Low  fan  perfor-

mance

Incorrect impeller rotational direction (not in accor-

dance with marking on fan enclosure)

Change polarity of power supply connection

Contaminated fan inlet grate

Clean inlet grate

Fan high vibrations

Incorrect fan - roof base or roof base - fan connec-

tion.

Check for correct connections

Contaminated or damaged impeller

Remove impeller contaminations.

Report any impeller damages at JUWENT service depart-

ment

Fan 

operates 

with  excess  noise, 

knocks

Plays on connections between fan elements or on 

connection between fan and roof base

Remove  plays  on  connections  by  tightening  bolts  and 

screws

Rubbing between impeller and enclosure

Report at JUWENT service department

Damaged motor bearings

Activation  of  mo-

tor  overload  pro-

tections

Damaged or worn bearings.

Damaged motor windings (break, overheat).

Damaged circuit-breaker or protection system.

Report at JUWENT service department

Incorrectly set protection relay.

Loss of one of supply phases

Check electrical installation and protection systems

15. INFORMATION

As to all issues concerning the roof fan please contact JUWENT Production Plant or our Representatives

Содержание WD-16

Страница 1: ...3 56 09 POLAND I CONTACTS II ORIGINAL INSTRUCTION MANUAL III WARRANTY TERMS AND CONDITIONS IV UNIT STARTUP REPORT V INSPECTION AND MAINTENANCE DOCUMENT VI SERVICE NOTIFICATION VII LIST OF SUBASSEMBLIE...

Страница 2: ...Szyma ski Nowakowski General Partnership 31 Lubelska Str 08 500 Ryki POLAND phone 48 81 883 56 00 fax 48 81 883 56 09 info juwent com pl www juwent com pl Export department mob 48 502 087 841 mob 48 6...

Страница 3: ...3 www juwent com pl ROOF FANS WD size 16 to 40 II ORIGINAL INSTRUCTION MANUAL...

Страница 4: ...ONS 5 5 TECHNICAL DATA 6 6 ADDITIONAL EQUIPMENT 7 7 TRANSPORT 10 8 SAFETY RECOMMENDATIONS 10 9 INSTALLATION 11 10 ELECTRICAL INSTALLATION 11 11 AUTOMATION ELEMENTS 14 12 DEVICE COMMISSIONING 15 13 REP...

Страница 5: ...is not admissible The fans are suitable for operation with impeller vertical rotation axis and the air is being removed in the vertical direction The fans are adapted for mounting on universal roof ba...

Страница 6: ...distance of 1m at the distance of 5m Three phase two speed motors WD 16 940 54 42 50 45 1400 63 51 59 54 WD 20 940 56 44 52 47 1400 65 53 61 56 WD 25 940 58 46 54 49 1400 67 55 63 59 WD 31 5 960 62 50...

Страница 7: ...deration the directional factor Q 2 and at the distance of 1 and 5m from the fan Operating noise level in dB A acoustic pressure level at the air inlet side with taking into consideration the accommod...

Страница 8: ...self closing damper TWD TWD PLUS silencer DW DW PLUS inlet diffuser Roof base PWD Typ B I Typ B II Typ B III Roof base size A mm d mm d1 mm nx 10 H mm L mm L1 mm H1 mm PWD 16 340 160 190 4 125 590 675...

Страница 9: ...SWD 3 DW 3 KEO 3 WD 31 5 PU 4 PUT 4 PWDt 4 PM 4 SWD 4 DW 4 KEO 4 WD 40 PU 5 PUT 5 PWDt 5 PM 5 SWD 5 DW 5 KEO 5 F roof fan PWDt roof base PU roof base PUT noise damping roof base PM assembly plate c c...

Страница 10: ...with polyethylene foil The fans should be transported on one level so as to prevent any mechanical damages 8 SAFETY RECOMMENDATIONS Roof fans should be used in accordance with the operation manual In...

Страница 11: ...ucture and tightness of the roofing Connection ducts ate the fan suction side should have their own supports and mountings Roof fans mounted on silencers over the roof and ventilation ducts need to pe...

Страница 12: ...e electric connnection diagram of WD16 TD WD20 TD WD25 TD WD31 5 TD fans with two speed three phase motors Y Y connection DESIGNATIONS FOR DIAGRAMS PT Motor overcurrent protection K Contactor PZ Contr...

Страница 13: ...Contactor PZ Control button ON PW Control button OFF B BS Fuses WS Service switch Fig 3 Example electric connnection diagram of WD roof fans with single phase motors Fig 4 Example electric connnectio...

Страница 14: ...e phase WD 16 J WD 20 J WD 25 J WD 31 5 J roof fans Electric connections diagrams of WD roof fans with or wihout TR speed controller are shown at fig 3 and 4 Before starting the fan control knob must...

Страница 15: ...e starting current consumed by the motor If the current is lower than the rated current the fan can be considered fit for further use If any problems and disturbances arise during the commissioning sw...

Страница 16: ...nections Contaminated or damaged impeller Remove impeller contaminations Report any impeller damages at JUWENT service depart ment Fan operates with excess noise knocks Plays on connections between fa...

Страница 17: ...damages and aleatory damages or damages caused by the atmospheric factors b damages occurred as a result of non observance of typical rules or the rules required by the instruction manual related to...

Страница 18: ...p name and signature Motor current A User s representative stamp name and signature Remarks V INSPECTION AND MAINTENANCE DOCUMENT Date of inspection Executor of inspection stamp name and signature Ser...

Страница 19: ...y No Year of production Startup executed by Description of defect NOTE AFTER COPYING AND FILLING IN SEND THE NOTIFICATION BY FAX OR EMAIL TOGETHER WITH A COPY OF THE STARTUP REPORT JUWENT Company acce...

Страница 20: ...IN THE UNIT No Name of subassembly 1 Impeller in standard version 2 Impeller in acidproof steel version 3 Three phase single speed fan motor 4 Three phase two speed fan motor 5 Single phase fan motor...

Отзывы: