12. DEVICE COMMISSIONING

Commissioning of the fan should be carried out by properly qualified personnel only. Before the 

commissioning check the following: 

 

»

the fan for correct mounting,

 

»

the electrical connection for correct execution according to electrical diagram,

 

»

the enclosure for the presence of any foreign particles,

 

»

the impeller for free rotation without rubbing the fan inlet funnel.

Turn the fan on for few seconds and observe the direction of rotation to check compliance of the fan 

rotor rotation direction of with the direction indicated by arrow on the cover of the fan.

Once the above works are completed, turn the fan on and observe if there is no vibrations and 

noise emitted by the impeller. Moreover, during the first commissioning of the fan it is advisable to 

measure the starting current consumed by the motor. If the current is lower than the rated current, 

the fan can be considered fit for further use.

If any problems and disturbances arise during the commissioning, switch the power off 

and contact the supplier or the JUWENT service department.

13. REPAIR, MAINTENANCE AND WITHDRAWAL FROM USE

The fans are intended for continuous operation.

At least once a year check the condition of the fan motor (the motor bearings require no regular 

lubrication)  and,  if  necessary,  remove  the  defects  found  according  to  the  motor  manufacturer 

instructions.

Depending on the degree of air pollution, and no less than once a year, clean the fan impeller from 

any dust and dirt.

Fan bodies in the lower part are equipped in the outflow holes. You should check and if necessary 

clean above holes.

All maintenance and repair works should be carried out with voltage off.

 Use of high-pressure washers is not admissible.

Once the device is withdrawn from use, handle it to a proper waste treatment plant

Содержание WD-16

Страница 1: ...3 56 09 POLAND I CONTACTS II ORIGINAL INSTRUCTION MANUAL III WARRANTY TERMS AND CONDITIONS IV UNIT STARTUP REPORT V INSPECTION AND MAINTENANCE DOCUMENT VI SERVICE NOTIFICATION VII LIST OF SUBASSEMBLIE...

Страница 2: ...Szyma ski Nowakowski General Partnership 31 Lubelska Str 08 500 Ryki POLAND phone 48 81 883 56 00 fax 48 81 883 56 09 info juwent com pl www juwent com pl Export department mob 48 502 087 841 mob 48 6...

Страница 3: ...3 www juwent com pl ROOF FANS WD size 16 to 40 II ORIGINAL INSTRUCTION MANUAL...

Страница 4: ...ONS 5 5 TECHNICAL DATA 6 6 ADDITIONAL EQUIPMENT 7 7 TRANSPORT 10 8 SAFETY RECOMMENDATIONS 10 9 INSTALLATION 11 10 ELECTRICAL INSTALLATION 11 11 AUTOMATION ELEMENTS 14 12 DEVICE COMMISSIONING 15 13 REP...

Страница 5: ...is not admissible The fans are suitable for operation with impeller vertical rotation axis and the air is being removed in the vertical direction The fans are adapted for mounting on universal roof ba...

Страница 6: ...distance of 1m at the distance of 5m Three phase two speed motors WD 16 940 54 42 50 45 1400 63 51 59 54 WD 20 940 56 44 52 47 1400 65 53 61 56 WD 25 940 58 46 54 49 1400 67 55 63 59 WD 31 5 960 62 50...

Страница 7: ...deration the directional factor Q 2 and at the distance of 1 and 5m from the fan Operating noise level in dB A acoustic pressure level at the air inlet side with taking into consideration the accommod...

Страница 8: ...self closing damper TWD TWD PLUS silencer DW DW PLUS inlet diffuser Roof base PWD Typ B I Typ B II Typ B III Roof base size A mm d mm d1 mm nx 10 H mm L mm L1 mm H1 mm PWD 16 340 160 190 4 125 590 675...

Страница 9: ...SWD 3 DW 3 KEO 3 WD 31 5 PU 4 PUT 4 PWDt 4 PM 4 SWD 4 DW 4 KEO 4 WD 40 PU 5 PUT 5 PWDt 5 PM 5 SWD 5 DW 5 KEO 5 F roof fan PWDt roof base PU roof base PUT noise damping roof base PM assembly plate c c...

Страница 10: ...with polyethylene foil The fans should be transported on one level so as to prevent any mechanical damages 8 SAFETY RECOMMENDATIONS Roof fans should be used in accordance with the operation manual In...

Страница 11: ...ucture and tightness of the roofing Connection ducts ate the fan suction side should have their own supports and mountings Roof fans mounted on silencers over the roof and ventilation ducts need to pe...

Страница 12: ...e electric connnection diagram of WD16 TD WD20 TD WD25 TD WD31 5 TD fans with two speed three phase motors Y Y connection DESIGNATIONS FOR DIAGRAMS PT Motor overcurrent protection K Contactor PZ Contr...

Страница 13: ...Contactor PZ Control button ON PW Control button OFF B BS Fuses WS Service switch Fig 3 Example electric connnection diagram of WD roof fans with single phase motors Fig 4 Example electric connnectio...

Страница 14: ...e phase WD 16 J WD 20 J WD 25 J WD 31 5 J roof fans Electric connections diagrams of WD roof fans with or wihout TR speed controller are shown at fig 3 and 4 Before starting the fan control knob must...

Страница 15: ...e starting current consumed by the motor If the current is lower than the rated current the fan can be considered fit for further use If any problems and disturbances arise during the commissioning sw...

Страница 16: ...nections Contaminated or damaged impeller Remove impeller contaminations Report any impeller damages at JUWENT service depart ment Fan operates with excess noise knocks Plays on connections between fa...

Страница 17: ...damages and aleatory damages or damages caused by the atmospheric factors b damages occurred as a result of non observance of typical rules or the rules required by the instruction manual related to...

Страница 18: ...p name and signature Motor current A User s representative stamp name and signature Remarks V INSPECTION AND MAINTENANCE DOCUMENT Date of inspection Executor of inspection stamp name and signature Ser...

Страница 19: ...y No Year of production Startup executed by Description of defect NOTE AFTER COPYING AND FILLING IN SEND THE NOTIFICATION BY FAX OR EMAIL TOGETHER WITH A COPY OF THE STARTUP REPORT JUWENT Company acce...

Страница 20: ...IN THE UNIT No Name of subassembly 1 Impeller in standard version 2 Impeller in acidproof steel version 3 Three phase single speed fan motor 4 Three phase two speed fan motor 5 Single phase fan motor...

Отзывы: