Figure 22: Setting the Input Switches for Redundant Power
2—
1—
Input
2
switch
ON
Input
1
switch
ON
7.
Insert the AC power cord couplers into input
1
and input
2
on the PSM (see
CAUTION:
One input on each AC PSM must be powered by a dedicated
power feed derived from feed A. and the other input on each PSM must
be powered by dedicated power feed derived from feed B.
This configuration provides the commonly deployed A/B feed redundancy
for the system. For example, you can connect input
1
on each AC PSM to
feed A, and input
2
on each AC PSM to feed B.
Figure 23: Connecting the AC Power Cords to a PSM
8.
Insert the power cord plug into an external AC power receptacle.
9.
Reinstall the PSM into the chassis (see
), and tighten the captive
screw to secure it.
25
Copyright © 2014, Juniper Networks, Inc.
Connect Redundant AC Power to the PTX3000 AC Power Supply Modules