Cabinet requirements consist of:
•
Cabinet size
•
Clearance requirements
•
Cabinet airflow requirements
provides the cabinet requirements and specifications.
Table 40: Cabinet Requirements and Specifications
Guidelines
Cabinet
Requirement
•
You can mount the device in a cabinet that contains a 19-in. rack as defined in
Cabinets, Racks,
Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics
Industry Association (
http://www.ecianow.org/standards-practices/standards/
•
The minimum cabinet size must be able to accommodate the maximum external dimensions of the
device.
Cabinet size
•
The outer edges of the mounting brackets extend the width of the chassis to 19 in. (48.2 cm).
•
The minimum total clearance inside the cabinet is 30 in. (76.2 cm) between the inside of the front
door and the inside of the rear door.
Cabinet clearance
When you mount the device in a cabinet, ensure that ventilation through the cabinet is sufficient to
prevent overheating.
•
Ensure adequate cool air supply to dissipate the thermal output of the device or devices.
•
Ensure that the hot air exhaust of the chassis exits the cabinet without recirculating into the device.
An open cabinet (without a top or doors) that employs hot air exhaust extraction from the top
ensures the best airflow through the chassis. If the cabinet contains a top or doors, perforations in
these elements assist with removing the hot air exhaust.
•
Install the device in the cabinet in a way that maximizes the open space on the side of the chassis
that has the hot air exhaust.
•
Route and dress all cables to minimize the blockage of airflow to and from the chassis.
•
Ensure that the spacing of rails and adjacent cabinets is such that there is proper clearance around
the device and cabinet.
•
A cabinet larger than the minimum required provides better airflow and reduces the chance of
overheating.
Cabinet airflow
requirements
Related
Documentation
Rack-Mounting and Cabinet-Mounting Warnings on page 330
•
Clearance Requirements for Airflow and Hardware Maintenance for an EX9208 Switch
When planning the site for installing an EX9208 switch, you must allow sufficient
clearance around the switch.
•
For the cooling system to function properly, the airflow around the chassis must be
unrestricted. Allow at least 6 in. (15.2 cm) of clearance between side-cooled switches.
Allow 2.8 in. (7.1 cm) between the side of the chassis and any non-heat-producing
surface such as a wall. See
.
Copyright © 2017, Juniper Networks, Inc.
88
EX9208 Switch Hardware Guide
Содержание EX9208
Страница 1: ...EX9208 Switch Hardware Guide Modified 2017 01 04 Copyright 2017 Juniper Networks Inc ...
Страница 18: ...Copyright 2017 Juniper Networks Inc xviii EX9208 Switch Hardware Guide ...
Страница 24: ...Copyright 2017 Juniper Networks Inc xxiv EX9208 Switch Hardware Guide ...
Страница 26: ...Copyright 2017 Juniper Networks Inc 2 EX9208 Switch Hardware Guide ...
Страница 36: ...Copyright 2017 Juniper Networks Inc 12 EX9208 Switch Hardware Guide ...
Страница 62: ...Copyright 2017 Juniper Networks Inc 38 EX9208 Switch Hardware Guide ...
Страница 66: ...Copyright 2017 Juniper Networks Inc 42 EX9208 Switch Hardware Guide ...
Страница 74: ...Copyright 2017 Juniper Networks Inc 50 EX9208 Switch Hardware Guide ...
Страница 100: ...Copyright 2017 Juniper Networks Inc 76 EX9208 Switch Hardware Guide ...
Страница 102: ...Copyright 2017 Juniper Networks Inc 78 EX9208 Switch Hardware Guide ...
Страница 126: ...Copyright 2017 Juniper Networks Inc 102 EX9208 Switch Hardware Guide ...
Страница 170: ...Copyright 2017 Juniper Networks Inc 146 EX9208 Switch Hardware Guide ...
Страница 176: ...Copyright 2017 Juniper Networks Inc 152 EX9208 Switch Hardware Guide ...
Страница 178: ...Copyright 2017 Juniper Networks Inc 154 EX9208 Switch Hardware Guide ...
Страница 196: ...Copyright 2017 Juniper Networks Inc 172 EX9208 Switch Hardware Guide ...
Страница 214: ...Copyright 2017 Juniper Networks Inc 190 EX9208 Switch Hardware Guide ...
Страница 226: ...Copyright 2017 Juniper Networks Inc 202 EX9208 Switch Hardware Guide ...
Страница 228: ...Copyright 2017 Juniper Networks Inc 204 EX9208 Switch Hardware Guide ...
Страница 252: ...Copyright 2017 Juniper Networks Inc 228 EX9208 Switch Hardware Guide ...
Страница 304: ...Copyright 2017 Juniper Networks Inc 280 EX9208 Switch Hardware Guide ...
Страница 318: ...Copyright 2017 Juniper Networks Inc 294 EX9208 Switch Hardware Guide ...
Страница 324: ...Copyright 2017 Juniper Networks Inc 300 EX9208 Switch Hardware Guide ...
Страница 338: ...Copyright 2017 Juniper Networks Inc 314 EX9208 Switch Hardware Guide ...
Страница 340: ...Copyright 2017 Juniper Networks Inc 316 EX9208 Switch Hardware Guide ...
Страница 346: ...Copyright 2017 Juniper Networks Inc 322 EX9208 Switch Hardware Guide ...
Страница 360: ...Copyright 2017 Juniper Networks Inc 336 EX9208 Switch Hardware Guide ...
Страница 366: ...Copyright 2017 Juniper Networks Inc 342 EX9208 Switch Hardware Guide ...