Product characteristics
-
Connection of multiple power extensions to one dimmer possible
-
Operation using upstream dimmer
-
Electronic short-circuit protection with permanent switch-off after 7 seconds at the latest
-
Electronic over-temperature protection
i
Brightness differences between the lighting at the dimmer and the lightning at the power
extension are possible.
4 Information for electrically skilled persons
4.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.
Fitting and connecting the power extension
i
Use the same external conductor for dimmers and power extensions. Do not swap L and N
on the power extension. Otherwise, there is the risk of malfunction.
picture 2
(1) Power extension
(4) Dimmer
o
Fit the power extension.
i
Minimum diameter of ceiling opening for installation in false ceilings: 63 mm.
o
Connect the power extension according to the connection diagram (picture 2).
i
In the case of lighting systems with an output of more than 3500 W/VA, the installation
must divided across two circuit breakers with the same external conductor.
o
If multiple circuit breakers supply dangerous voltages to the device or load, couple the
circuit breaker to ensure tripping.
2/4
82539913
J:0082539913
11.08.2010
Light Management
TRONIC amplifier, built-in