Product characteristics 

Connection of multiple power extensions to one dimmer possible 

Operation using upstream dimmer 

Electronic short-circuit protection with permanent switch-off after 7 seconds at the latest 

Electronic over-temperature protection 

Brightness differences between the lighting at the dimmer and the lightning at the power 
extension are possible. 

4 Information for electrically skilled persons 

4.1 Fitting and electrical connection 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Before carrying out work on the device or load, disengage all the 
corresponding circuit breakers. Cover up live parts in the working environment. 

Fitting and connecting the power extension 

Use the same external conductor for dimmers and power extensions. Do not swap L and N 
on the power extension. Otherwise, there is the risk of malfunction. 

picture 2 

(1)  Power extension 
(4)  Dimmer 

Fit the power extension. 

Minimum diameter of ceiling opening for installation in false ceilings: 63 mm. 

Connect the power extension according to the connection diagram (picture 2). 

In the case of lighting systems with an output of more than 3500 W/VA, the installation 
must divided across two circuit breakers with the same external conductor. 

If multiple circuit breakers supply dangerous voltages to the device or load, couple the 
circuit breaker to ensure tripping. 

2/4 

82539913 
J:0082539913 

11.08.2010 

Light Management  

TRONIC amplifier, built-in 