Help in case of problems

Overviews 4 and 5 describe a few error messages 

and problems as well as probable causes and 

solutions.

Error message/problem

Possible cause

 

– Suggestions for troubleshooting

Display of device faults

Errors in the hardware configuration can be shown on 

the display. In this case, ERR and an error type are 

displayed as marquee text.

ERR CONFIGURATION

The controls and insert do not match.

 

– Only use matching components.

 

Turn the power off and on.

ERR COMMUNICATION

Communication problem between the controls and 

insert.

 

– Remove the controls and put them back on.

 

Turn the power off and on.

ERR  EXT SENSOR

External remote sensor broken/shorted/missing.

 

– Check whether the remote sensor is connected.

The limits of the display range are exceeded.

 

– Determine the cause and eliminate it.

Overview 4: Display of device faults

 Other problems and operating errors

Heating takes too long.

The programmed switching times or time are 

incorrect.

 

– Adapt programming (G1, G2).

The time switched to/from daylight savings.

 

– Adapt the time (G3, G5).

The optimum start is deactivated or does not run 

long enough (a few days) in order to determine the 

optimum preheating time.

 

– Select the optimum start (H7) and give the con-

troller time to adjust to the surrounding conditions.

The room is heating up too slowly.

The floor temperature is limited by the maximum 

limiter.

 

– Deactivate the upper limit (H3).
The room temperature is too hot.

The floor temperature is limited by the minimum 

limiter.

 

– Deactivate the bottom limit (H3).
No entries can be made.

Access protection is enabled.

 

– Disable access protection (G6).
The desired temperature cannot be set.

The temperature limitation prevents the desired 

setting.

 

– Reset the temperature limitation (G7).
The temperature display does not change.

The target temperature display is activated.

 

– Enable the display of the room temperature 

(G10).

Overview 5: Other problems and operating errors

ACCESSORIES

Remote sensor (not included in the delivery)

The external sensor must meet the requirements of 

protection class II.

Please use sensor cable H03VV-F for installation in 

protection tube or H05VV-F without protection tube.

Type: 

FF 7.8

Length: 

4 m (can be extended up to 50 m)

Wire: 

flexible, finely stranded

Stripped end: 

8 mm

Fig. 8: External remote sensor

Resistance/temperature table for remote sensor 

FF 7.8

Temperature [°C]

Resistance [k

W

]

 10

 66.8

 20

 41.3

 25

 33

 30

 26.3

 40

 17.0

 50

 11.3

Table 7: Resistance/temperature table for remote 

sensor FF 7.8