Help in case of problems
Overviews 4 and 5 describe a few error messages
and problems as well as probable causes and
solutions.
Error message/problem
Possible cause
– Suggestions for troubleshooting
Display of device faults
Errors in the hardware configuration can be shown on
the display. In this case, ERR and an error type are
displayed as marquee text.
ERR CONFIGURATION
The controls and insert do not match.
– Only use matching components.
–
Turn the power off and on.
ERR COMMUNICATION
Communication problem between the controls and
insert.
– Remove the controls and put them back on.
–
Turn the power off and on.
ERR EXT SENSOR
External remote sensor broken/shorted/missing.
– Check whether the remote sensor is connected.
The limits of the display range are exceeded.
– Determine the cause and eliminate it.
Overview 4: Display of device faults
Other problems and operating errors
Heating takes too long.
The programmed switching times or time are
incorrect.
– Adapt programming (G1, G2).
The time switched to/from daylight savings.
– Adapt the time (G3, G5).
The optimum start is deactivated or does not run
long enough (a few days) in order to determine the
optimum preheating time.
– Select the optimum start (H7) and give the con-
troller time to adjust to the surrounding conditions.
The room is heating up too slowly.
The floor temperature is limited by the maximum
limiter.
– Deactivate the upper limit (H3).
The room temperature is too hot.
The floor temperature is limited by the minimum
limiter.
– Deactivate the bottom limit (H3).
No entries can be made.
Access protection is enabled.
– Disable access protection (G6).
The desired temperature cannot be set.
The temperature limitation prevents the desired
setting.
– Reset the temperature limitation (G7).
The temperature display does not change.
The target temperature display is activated.
– Enable the display of the room temperature
(G10).
Overview 5: Other problems and operating errors
ACCESSORIES
Remote sensor (not included in the delivery)
The external sensor must meet the requirements of
protection class II.
Please use sensor cable H03VV-F for installation in
protection tube or H05VV-F without protection tube.
Type:
FF 7.8
Length:
4 m (can be extended up to 50 m)
Wire:
flexible, finely stranded
Stripped end:
8 mm
Fig. 8: External remote sensor
Resistance/temperature table for remote sensor
FF 7.8
Temperature [°C]
Resistance [k
W
]
10
66.8
20
41.3
25
33
30
26.3
40
17.0
50
11.3
Table 7: Resistance/temperature table for remote
sensor FF 7.8
Warranty
The warranty is provided in accordance with statutory
requirements via the specialist trade.