background image

Start-up

 

V

CAUTION! 

The heating system will malfunction if the 

controls are incorrectly set. 

This can damage the heating system. 

Only a technician may adjust the settings.

Set the heating mode when starting the controller.

•  Press 

M

 in the default display.

MENU briefly appears in the function display (8)

A help text as a marquee appears at the bottom 

edge of the display.

•  Press the 

+

 / 

-

 buttons until INSTALLER 

SETTINGS appears.

•  Select INSTALLER SETTINGS with 

O

.

CODE is displayed, and code number 0 flashes.

•  Select code 7 with 

+

 / 

-

, confirm with 

O

.

H1 and the marquee text APPLICATION is 

displayed.
Press 

O

.

ROOM 

is the default. When switching the heating 

mode, all of the user and installer settings are reset 

to the default.

•  Press 

+

 / 

-

 to set the desired heating mode and 

confirm with 

O

.

The heating mode is set.

Additional settings are available under “Installer 

settings”.

Installer settings

Overview 3

A marquee at the bottom of the display shows 

information for an individual menu items identified 

with H1 to H11.

 

W

Some menu items are not available under the 

control modes set under H1.

The abbreviations for the relevant control mode for 

each menu item are indicated in the table.

The abbreviations have the following meaning:

R

 = Room temperature controller

F

 = Floor temperature controller

L

 = Room temperature controller with a limiting 

function

(The menu displays and set all values are in 

UPPERCASE, and the 

settings are bold

)

H1 APPLICATION

R F L

Selection of the control method depending on the 

heating mode:

 

ROOM 

= Room temperature controller with 

the setting of whether or not a remote sensor is 

connected: 

EXTERN SENSOR = YES/

NO

 

– FLOOR = Floor temperature controller

 

– LIMITER = Room temperature controller with 

limiter

Select with 

+

 / 

-

, confirm with 

O

.

H2  CONTROL MODE

R F L

Select the control mode:

 

PWM

 = Pulse width modulation with the cycle 

time set in minutes: 

10

, 15 ... 30.

 

W

For fast heating systems, select a short cycle 

time, for slow heating systems, select a long 

cycle time. The minimum on/off time is 10% of 

the cycle time.

 

– ON/OFF= two-point control with adjustable 

hysteresis (

OFF

, 0.1°C, 0.2°C … 5.0°C) and 

minimum relay on/off time in minutes 

 

(1, 2 … 

10

 ... 30).

 

W

If the hysteresis is not set, the relay switches 

with the minimum on/off time even when the 

temperature differences are very small.

Select with 

+

 / 

-

, confirm with 

O

.

H3  MIN/MAX FLOOR TEMP

L

Setting the top and bottom limit for the floor temper

-

ature:

 

LOWER TEMP LIMIT: The floor should not be 

colder than the set temperature (

OFF

, 10.0°C, 

10.5°C … 35.0°C).

 

UPPER TEMP LIMIT: The floor should not be 

warmer than the set temperature (OFF, 10.0°C, 

10.5°C …

 35.0°C

... 40.0°C, OFF).

Set the temperatures with 

+

 / 

-

 and confirm with 

O

.

 

W

To deactivate the top or bottom limit, set the 

bottom temperature limit < 10°C, or the top 

temperature limit > 40°C with 

+

 / 

-

 . OFF is 

displayed.

H4  HEATING OR COOLING

R

Switching the controller between heating and 

cooling mode:

 

HEATING

 

– COOLING

 

W

Precondition for switching to cooling mode: 

H2 - CONTROL MODE = ON/OFF

 

W

When switching to cooling mode, H6 - FROST 

PROTECTION is automatically set to OFF, and 

H7 - OPTIMUM START is set to NO.

 

W

The switching times and temperatures of heat-

ing mode are used.

Select with 

+

 / 

-

, confirm with 

O

.

H5  VALVE PROTECTION

R

L

Protection of the valve from seizing after long pe-

riods of nonuse. The valve is opened at 10 o'clock 

every day for the time in minutes set here:  

OFF, 1, 2, 

3

 … 10.

Set the opening time with 

+

 / 

-

 and confirm with 

O

.

H6  FROST PROTECTION

R F L

Setting the frost protection temperature:

 

– For H1 = ROOM or LIMITER: 

OFF, 

5.0°C

, 5.5°C … 30.0°C

 

– For H1 = FLOOR: 

OFF, 

10.0°C

, 10.5°C … 40.0°C

Press 

+

 / 

-

 to set the temperature and confirm 

with 

O

.

If the temperature falls below the set frost protection 

temperature, heating is turned on.

 

W

To deactivate the frost protection with a button 

select the OFF setting under the lowest 

temperature.

 

W

Frost protection mode is only possible when 

the control is shut off; see user settings:

 

G4 - OFF HEATING PERMANENT = YES

H7  OPTIMUM START

R F L

This setting causes the system to go to the set 

target temperature upon starting:

 

YES

 = OPTIMUM START

 

– NO

AUTO_ is displayed in the required preheating time.

Select YES/NO with 

+

 / 

-

, confirm with 

O

.

H8  VALVES NORMALLY OPEN

R

L

Reverse of the relay switching behaviour for using 

actuators that are normally open:

 

– YES = activated

 

NO

 = deactivated

Select YES/NO with 

+

 / 

-

, confirm with 

O

.

H9  ENERGY COUNTER RESET

R F L

Reset to zero the energy cost meter set under G8/

G9 (see user settings).

 

– YES = reset

 

NO

Select YES/NO with 

+

 / 

-

, confirm with 

O

.

H10  FLOOR TEMPERATURE DISPLAY

L

Display the current floor temperature for service 

purposes.
H11  RESET ALL

R F L

Reset to the defaults all of the settings made in the 

menus for the installer and user.

 

– YES = reset

 

NO

Select YES/NO with 

+

 / 

-

, confirm with 

O

.

 

W

For safety reasons settings among H1 and the 

selected language will not be changed with a 

RESET.

Overview 3: Installer settings

Open the settings menu and make settings

The menu ID H1 appears in the display (8), and 

APPLICATION appears at the bottom as a marquee.

•  Press 

+

 / 

-

 o select the desired menu.

The menu ID and a help text appear at the 

bottom edge of the display (7) and (11).

• 

Confirm with 

O

.

The first settable value flashes in the display.

•  Set the desired value by pressing 

+

 / 

-

.

• 

Confirm with 

O

.

The second settable value flashes.

•  Repeat the aforementioned steps until all the 

values are set.

The display returns to higher-level and displays 

the menu ID.

Appendix

Do not dispose of this product in household 

garbage. Dispose of the device in a facility 

designated for electronics waste. Consult 

the local recycling authorities.

C

This symbol confirms that the product is in 

conformance with the relevant guidelines.

Technical data

Operating voltage: 

AC 230 V ~

Rated frequency: 

50 Hz

Output: 

Make contact relay, non-floating

Switching current: 

10 mA ... 16 (4) A, 230 V~ 

Power consumption: 

~ 1.2 W

Degree of protection: 

IP 30

Protection class:  II (with corresponding installation)

Pollution category: 

2

Ambient temperature: 

- operation: 

0°C to 40 °C (without thawing)

- Storage: 

-20°C to 70°C (without thawing)

Temperature setting range (in increments of 0.5 °C): 

- as a room temperature controller: 

5°C ... 30 °C  

- as a floor temperature controller  10°C ... 40 °C

Temperature display: 

in increments of 0.1°C

Output signal: 

Pulse width modulation (PWM) 

 

or two-point control ( on/off)

PWM cycle time: 

adjustable (10 ... 30 min)

Hysteresis: 

adjustable (with two-point control)

Minimum switching time  

adjustable (1 ... 30 min)  

Rated impulse voltage: 

4 kV

Temperature for the ball thrust test: 

75 ± 2°C

Voltage and current for the 

EMC emitted interference  test: 

230 V, 0.1 A

Software class: 

A

Accuracy: 

< 4 min/year

Reserve power: 

~ 10 years (lithium cell)