Start-up
V
CAUTION!
The heating system will malfunction if the
controls are incorrectly set.
This can damage the heating system.
Only a technician may adjust the settings.
Set the heating mode when starting the controller.
• Press
M
in the default display.
MENU briefly appears in the function display (8)
.
A help text as a marquee appears at the bottom
edge of the display.
• Press the
+
/
-
buttons until INSTALLER
SETTINGS appears.
• Select INSTALLER SETTINGS with
O
.
CODE is displayed, and code number 0 flashes.
• Select code 7 with
+
/
-
, confirm with
O
.
H1 and the marquee text APPLICATION is
displayed.
Press
O
.
ROOM
is the default. When switching the heating
mode, all of the user and installer settings are reset
to the default.
• Press
+
/
-
to set the desired heating mode and
confirm with
O
.
The heating mode is set.
Additional settings are available under “Installer
settings”.
Installer settings
Overview 3
A marquee at the bottom of the display shows
information for an individual menu items identified
with H1 to H11.
W
Some menu items are not available under the
control modes set under H1.
The abbreviations for the relevant control mode for
each menu item are indicated in the table.
The abbreviations have the following meaning:
R
= Room temperature controller
F
= Floor temperature controller
L
= Room temperature controller with a limiting
function
(The menu displays and set all values are in
UPPERCASE, and the
settings are bold
)
H1 APPLICATION
R F L
Selection of the control method depending on the
heating mode:
–
ROOM
= Room temperature controller with
the setting of whether or not a remote sensor is
connected:
EXTERN SENSOR = YES/
NO
– FLOOR = Floor temperature controller
– LIMITER = Room temperature controller with
limiter
Select with
+
/
-
, confirm with
O
.
H2 CONTROL MODE
R F L
Select the control mode:
–
PWM
= Pulse width modulation with the cycle
time set in minutes:
10
, 15 ... 30.
W
For fast heating systems, select a short cycle
time, for slow heating systems, select a long
cycle time. The minimum on/off time is 10% of
the cycle time.
– ON/OFF= two-point control with adjustable
hysteresis (
OFF
, 0.1°C, 0.2°C … 5.0°C) and
minimum relay on/off time in minutes
(1, 2 …
10
... 30).
W
If the hysteresis is not set, the relay switches
with the minimum on/off time even when the
temperature differences are very small.
Select with
+
/
-
, confirm with
O
.
H3 MIN/MAX FLOOR TEMP
L
Setting the top and bottom limit for the floor temper
-
ature:
–
LOWER TEMP LIMIT: The floor should not be
colder than the set temperature (
OFF
, 10.0°C,
10.5°C … 35.0°C).
–
UPPER TEMP LIMIT: The floor should not be
warmer than the set temperature (OFF, 10.0°C,
10.5°C …
35.0°C
... 40.0°C, OFF).
Set the temperatures with
+
/
-
and confirm with
O
.
W
To deactivate the top or bottom limit, set the
bottom temperature limit < 10°C, or the top
temperature limit > 40°C with
+
/
-
. OFF is
displayed.
H4 HEATING OR COOLING
R
Switching the controller between heating and
cooling mode:
–
HEATING
– COOLING
W
Precondition for switching to cooling mode:
H2 - CONTROL MODE = ON/OFF
W
When switching to cooling mode, H6 - FROST
PROTECTION is automatically set to OFF, and
H7 - OPTIMUM START is set to NO.
W
The switching times and temperatures of heat-
ing mode are used.
Select with
+
/
-
, confirm with
O
.
H5 VALVE PROTECTION
R
L
Protection of the valve from seizing after long pe-
riods of nonuse. The valve is opened at 10 o'clock
every day for the time in minutes set here:
OFF, 1, 2,
3
… 10.
Set the opening time with
+
/
-
and confirm with
O
.
H6 FROST PROTECTION
R F L
Setting the frost protection temperature:
– For H1 = ROOM or LIMITER:
OFF,
5.0°C
, 5.5°C … 30.0°C
– For H1 = FLOOR:
OFF,
10.0°C
, 10.5°C … 40.0°C
Press
+
/
-
to set the temperature and confirm
with
O
.
If the temperature falls below the set frost protection
temperature, heating is turned on.
W
To deactivate the frost protection with a button
-
select the OFF setting under the lowest
temperature.
W
Frost protection mode is only possible when
the control is shut off; see user settings:
G4 - OFF HEATING PERMANENT = YES
H7 OPTIMUM START
R F L
This setting causes the system to go to the set
target temperature upon starting:
–
YES
= OPTIMUM START
– NO
AUTO_ is displayed in the required preheating time.
Select YES/NO with
+
/
-
, confirm with
O
.
H8 VALVES NORMALLY OPEN
R
L
Reverse of the relay switching behaviour for using
actuators that are normally open:
– YES = activated
–
NO
= deactivated
Select YES/NO with
+
/
-
, confirm with
O
.
H9 ENERGY COUNTER RESET
R F L
Reset to zero the energy cost meter set under G8/
G9 (see user settings).
– YES = reset
–
NO
Select YES/NO with
+
/
-
, confirm with
O
.
H10 FLOOR TEMPERATURE DISPLAY
L
Display the current floor temperature for service
purposes.
H11 RESET ALL
R F L
Reset to the defaults all of the settings made in the
menus for the installer and user.
– YES = reset
–
NO
Select YES/NO with
+
/
-
, confirm with
O
.
W
For safety reasons settings among H1 and the
selected language will not be changed with a
RESET.
Overview 3: Installer settings
Open the settings menu and make settings
The menu ID H1 appears in the display (8), and
APPLICATION appears at the bottom as a marquee.
• Press
+
/
-
o select the desired menu.
The menu ID and a help text appear at the
bottom edge of the display (7) and (11).
•
Confirm with
O
.
The first settable value flashes in the display.
• Set the desired value by pressing
+
/
-
.
•
Confirm with
O
.
The second settable value flashes.
• Repeat the aforementioned steps until all the
values are set.
The display returns to higher-level and displays
the menu ID.
Appendix
Do not dispose of this product in household
garbage. Dispose of the device in a facility
designated for electronics waste. Consult
the local recycling authorities.
C
This symbol confirms that the product is in
conformance with the relevant guidelines.
Technical data
Operating voltage:
AC 230 V ~
Rated frequency:
50 Hz
Output:
Make contact relay, non-floating
Switching current:
10 mA ... 16 (4) A, 230 V~
Power consumption:
~ 1.2 W
Degree of protection:
IP 30
Protection class: II (with corresponding installation)
Pollution category:
2
Ambient temperature:
- operation:
0°C to 40 °C (without thawing)
- Storage:
-20°C to 70°C (without thawing)
Temperature setting range (in increments of 0.5 °C):
- as a room temperature controller:
5°C ... 30 °C
- as a floor temperature controller 10°C ... 40 °C
Temperature display:
in increments of 0.1°C
Output signal:
Pulse width modulation (PWM)
or two-point control ( on/off)
PWM cycle time:
adjustable (10 ... 30 min)
Hysteresis:
adjustable (with two-point control)
Minimum switching time
adjustable (1 ... 30 min)
Rated impulse voltage:
4 kV
Temperature for the ball thrust test:
75 ± 2°C
Voltage and current for the
EMC emitted interference test:
230 V, 0.1 A
Software class:
A
Accuracy:
< 4 min/year
Reserve power:
~ 10 years (lithium cell)