Setting the offset
This function allows the adjustment of the position of the control knob so that it cor-
responds to the room temperature. Thus, the indication of the temperature via the
control button is comparable in different rooms. An adaptation of up to +/- 3 °C is
possible.
This setting is only possible if the lower temperature limit has not been raised
by the blue setting ring (see Setting the temperature limits).
Precondition: The desired setpoint temperature has been reached in the room.
■
Turn the control knob to 5 °C (left stop) and press twice in quick succession
(double-click).
The LED flashes quickly, alternately red and green.
■
Turn the control knob to the desired position for the current room temperature
and press it for longer than one second.
The control knob position is saved and the LED lights up green for 5 seconds.
If the LED flashes red for 5 seconds, the change was greater than +/- 3 °C and
the adaptation is discarded.
8
Technical data
Rated voltage
AC 24 V SELV (± 10%)
Mains frequency
50 / 60 Hz
Standby power
max. 0.1 W
Connected load
max. 24 W
Connection: Thermal valve drive 24 V~, art. no. TSA24NCWW
Number valve drive
1 ... 5
Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Cable length inputs
max. 100 m
Controller class (EU 811/2013)
IV
Contribution to energy efficiency
2%
9
Warranty
The warranty is provided in accordance with statutory requirements via the specialist
trade.
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Room thermostat (heating/cooling) 24 V
11 / 12
82405003
16.09.2022
J0082405003