grey, GY,
1
Installation button connection
PE
Earth conductor
o
Connect optional installation button (13) to all presence detectors (figure 7). This is only
necessary if manual operation is also desired.
i
Lit installation buttons may only be connected if they have an N terminal.
o
Screw presence detector to connection box (4) with screws (12) and mounting pins (11)
(figure 4).
5.2 Commissioning
Testing the detection area
The presence detector is mounted and connected properly.
o
Pull off decor ring (3).
o
Set
lux
adjuster to
3
(figure 1).
The presence detector operates independently of the brightness.
o
Turn
time
adjuster to
test
(figure 1).
The presence detector switches on for approx. 1 second when there is motion.
o
Pace off the detection area, paying attention to reliable detection and interference sources.
Limit detection area if necessary using the push-on cover.
i
In the case of presence detectors connected in parallel, check the detection areas one
after the other. Turn
lux
adjuster to
0
on the presence detectors whose detection areas are
not being tested (figure 1).
o
Attach decor ring (3).
Limiting the detection area
Figure 8: Push-on cover
The push-on cover can be used to limit the detection area, e.g. in order to mask out
interference sources.
Cover size
Detection area on the floor
Complete cover
Ø approx 2.2 m
Area I cut out
Ø approx. 4 m
Areas I + II cut out
Ø approx. 6 m
7/11
82552623
J0082552623
04.09.2015
Light Management
Presence detector compact