Jung PMK 360 AL Скачать руководство пользователя страница 7

grey, GY, 

1

Installation button connection

PE

Earth conductor

o

Connect optional installation button (13) to all presence detectors (figure 7). This is only
necessary if manual operation is also desired.

i

Lit installation buttons may only be connected if they have an N terminal.

o

Screw presence detector to connection box (4) with screws (12) and mounting pins (11)
(figure 4).

5.2 Commissioning

Testing the detection area

The presence detector is mounted and connected properly.

o

Pull off decor ring (3).

o

Set 

lux

 adjuster to

3

 (figure 1).

The presence detector operates independently of the brightness.

o

Turn 

time

 adjuster to 

test

 (figure 1).

The presence detector switches on for approx. 1 second when there is motion.

o

Pace off the detection area, paying attention to reliable detection and interference sources.
Limit detection area if necessary using the push-on cover. 

i

In the case of presence detectors connected in parallel, check the detection areas one
after the other. Turn 

lux

 adjuster to 

0

 on the presence detectors whose detection areas are

not being tested (figure 1).

o

Attach decor ring (3).

Limiting the detection area

Figure 8: Push-on cover

The push-on cover  can be used to limit the detection area, e.g. in order to mask out
interference sources.

Cover size

Detection area on the floor

Complete cover

Ø approx 2.2 m

Area I cut out

Ø approx. 4 m

Areas I + II cut out

Ø approx. 6 m

7/11

82552623
J0082552623

04.09.2015

Light Management 

Presence detector compact

Содержание PMK 360 AL

Страница 1: ...ltage Danger of electric shock Always disconnect before carrying out work on the devise or load At the same time take into account all circuit breakers that supply dangerous voltage to the device or l...

Страница 2: ...sence detector A soon as a presence detector switches on this is detected by the other presence detectors They switch on when there is motion in their detection area unless the brightness in their det...

Страница 3: ...eous light e g daylight o Press the installation button within 3 minutes after switch off The light is switched on The light remains switched on as long as the presence detector detects motions The br...

Страница 4: ...duced i If necessary the detection area can be limited using the push on cover see Limiting the detection area o Select a vibration free installation location vibrations can lead to unwanted switching...

Страница 5: ...e away from the windows This reduces the effects of scattered light o Fasten connection both 4 with enclosed anchor screw set through holes 8 figure 5 i Alternatively the presence detector can also be...

Страница 6: ...ce detector to connection box 4 with screws 12 and mounting pins 11 figure 4 Connecting presence detectors in parallel Figure 7 Connection diagram for connection in parallel Several presence detectors...

Страница 7: ...re 1 The presence detector switches on for approx 1 second when there is motion o Pace off the detection area paying attention to reliable detection and interference sources Limit detection area if ne...

Страница 8: ...e is too dark load remains switched on when motion detected When no motion is detected it is switched off after the run on time elapses LED on Monitored surface is bright enough due to lighting that i...

Страница 9: ...rox 10 1000 lx Connected load at 25 C Incandescent lamps 1000 W HV halogen lamps 1000 W Tronic transformers 750 W Inductive transformers 750 VA Fluorescent lamps uncompensated 500 VA Fluorescent lamps...

Страница 10: ...tection is switched off Switch on via extension Turn lux adjuster in 3 direction see Calibrating the brightness Switched off via extension Switch on via extension Presence detector switches on without...

Страница 11: ...h off Turn lux adjuster in 3 direction see Commissioning section 6 3 Accessories Not combinable with devices from the light management system 6 4 Warranty The warranty is provided in accordance with s...

Отзывы: