6 Appendix
6.1 Technical data
KNX
KNX medium
TP 1
Commissioning mode
S mode
Rated voltage KNX
DC 21 ... 32 V SELV
Power consumption KNX
max. 240 mW
Connection mode KNX
Connection terminal
Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Control outputs
Control voltage
1 ... 10 V
Control current per output
max. 100 mA
Cable length
max. 500 m (0.5mm
2
)
Switching outputs
Contact type
µ contact
Switching voltage
AC 250 / 400 V
Switching current 230 V AC 1
16 A
Switching current 230 V AC 3
10 A
Switching current 400 V AC 1
10 A
Switching current 400 V AC 3
6 A
Fluorescent lamps
10 AX
Switching voltage DC
DC 12 ... 24 V
Switching current DC
16 A
Minimum switching current
100 mA
Switch-on current 150 µs
400 A
Switch-on current 600 µs
200 A
Ohmic load
3680 W
Capacitive load
10 A / 140 µF
Lamp loads
Incandescent lamps
2500 W
HV halogen lamps
2500 W
LV halogen lamps with inductive transformer
1200 VA
LV halogen lamps with Tronic transformer
1500 W
Fluorescent lamps T5/T8
uncompensated
2500 W
parallel compensated
1300 W / 140 µF
Duo circuit
2300 W / 140 µF
Compact fluorescent lamps
uncompensated
2500 W
parallel compensated
1300 W / 140 µF
Mercury vapour lamps
uncompensated
2000 W
parallel compensated
2000 W / 140 µF
Connection
Single stranded
0.5 ... 4 mm²
finely stranded without conductor sleeve
0.34 ... 4 mm²
finely stranded with conductor sleeve
0.14 ... 2.5 mm²
Fitting width
72 mm / 4 modules
6.2 Accessories
Connection cover
Art.-No.: 2050 K
5/6
82506533
J:0082506533
13.08.2010
Control unit 1-10 V, 3-gang