Intended use 

Switching and brightness setting for lamps with operating devices with 1-10-V interface 

Mounting on DIN rail according to EN 60715 in distribution boxes 

Product characteristics 

Relay switch contact for switching the connected loads 

Manual operation of the relay independently of the bus 

Various L1, L2 and L3 external conductors can be connected. 

No additional power supply necessary 

Feedback of switching state and brightness value 

Switch position display 

Switch-on and dimming behaviour can be set 

Time dimmer can be set 

Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time 

Integration into light scenes 

4 Operation 

Switching relay contacts manually 

The status of the relay is reflected by the slide switches (3) on the front of the device (picture 1). 
At the same time they can be used for manual operation of the relay outputs sing a suitable 
tool. 

Move slide switch to 

ON

 position. 

Relay contact is closed, load is switched on. 

Move slide switch to 

OFF

 position. 

Relay contact is open, load is switched off. 

The position of the slide switch immediately reflects the status of the relay, regardless of 
whether the output is in NO or NC mode of operation. 

Manual switching of the relays is independent of the bus. Thus in case of manual switching 
there will be no feedback via the bus. 

Outputs disabled via software can still be switched manually. 

5 Information for electrically skilled persons 

5.1 Fitting and electrical connection 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Before carrying out work on the device or load, disengage all the 
corresponding circuit breakers. Cover up live parts in the working environment. 

Fitting the device 

Observe the temperature range. Ensure adequate cooling. 

Mount device on DIN rail. Output terminals must be at the top. 

2/6 

82506533 
J:0082506533 

13.08.2010 

Control unit 1-10 V, 3-gang 

Содержание KNX 2193 REG

Страница 1: ...mains voltage and control voltage circuits These instructions are an integral part of the product and must remain with the end customer 2 Device components picture 1 1 Connection for control outputs 2 Connection for switching outputs 3 Slide switch Status indication 4 Programming LED 5 Programming button 6 KNX connection 3 Function System information This device is a product of the KNX system and ...

Страница 2: ...f the device picture 1 At the same time they can be used for manual operation of the relay outputs sing a suitable tool o Move slide switch to ON position Relay contact is closed load is switched on o Move slide switch to OFF position Relay contact is open load is switched off i The position of the slide switch immediately reflects the status of the relay regardless of whether the output is in NO ...

Страница 3: ...g devices generate high current spikes when they are switched on that can result in sticking of the relay contacts Note switch on currents In the case of loads with high switch on current use switch on current limiter or separate load protection o Connect the device according to the connection diagram picture 2 o Connect load operating devices with protective earth conductor in accordance with the...

Страница 4: ...over picture 4 Removing the cover o Press the cover to the side and pull it off picture 4 5 2 Commissioning Load the address and the application software o Switch on the bus voltage o Assign physical addresses and load application software into the device o Note the physical address on the device label 4 6 82506533 J 0082506533 13 08 2010 Control unit 1 10 V 3 gang ...

Страница 5: ... Minimum switching current 100 mA Switch on current 150 µs 400 A Switch on current 600 µs 200 A Ohmic load 3680 W Capacitive load 10 A 140 µF Lamp loads Incandescent lamps 2500 W HV halogen lamps 2500 W LV halogen lamps with inductive transformer 1200 VA LV halogen lamps with Tronic transformer 1500 W Fluorescent lamps T5 T8 uncompensated 2500 W parallel compensated 1300 W 140 µF Duo circuit 2300 ...

Страница 6: ...ax 49 0 23 55 80 61 89 mail vki jung de Technik Allgemein Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 mail vkm jung de Technik KNX Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 mail vkm jung de The Œ symbol is a free trade symbol which is solely intended for the authorities and does not guarantee any properties ALBRECHT JUNG GMBH CO KG Volmestraße 1 D 58579 Schalksm...

Отзывы: