Power consumption KNX
max. 125 mW
Connection type for bus
Connection terminal
5.2 Troubleshooting
Actuators of an output or all outputs do not switch
Cause: An output is overloaded.
Determine cause of the overload switch-off. Eliminate short-circuits, replace defective
actuators. Check number of actuators connected to the output, reduce if necessary. Do not
exceed max. switching current.
Reset overload switch-off: disconnect device from mains completely for approx. 5 seconds,
switch off miniature circuit-breaker. Then switch on again.
i
In case of overload, initially one or both output groups switch off for approx. 6 minutes.
After that the devices determines which output is overloaded and switches it off
permanently. This rest and test phase typically lasts 6...20 minutes.
i
After resetting of the overload switch-off it is no longer possible for the device to determine
which output is overloaded. If the cause is not eliminated, overload switch-off will occur
again.
5.3 Accessories
Connection cover
Art.-No.: 2050 K
5.4 Warranty
We reserve the right to make technical and formal changes to the product in the interest of
technical progress.
We provide a warranty as provided for by law.
Please send the unit postage-free with a description of the defect to our central customer
service office:
ALBRECHT JUNG GMBH & CO. KG
Service Center
Kupferstr. 17-19
D-44532 Lünen
Service-Line: +49 (0) 23 55 . 80 65 51
Telefax: +49 (0) 23 55 . 80 61 89
[email protected]
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
D-58579 Schalksmühle
Telefon: +49.23 55.8 06-0
Telefax: +49.23 55.8 06-1 89
E-mail: [email protected]
Internet: www.jung.de
www.jung-katalog.de
5/5
82543713
J:0082543713
20.12.2011
Heating actuator 6-gang