Power consumption KNX 

max. 125 mW 

Connection type for bus 

Connection terminal 

5.2 Troubleshooting 

Actuators of an output or all outputs do not switch 

Cause: An output is overloaded.  

Determine cause of the overload switch-off. Eliminate short-circuits, replace defective 
actuators. Check number of actuators connected to the output, reduce if necessary. Do not 
exceed max. switching current. 
Reset overload switch-off: disconnect device from mains completely for approx. 5 seconds, 
switch off miniature circuit-breaker. Then switch on again. 

In case of overload, initially one or both output groups switch off for approx. 6 minutes. 
After that the devices determines which output is overloaded and switches it off 
permanently. This rest and test phase typically lasts 6...20 minutes.  

After resetting of the overload switch-off it is no longer possible for the device to determine 
which output is overloaded. If the cause is not eliminated, overload switch-off will occur 
again. 

5.3 Accessories 

Connection cover

Art.-No.: 2050 K

5.4 Warranty 

We reserve the right to make technical and formal changes to the product in the interest of 
technical progress. 
We provide a warranty as provided for by law. 
Please send the unit postage-free with a description of the defect to our central customer 
service office: 

ALBRECHT JUNG GMBH & CO. KG 

Service Center 
Kupferstr. 17-19 
D-44532 Lünen 
Service-Line: +49 (0) 23 55 . 80 65 51 
Telefax: +49 (0) 23 55 . 80 61 89 
[email protected] 

ALBRECHT JUNG GMBH & CO. KG 

Volmestraße 1 
D-58579 Schalksmühle 

Telefon: +49.23 55.8 06-0 
Telefax: +49.23 55.8 06-1 89 
E-mail: [email protected] 
Internet: www.jung.de 
              www.jung-katalog.de 

5/5 

82543713 
J:0082543713 

20.12.2011 

Heating actuator 6-gang 

Содержание KNX 2136 REG HZ

Страница 1: ...ed from the mains even when the device is switched off These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 1 Connection of electrothermal actuators 2 Programming LED 3 Programming button 4 KNX connection 5 Mains voltage connection 3 Function System information This device is a product of the KNX system and complies with the KNX ...

Страница 2: ... and connected actuators in case of overload the device determines which output is involved and switches it off Non overloaded outputs continue to work which means that the rooms in question are still heated In case of major overloads the actuator initially switches all off the outputs A1 A6 off In the case of more minor overloads the actuators switches output groups A1 A3 and or A4 A6 off The act...

Страница 3: ...t the neutral conductor from the output terminals through to additional devices Do not connect any inductive or capacitive loads o Connect the outputs according to connection diagram figure 2 o Connect the mains voltage figure 2 o Connect bus cable with connecting terminal Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connec...

Страница 4: ... frequency 50 60 Hz Power loss approx 2 W Ambient conditions Ambient temperature 5 45 C Storage transport temperature 25 70 C Heating outputs Contact type Semi conductor Triac ε Switching voltage AC 230 V 240 V Switching current 5 50 mA Switch on current max 1 5 A 2 sec Number of drives per output max 4 Housing Fitting width 72 mm 4 modules Connection of outputs Connection mode Screw terminal Sing...

Страница 5: ... typically lasts 6 20 minutes i After resetting of the overload switch off it is no longer possible for the device to determine which output is overloaded If the cause is not eliminated overload switch off will occur again 5 3 Accessories Connection cover Art No 2050 K 5 4 Warranty We reserve the right to make technical and formal changes to the product in the interest of technical progress We pro...

Отзывы: