carried out with the aid of KNX-certified software. The latest versions of product database and 
the technical descriptions are available on our website. 

Intended use 

Switching of electrothermal actuators for heaters or cooling ceilings 

Installation in distribution boxes on DIN rail according to DIN EN 60715 

Product characteristics 

Switching operation or PWM operation 

Actuators with characteristics opened or closed without power 

Overload-protected, short circuit-protected 

Protection against jamming valves 

Forced position 

Various setpoints for forced position or emergency operation in case of bus failure for 
summer or winter 

Cyclical monitoring of the input signals can be parameterized 

Feedback via bus, e.g. in case of mains failure, overload or sensor failure 

PWM operation: electrothermal actuators only have the positions "open" and "closed". In 
PWM operation, switch-on and switch-off during the drive's cycle time achieves an almost 
constant behaviour. 

Overload protection 

In order to protect the device and connected actuators, in case of overload the device 
determines which output is involved and switches it off. Non-overloaded outputs continue to 
work, which means that the rooms in question are still heated. 

In case of major overloads the actuator initially switches all off the outputs 

A1...A6

 off. 

In the case of more minor overloads the actuators switches output groups 

A1...A3

 and/or 

A4...A6

 off. 

The actuator determines the overloaded output in up to 4 test cycles. 

If in the event of only a minor overload it is not possible to unambiguously identify any 
output as overloaded, then the actuator switches individual outputs off one after the other. 

The overload can be reported to the bus for each output. 

4 Information for electrically skilled persons 

4.1 Fitting and electrical connection 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Before carrying out work on the device or load, disengage all the 
corresponding circuit breakers. Cover up live parts in the working environment. 

Fitting the device 

Observe the temperature range. Ensure adequate cooling. 

Mount device on DIN rail. Output terminals must be at the top. 

2/5 

82543713 
J:0082543713 

20.12.2011 

Heating actuator 6-gang 

Содержание KNX 2136 REG HZ

Страница 1: ...ed from the mains even when the device is switched off These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 1 Connection of electrothermal actuators 2 Programming LED 3 Programming button 4 KNX connection 5 Mains voltage connection 3 Function System information This device is a product of the KNX system and complies with the KNX ...

Страница 2: ... and connected actuators in case of overload the device determines which output is involved and switches it off Non overloaded outputs continue to work which means that the rooms in question are still heated In case of major overloads the actuator initially switches all off the outputs A1 A6 off In the case of more minor overloads the actuators switches output groups A1 A3 and or A4 A6 off The act...

Страница 3: ...t the neutral conductor from the output terminals through to additional devices Do not connect any inductive or capacitive loads o Connect the outputs according to connection diagram figure 2 o Connect the mains voltage figure 2 o Connect bus cable with connecting terminal Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connec...

Страница 4: ... frequency 50 60 Hz Power loss approx 2 W Ambient conditions Ambient temperature 5 45 C Storage transport temperature 25 70 C Heating outputs Contact type Semi conductor Triac ε Switching voltage AC 230 V 240 V Switching current 5 50 mA Switch on current max 1 5 A 2 sec Number of drives per output max 4 Housing Fitting width 72 mm 4 modules Connection of outputs Connection mode Screw terminal Sing...

Страница 5: ... typically lasts 6 20 minutes i After resetting of the overload switch off it is no longer possible for the device to determine which output is overloaded If the cause is not eliminated overload switch off will occur again 5 3 Accessories Connection cover Art No 2050 K 5 4 Warranty We reserve the right to make technical and formal changes to the product in the interest of technical progress We pro...