Fan outputs: When switching off the manual control, the outputs, depending on the 
programming, switch to the active position, e.g. forced position. 
Switching outputs: When the manual operation is switched off, the output relays remain in 
the current position. 

Operating the outputs 

In manual operation the relay outputs can be operated instantly. Depending on programming, 
the switching of an output also influences additional outputs. 
The device is in continuous or short-term manual mode. 

Press 

c

 button briefly, < 1 s, as many times as necessary until the desired output is 

selected. 
The LED of the selected output 

A1...A8

 flashes. 

The LEDs 

ON/

n

 and 

OFF/

o

 indicate the status. 

Operate output with 

ON/

n

 or 

OFF/

o

 button.

Heating/cooling outputs: Open or close valve.
Fan outputs: Set fan level.
Switching outputs: Switch on or switch off. 
The selected output switches on or off.  
The LEDs 

ON/

n

 and 

OFF/

o

 indicate the status. 

Depending on programming and the selected output, several outputs switch 
simultaneously. 

Heating and cooling of a fan-coil output are never switched on simultaneously. 

At least the first fan level is active with the heating or cooling output. 

Short-term manual operation: After running through all of the outputs the device exits 
manual mode after another brief press. 

Switching off all outputs 

The device is in continuous manual mode. 

Press the 

ALL OFF

 button. 

All outputs are shut off. 

Disabling individual outputs 

The device is in continuous manual mode. 

Press 

c

 button briefly as many times as necessary until the desired output is selected. 

The status LED of the selected output 

A1...

 flashes. 

Press 

ON/

n

 and 

OFF/

o

 buttons simultaneously for at least 5 seconds. 

Selected output is disabled. 
The status LED of the selected output 

A1...

  flashes quickly. 

Activate bus mode (see section Deactivating permanent manual control). 

A disabled output can be operated in permanent manual mode. 

If a disabled output is selected in manual control, the LEDs flash twice briefly with a time 
interval. 

Re-enabling outputs 

The device is in continuous manual mode. 

Press 

c

 button briefly as many times as necessary until the desired output is selected. 

The status LED of the selected output 

A1...A8

  flashes twice briefly at time intervals. 

Press 

ON/

n

 and 

OFF/

o

 buttons simultaneously for at least 5 seconds. 

Selected output is enabled. 
LED of the selected output flashes slowly. 

Activate bus mode (see section Deactivating permanent manual control). 

4/11 

82565513 
J:0082565513 

20.12.2011 

Fan coil actuator 2-gang 

Содержание FCA 2 REGHE

Страница 1: ...at supply dangerous voltage to the device or load Danger of electric shock Device is not suitable for disconnection from supply voltage Danger of electric shock on the SELV PELV installation Not suita...

Страница 2: ...and other auxiliary programs are available on our Internet website Intended use Switching of electrical fan coil units Switching of electrical loads AC 230 V e g fans Installation in distribution box...

Страница 3: ...s the actuator returns automatically to bus operation Deactivating temporary manual control The device is in short term manual mode o No button press for 5 seconds or o Press c button briefly as many...

Страница 4: ...i Short term manual operation After running through all of the outputs the device exits manual mode after another brief press Switching off all outputs The device is in continuous manual mode o Press...

Страница 5: ...d value Table 1 Operating modes i Outputs not used for controlling fan levels can be used for simple switching Please see configuration data for the assignment of output terminals o Connect bus cable...

Страница 6: ...oling valve Fan levels 3 Heating cooling valve Fan levels 4 Cooling valve Heating valve Fan levels 5 Cooling valve Heating valve Fan levels Table 2 Output assignment 1 fan coil output Figure 4 Single...

Страница 7: ...Connection example load connection for 2 fan coil outputs Operating mode A1 A5 A2 4 A6 8 1 Heating valve Fan levels 2 Cooling valve Fan levels 3 Heating cooling valve Fan levels Table 3 Output assignm...

Страница 8: ...Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connection area Figure 9 Installing the cover o Route the bus cable towards the...

Страница 9: ...3 W Ambient conditions Ambient temperature 5 45 C Storage transport temperature 25 70 C Outputs Contact type contact potential free NO contact Switching voltage AC 250 V Switching current AC1 10 A Sw...

Страница 10: ...use 2 Manual control via bus disabled Enable manual control Cause 3 No mains voltage Switch on mains voltage Check fuse Output cannot be operated Cause Output is disabled Cancel disabling None of the...

Страница 11: ...5 80 65 51 Telefax 49 0 23 55 80 61 89 kundencenter jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 kundencenter jung de KNX equipment Service Line 49 0 23 55 80...

Отзывы: