Switch-on on brightness
undershoot
On, Off
Basic setting: Off
Allows automatic switch-on
according to the brightness. If
the parameter is On, then the
light controller switches on
automatically when the
brightness setpoint is greatly
undershot. We recommend
only using the parameter in
connection with the parameter
"Switch-off on brightness
overshoot". This parameter is
not yet active, as a light
controller has not yet been
implemented.
Invert switching output
On, Off
Basic setting: Off
Inverts the switching output
from NO contact function
(factory setting) to NC contact
function
Minimum switching repeat
time
100 ms ... 10 sec
Basic setting: 100 ms
Limits the switching speed of
the device by increasing the
value, in order to protect the
load, for example. Only when
the set time has elapsed is
switching possible again. The
last command during the
blocking time is executed after
a delay. The switching repeat
time starts after each
switching operation.
Operating hours
0...65535
Basic setting: Current value
The time is counted during
which the load is physically
switched on (relay contact
closed).
This parameter can be reset to
"0", for example after
exchanging the load.
The Reset button is used to
reset the counter to "0". The
device must be programmed
to apply the change.
Information window
During channel selection in the Information window, the following settings can be made or
values displayed.
Display value
Explanations
Load state
The load can be switched on or off.
Restraint
Display of forced position status.
Switching cycle counter
Display of the switching cycles with the factor
10, e.g. the value 5 x 10 is displayed for 50
switching cycles.
Total operating hours
Display of the operating hours since the start
of operation.
Operating hours
Display of the operating hours since the last
restart in the Settings window.
i
The value can be updated using the arrow next to the display values.
10/11
82581713
J:0082581713
11.03.2014
eNet
Radio switch actuator for rail mounting, 1-channel