6
Commissioning
Setting date, time and other parameters
When the year is flashing on the display, you must set or confirm the data listed in
the table.
–
Briefly press the – or + button to change values or toggle between YES / No.
–
A long press of the – or + button accelerates value changes.
–
Press the
Ƨ
button to go back in the menu.
–
Press the
ƨ
button to apply the setting and call the next value. After editing
the last parameter, all values will be saved and automatic mode will be in-
voked.
Parameters
Display icon
Setting option/
Default setting
Year
ƛƜ
2019 or later
Month
ƛƜ
01 ... 12
Day
ƛƜ
01 ... 31
Hour
ƛƜ
00 ... 12 ... 23
Minute
ƛƜ
00 ... 59
Automatic summer time
changeover
ƛƜ Ơ
YES / No
Controller output
1)
ƛƜ Ƽ
YES / No
Valve adaptation
2)
ƛƜ Ƹ
NO / NC
Optimised heating up
Ʋ ƹ
YES / No
Temperature drop detection
Ʋ Ʒ
YES / No
Temp. unit
Ʋ
°C / °F
Comfort temp.
Ʋ
Ƶ
5 ... 21.0 ... 30 °C
ECO temp.
Ʋ ƶ
5 ... 18.0 ... 30 °C
Frost protection
Ʋ ƽ
5 ... 7.0 ... 30 °C
Heating / cooling
Ʋ ƾ
YES / No
Cooling temp.
3)
Ʋ
ƾ
5 ... 24.0 ... 30 °C
Temperature sensor
Ʋ ƻ
ƻ
,
ƺ
or both
Max. floor temp.
4)
Ʋ
MAX
10 ... 35.0 ... 45 °C
Offset
Ʋ Ƴ
-5 ... 0.0 ... +5 °C
1)
Pulse width modulation (PWM) = YES, two-point control = No
2)
NC: Valve is closed when deenergised.
NO: Valve is open when deenergised.
3)
This parameter only appears if the device is set to "Heating and cooling".
4)
This parameter only appears if
ƻ
and
ƺ
have been set for the temperature
sensor.
LB Management room thermostat display
7 / 14
32401513
17.08.2022
J0082401513