Image 4: Assignment of LED colour for the operating mode

Keep pressing button Test (1) for less than 1 second, until the necessary oper-
ating mode is selected.

The LED (2) lights up in the colour of the selected operating mode
(see figure 4).

Save the settings: Press the button Test (1) for more than 1 second or do not
press for 30 seconds.

LED (2) goes out and the light is switched on: The operating mode is saved.

6

Technical data

Rated voltage

AC 230 V ~

Mains frequency

50 / 60 Hz

Standby load depending on the cover

approx. 0.1 ... 0.5 W

Power loss

approx. 4 W

Ambient temperature

-5 ... +45 °C

Light loads

Connected load at 25 °C (see figure 5)

Image 5: Connected load

When operating with neutral conductor or without neutral conductor in operat-
ing mode 

{

 : Connected load for HV-LED lamps typ. 3...200 W, elec-

tronic transformers with NV-LED typ. 20...200 W.

Mixed load

ohmic-capacitive

20 ... 400 W

capacitive-inductive

not permitted

ohmic-inductive

20 ... 400 VA

ohmic and HV LED

typ. 3 ... 100 W

Electronic switch insert 1-channel

8 / 11

82400533

25.08.2022

J0082400533

Содержание 1704ESE

Страница 1: ...ectronic switch insert 1 channel Art no 1704ESE 25 08 2022 82400533 J0082400533 ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm hle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundence...

Страница 2: ...eristics 3 4 Operation 4 5 Information for electrically skilled persons 4 5 1 Mounting and electrical connection 4 5 2 Commissioning 7 6 Technical data 8 7 Troubleshooting 9 8 Accessories 10 9 Warrant...

Страница 3: ...mode and load type do not match Set correct operating mode when connecting or exchanging the load This manual is an integral part of the product and must remain with the end cus tomer 2 Intended use O...

Страница 4: ...ontrol principle Automatic or manual setting of the suitable operating mode for the load Indication of the set operating mode by means of LED Brief flickering upon load detection possible No operation...

Страница 5: ...connected load on LED lamps is dependent on the type of lamp and in stallation conditions The connected load of the specified values could vary We cannot assume any guarantee for proper function Opera...

Страница 6: ...stallation height 1 50 m Image 3 Connection diagram in combination with a room thermostat cover and KNX RF push button 6 Switching contact for switching to cooling mode 7 Electrothermal valve drive If...

Страница 7: ...nt lamps HV halogen lamps dimmable HV LED or compact fluor escent lamps dimmable electronic or inductive transformers for halogen or LED lamps LED trailing edge phase control The connection of inducti...

Страница 8: ...cal data Rated voltage AC 230 V Mains frequency 50 60 Hz Standby load depending on the cover approx 0 1 0 5 W Power loss approx 4 W Ambient temperature 5 45 C Light loads Connected load at 25 C see fi...

Страница 9: ...on unlimited 3 wire rotary extension 10 Total line length Extension max 100 m Power cable max 100 m Loads for room temperature control Thermal valve drive NC order no TSA230NCWW Number 1 10 7 Troubles...

Страница 10: ...D leading edge phase control setting reduce connected load as well if necessary Exchange lamps for another type Cause 3 Short circuit protection has tripped Disconnect device from mains by switching o...

Страница 11: ...JUNG GMBH CO KG Volmestra e 1 58579 Schalksm hle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de Electronic switch insert 1 channel 11 11 82400533 25 08 2022 J00...

Отзывы: