Light Management

 

Pushbutton control unit 
Ref.-no.: 1240 STE  
R3 

 
3. Fitting instructions 

Install the pushbutton control unit (1) in a flush-mounting box in acc. with 
DIN 49073 (fig A). The connecting terminals of the insert must be at the 
bottom (wall mounting). Use the pushbutton control unit only in 
combination with an attachment. Plug the attachment (2) together with 
frame (3) into the insert. The electrical contact is ensured by connector 
(4). The overall power consumption of the lamps connected must not 
exceed 700 W. 
 

 

 
Depending on the type of installation, the max. load connected must be 
reduced: 
- 10 % for every 5 °C above the ambient temperature of 25 °C 
- 15 % for installations in wooden, gypsum plasterboard or hollow walls, 
- 20 % for installations in multi-device combinations. 

Observe the technical connection requirements of the power supply 
companies. 

 

4. Short-circuit protection 

The load output has no internal protection. For protection install a circuit-
breaker of 10 A ahead of the device. The 1-10 V control output is 
protected against shortcircuiting of the control current. 
 

Do not connect the control output to 230 V ~. The pushbutton 
control unit will be irreparably damaged. 

 

Connection without extension units 

The insert is connected as shown in fig B. The extension unit input „1“ 
remains open. 
 
 
 
 
 
 

 

Содержание 1240 STE

Страница 1: ...ic ballasts or TRONIC transformers with 1 10V interface Switching and dimming commands are given by actuating the attachments for the pushbutton control units extension units or radio control transmit...

Страница 2: ...itself For storing press the center of the button not multifunction pushbutton with radio control receiver and multifunction pushbutton Universal for at least 20 seconds when off The lights are at fi...

Страница 3: ...ation the max load connected must be reduced 10 for every 5 C above the ambient temperature of 25 C 15 for installations in wooden gypsum plasterboard or hollow walls 20 for installations in multi dev...

Страница 4: ...1240 STE R3 1 pushbutton control unit 5 load 6 switched phase to other loads 7 1 10 V control lines to other loads 8 2 wire extension unit art no 1220 NE 9 3 wire extension insert art no 1223 NE 10 m...

Страница 5: ...Functions available only if an automatic switch or a presence detector attachment is used also on the main unit Extension unit 2 wire with short stroke key Same functions as with the pushbutton contr...

Страница 6: ...rt is connected as shown in fig C The number of electronic ballasts or TRONIC transformers that can be dimmed with a single pushbutton control unit depends on the control current of the individual ele...

Страница 7: ...ns potential Total length of cable to extension units max 100 m 7 Guarantee Our products are under guarantee within the scope of the statutory provisions Please return the unit postage paid to our cen...

Отзывы: