6  Special device functions

6.1 Detection of load faults

Load monitoring detects the percentage change in resistance of the load. It
can detect and signal a load failure, partial load failure, or a partial load short
circuit.

Undercurrent

This function is used for one or more heating elements connected in parallel
that are to be monitored for failure.

Overcurrent

This function is used for several heating elements connected in series that are
to be monitored for short circuits.

Function

This function not only takes the decreasing or increasing load current into con-
sideration but also includes the load voltage in the monitoring process.

The plant's correct load ratios are saved during Teach-In.
Based on this state, the load changes are continuously monitored irrespective
of the required output level. In the event of a failure or short circuit of a heating
element, the load current increases or decreases. This is detected by the load
monitoring and a load fault is signaled.

Limit value

A limit value must be entered as a % in the configuration or operating level for
load monitoring. This limit value depends upon the number of heating ele-
ments connected in parallel or in series.

For heating elements with a high positive or negative temperature coefficient,
a suitable limit value must be determined independently. The % value shown
below (see arrow) can be used as an aid for this. 
This value represents the current deviation from the teach-in value. If the value
is > 0 %, the load has become more high-resistance; if the value is < 0 %, it
has become more low-resistance. This window can be accessed via Operator
level

r

Monitoring 

r

Limit value load monit.

For heating elements with a temperature coefficient TC 

 1, the limit value can

be taken directly from the following tables:

Undercurrent 

Number of 
heating ele-
ments

Single-phase 
operation

Star connection 
with separate star 
points without neu-
tral conductor

Star connection with 
common star points 
without neutral con-
ductor

Delta connection

5

10 %

-

-

4

13 %

10 %

-

3

17 %

13 %

10 %

Содержание TYA S201

Страница 1: ...201 Single Phase Thyristor Power Controller Operating Manual 70906500T90Z001K000 V1 00 EN 00709718 709065 8 01 020 709065 8 01 050 709065 8 01 150 709065 8 01 200 709065 8 01 250 709065 8 01 100 70906...

Страница 2: ...QPJOU JOQVU B JOQVU B WBMVF JOQVU JO UIF FWFOU PG BO FSSPS WBMVF JO UIF FWFOU PG BO FSSPS BYJNVN PVUQVU WBMVF BTJD MPBE JNJU WBMVF NPOJUPSJOH JNJU WBMVF JO BMBSN JNJU WBMVF BY BMBSN JNJU WBMVF ZTUFSFT...

Страница 3: ...ironmental influences 16 2 1 2 Filtering and interference suppression 17 2 1 3 Admissible load current depending on the ambient temperature and the site altitude 17 2 1 4 Wall mounting with screws per...

Страница 4: ...ion phase phase 38 3 4 3 Star connection with accessible star point N 39 3 4 4 Open delta connection six wire connection 40 4 Operation 41 4 1 Display after switching on the device 41 4 1 1 Display an...

Страница 5: ...e for Teach In in manual mode 64 6 2 3 Performing Teach In in manual mode 65 6 3 Setpoint specification via potentiometer 66 6 4 Dual energy management 66 6 5 start 68 6 6 Monitoring of the mains volt...

Страница 6: ...8 2 3 Semiconductor fuses type 709065 X 0X 32 0X XXX XX 82 9 What to do if 85 10 Technical data 87 10 1 Voltage supply fan specifications for 250A load current 87 10 2 Galvanic isolation 87 10 3 Anal...

Страница 7: ...6106140 Email info jumo at Switzerland Phone 41 1 928 24 44 Fax 41 1 928 24 48 Email info jumo ch A The power controller produces the power that is needed at the analog input or in manual mode Safety...

Страница 8: ...cept any liability for damage caused by ESD ESD Electrostatic Discharge V This symbol is used when personal injury may occur if the instruc tions are disregarded or not followed correctly A This symbo...

Страница 9: ...itself The identification marking in the text is arranged as continuous su perscript numbers h Plug in the connector This symbol marks the description of a required action The individual steps are mar...

Страница 10: ...00 A 250 AC 250 A 5 Partial load failure monitoring 00 None 01 Partial load failure monitoring 6 Mains voltage a 230 AC 230 V 20 to 15 48 to 63 Hz 400 AC 400 V 20 to 15 48 to 63 Hz 460 AC 460 V 20 to...

Страница 11: ...rung austauschen Installation kit for DIN rail 50 A TYA S201 00600095 Item Part no Item Load current Inom IN Part no Super fast semiconductor fuse 40 A IN 20 A 00513108 Super fast semiconductor fuse 8...

Страница 12: ...the wall Operating modes The power controller works in burst firing operation Here the phase angle of the first half wave can be cut so that transformer loads can also be operated During a soft start...

Страница 13: ...ions only Industrial requirements Mechanical tests Vibration test 3M2 Toppling test class 2M1 DIN EN 60068 2 6 DIN EN 60721 3 3 DIN EN 60068 2 31 DIN EN 60721 3 2 Labels identification marking DIN EN...

Страница 14: ...1 Introduction 14 V1 00 EN 00709718 Thyristor power switch TYA S201...

Страница 15: ...the terminals U1 U2 N L2 V and L1 must have an electric strength of AC 500 V k For UL applications the fuse for the supply protection of the control elec tronics must be between 2 A and a maximum of...

Страница 16: ...nnected electrical circuits are also safely isolated The required auxiliary voltages must be SELV voltages 2 1 1 Environmental influences Incorrect use The device is not suitable for installation in p...

Страница 17: ...by themselves They only serve as a component function within a plant Where applicable the power controller s entire load circuit must also have suitable interference suppression filters fitted by the...

Страница 18: ...this reason at ambient temperatures above 45 C the maximum load cur rent must be reduced as shown in the image as the thyristor module would otherwise be destroyed The device temperature shown on the...

Страница 19: ...wer controllers with a load current between 20 and 50 A are affixed to a fire proof control cabinet wall with 2 screws The left hand hole is more easily ac cessible in the upper section Power controll...

Страница 20: ...2 Mounting 20 V1 00 EN 00709718 Thyristor power switch TYA S201 TYA S201 100A TYA S201 150 200A...

Страница 21: ...V1 00 EN 00709718 Thyristor power switch TYA S201 21 2 Mounting TYA S201 250A...

Страница 22: ...e click During operation the power controller heats up to a maximum of 110 C depending on the load Ensure that the lamellae of the heat sink are vertically aligned to allow the heat to be dissipated t...

Страница 23: ...V1 00 EN 00709718 Thyristor power switch TYA S201 23 2 Mounting 2 2 Dimensions 2 2 1 Type 709065 X 0X 020 0X XXX XX 2 2 2 Type 709065 X 0X 032 0X XXX XX...

Страница 24: ...2 Mounting 24 V1 00 EN 00709718 Thyristor power switch TYA S201 2 2 3 Type 709065 X 0X 050 0X XXX XX 2 2 4 Type 709065 X 0X 100 0X XXX XX...

Страница 25: ...V1 00 EN 00709718 Thyristor power switch TYA S201 25 2 Mounting 2 2 5 Type 709065 X 0X 150 0X XXX XX Type 709065 X 0X 200 0X XXX XX...

Страница 26: ...switch TYA S201 2 2 6 Type 709065 X 0X 250 0X XXX XX 2 2 7 Clearances all types h Allow a clearance of 10 cm from the floor h Allow a clearance of 15 cm from the ceiling h When fitted next to each ot...

Страница 27: ...0 A is connected via pluggable screw termi nals The electrical connection must only be carried out by qualified per sonnel Dangerous voltages will cause an electric shock in the event of contact with...

Страница 28: ...Terminal Version Conductor cross section Maximum tightening torque X2_1 and X2_2 Slotted screws blade width 2 mm 0 2 1 5 mm2 0 25 Nm X3 Slotted screws blade width 3 mm 0 2 2 5 mm2 0 5 Nm U2 N L2 V L1...

Страница 29: ...c tion Maximum tightening torque X2_1 and X2_2 Slotted screws blade width 2 mm 0 2 to 1 5 mm2 0 25 Nm X3 Slotted screws blade width 3 mm 0 2 to 2 5 mm2 0 5 Nm U2 U1 M6 recessed head screws 6 to 25 mm2...

Страница 30: ...3 Electrical connection 30 V1 00 EN 00709718 Thyristor power switch TYA S201 2 X2_ X2_1 X8 X3 U1 U2 N L2 V L1 PE...

Страница 31: ...ghtening torque X2_1 and X2_2 Slotted screws blade width 2 mm 0 2 to 1 5 mm2 0 25 Nm X3 Slotted screws blade width 3 mm 0 2 to 2 5 mm2 0 5 Nm U2 U1 M6 hex headed screws wrench size 10 mm 16 to 50 mm2...

Страница 32: ...rminal Version Conductor cross section Maximum tightening torque X2_1 and X2_2 Slotted screws blade width 2 mm 0 2 to 1 5 mm2 0 25 Nm X3 Slotted screws blade width 3 mm 0 2 to 2 5 mm2 0 5 Nm U2 U1 M8...

Страница 33: ...um tightening torque X2_1 and X2_2 Slotted screws blade width 2 mm 0 2 to 1 5 mm2 0 25 Nm X3 Slotted screws blade width 3 mm 0 2 to 2 5 mm2 0 5 Nm U2 U1 M8 hex headed screws wrench size 13 mm 95 to 15...

Страница 34: ...ction Voltage supply for control electronics corresponds to the mains voltage of the ordered device type L1 N L2 V Load connection in the power section and protective conductor connection U1 U2 PE Fan...

Страница 35: ...potential EIN AUS 11 10 3 3V 10kW TYA 8 7 U 8 8 7 7 Connection for Screw terminal X3 Connection Relay 13 N O contact 14 N C contact 15 Pole S P 13 14 15 RelaY OUTPUT Modbus connection RS422 RS485 PRO...

Страница 36: ...lways remain connected to the mains volt age e g S1 always closed in order to maintain the fieldbus communication S2 is used to activate the load In the event of transformer loads or loads with a larg...

Страница 37: ...FE QPXFS UPU DVSSFOU JO QIBTF DPOEVDUPS DVSSFOU JO UIZSJTUPS QPXFS VOJU 5IZ VTJOH UP QSPUFDU UIF QPXFS TFDUJPO DBCMJOH 4FUQPJOU JOQVU VTF GPS DPOUSPM FMFDUSPOJDT VQ UP B NBYJNVN PG TFF TXJUDI PO TFRVF...

Страница 38: ...MUBHF PO UIZSJTUPS QPXFS VOJU 5IZ 1 UPUBM DPOUSPMMFE QPXFS UPU DVSSFOU JO QIBTF DPOEVDUPS DVSSFOU JO UIZSJTUPS QPXFS VOJU 5IZ 7 5IZ 7 7 N 1 6 6 6 6 BMCMFJUFS TJDIFSVOH 4 3FMBJT 1 4 4 TFF TXJUDI PO TFR...

Страница 39: ...O UIZSJTUPS QPXFS VOJU 5IZ 6 6 5IZ 5IZ 1UPU r 6 1UPU r 6 5IZ PBE VTJOH UP QSPUFDU UIF QPXFS TFDUJPO DBCMJOH 4FUQPJOU JOQVU VTF GPS DPOUSPM FMFDUSPOJDT VQ UP B NBYJNVN PG 5 3 5 3 5 3 7 7 7 5IZ N 1 6 6...

Страница 40: ...QPXFS UPU DVSSFOU JO QIBTF DPOEVDUPS DVSSFOU JO UIZSJTUPS QPXFS VOJU 5IZ 6 6 5IZ 5IZ 1UPU r 6 1UPU r 6 r 5IZ 1 5 3 5 3 5 3 7 7 7 N 6 6 5IZ 6 6 BMCMFJUFS TJDIFSVOH 4 3FMBJT 1 6 6 BMCMFJUFS TJDIFSVOH 4...

Страница 41: ...hows a range of language options on the display Select the national language and confirm your selection with Language wiz ard This option enables you to select whether the language wizard should be re...

Страница 42: ...e It is also used to display temporary states e g error messages v Chapter 8 Fehlermeldungen und Alarme Legend Comment Diagram 1 The Power LED green lights up permanently when the voltage supply is co...

Страница 43: ...ignal Subordinate control loop Operating mode load output Voltage None Burst firing operation Current Logic switch Soft start with phase angle control Interface Invalid con trol config ured Burst firi...

Страница 44: ...sured load voltage Measured between the V and U2 terminals V Load current1 Effective value of the measured load current A Power1 Measured effective power W or kW Load resistance 1 Measured effective r...

Страница 45: ...or selection Once you have reached the required parameter the or key can be used to enter a numerical value or to select a parameter h Save the setting using If you do not wish to apply the value the...

Страница 46: ...for display contrast has been found the param eter can be stored by pressing If you do not wish to apply the value the entry can be canceled by pressing 4 2 1 Device data H All parameters for the maxi...

Страница 47: ...k bold default setting Value range Description Current load voltage 0 to 100 of the output level Note This setting is only available if Power controller rThyristor control rContinuous power controller...

Страница 48: ...nt or overcurrent v Chapter 5 1 5 berwachungen By displaying the current deviation from the teach in value it is possi ble to check whether for example an output level dependent resis tance modificati...

Страница 49: ...r no password is set per default The configuration level can be accessed from the overview of measured val ues by pressing the following keys h In the measured value overview press the key h Select th...

Страница 50: ...ure unit C Defines the unit for the displayed temperatures such as the device temperature F Display contrast 0 to 50 to 100 Bright dark contrast setting Switch off Display lighting 0000 to 1440 min Th...

Страница 51: ...e waves Dependent on the cycle time setting At least three full sine waves are always let through At an output level of 50 and with the fastest possible cycle time 3 sine waves are switched on and 3 s...

Страница 52: ...roups This setting is available in burst firing operation mode with a fixed cycle time and with the fastest possible cycle time During the soft start time the ON OFF ratio is increased from 0 to a max...

Страница 53: ...pecifies which current standard signal is con nected v Chapter 3 3 Anschlussplan 4 to 20 mA Customer specific1 Current measuring range start 0 to 20 mA Note This parameter only appears if Customer spe...

Страница 54: ...rent voltage and interface input are monitored for errors wire breaks or bus errors This setting specifies which re placement value the power controller should use if the set point specification is in...

Страница 55: ...temperature Min limit value alarm 0 to 9999 9 The absolute minimum limit values for load voltage load cur rent power resistance mains voltage or device temperature can be monitored If the measurand f...

Страница 56: ...rt wave infrared radiators Teach In type load monitoring Automatic once The Teach In value is automatically determined once after each power ON v Chapter 6 1 1 Teach In Manual Teach in can be performe...

Страница 57: ...connected Value settings Description Inhibit input control direction The firing pulse inhibit can be triggered when the switching contact is closed or open v Chapter 3 3 Anschlussplan Open load ON Per...

Страница 58: ...ured as an N C contact or as an N O contact see below The K1 LEDs also light up in the event of a fault Interf signal The digital output is controlled via an interface Control direction digital output...

Страница 59: ...hem from unau thorized access Value settings Description Baud rate 9600 19200 38400 Data format 8 1 none Data bits stop bits parity check 8 1 odd 8 1 even 8 2 none Device address 1 to 255 Min response...

Страница 60: ...Mains voltage 400 V 3 heating elements each with 1 kW connected in parallel Load current 3000 W 400 V 7 5 A Temperature coefficient TC 1 Base load 0 Setpoint specification via standard signal of 0 to...

Страница 61: ...current increases or decreases This is detected by the load monitoring and a load fault is signaled Limit value A limit value must be entered as a in the configuration or operating level for load mon...

Страница 62: ...conductor Star connection with common star points without neutral con ductor Delta connection N L1 L3 L2 L1 L3 L2 L1 L3 L2 L1 Number of heating ele ments Single phase op eration Star connec tion with...

Страница 63: ...Manual Teach In has been configured but no Teach In has been conduct ed the message Teach In load monitoring appears on the display as a re minder Manual Teach In can only be performed on the device...

Страница 64: ...2 Configuring Teach In prerequisite for Teach In in manual mode The Teach In function records the current voltage ratio of a load in the OK state This function is not configured per default v Configur...

Страница 65: ...essage Teach In load monitoring now appears in the bottom line of the display h Press the key and the following message will appear h Press the key to apply the current load state as the OK state A ch...

Страница 66: ...ers without causing current peaks in the network when they are switched on simultaneously No current peaks are caused in the network even if the setpoint values are asymmetrically distributed e g 30 a...

Страница 67: ...ight see arrows For as long as the total output level of the two devices is below 100 two device currents in a single phase are prevented from overlapping The next power level in the network is not st...

Страница 68: ...ing pulse inhibit prevents the connected transformer loads from destroying the semiconductor fuse due to a DC component If there are no further mains voltage drops the firing pulse inhibit is removed...

Страница 69: ...the thyristors are fired in zero crossing of the mains voltage and are only locked again when the ana log input is deactivated Transformer loads In the case of transformer loads the first mains volta...

Страница 70: ...6 Special device functions 70 V1 00 EN 00709718 Thyristor power switch TYA S201...

Страница 71: ...lete installa tion cannot be guaranteed Software versions The software versions for the device and the setup program must be compati ble An error message will appear if this is not the case h After sw...

Страница 72: ...7 Setup program 72 V1 00 EN 00709718 Thyristor power switch TYA S201 7 3 Installation h Installing the setup program Installation steps Appearance on the PC screen 1 2 Enter license number 3 4 5 6...

Страница 73: ...V1 00 EN 00709718 Thyristor power switch TYA S201 73 7 Setup program Installation complete 7 8 Run setup program 9 Installation steps Appearance on the PC screen...

Страница 74: ...to a USB socket on the PC us ing the supplied USB cable h Click Connect in the menu bar Diagnostics The diagnosis window appears at the bottom of the screen and shows the de vice info and the current...

Страница 75: ...he device data or enter a new code word via the setup program Extracting set up data h Perform a Data transfer rFrom the device The extracted codes are visible in the Device data menu Entering new cod...

Страница 76: ...he device h Edit rExecute hardware and the hardware wizard will start h Click Automatic detection and the dialog for the device language will ap pear h Select the desired national language h Continue...

Страница 77: ...Besondere Ger tefunk tionen Replace defective heating ele ments Malfunction Blown fuse red LED fuse is lit 1 Semiconductor fuse defective v Chapter 8 2 Replacing a defec tive semiconductor fuse 2 No...

Страница 78: ...5 berwachungen Ensure stable mains supply Teach In load monitoring Reminder that manual Teach In has been configured but not yet executed Perform Teach In v Chapter 6 1 Erkennung von Lastfehlern Inhib...

Страница 79: ...error messages are to be grouped together as a binary signal for a collective fault TYA 200 Series This selection contains all of the events that are used in the TYA 200 Series Some events such as Sla...

Страница 80: ...olated green Power LED must not be lit h Press spring clip A to the right and lever up the plastic housing at the point marked with an arrow using a screwdriver B A plug connection separates the displ...

Страница 81: ...ype Tripping current Screws Tighten ing torque Part no 20 A Tripping current 40 A Recessed head 3 Nm 00513108 32 A Tripping current 80 A Recessed head 5 Nm 00068011 50 A Tripping current 80 A Recessed...

Страница 82: ...00709718 Thyristor power switch TYA S201 h Replace the defective semiconductor fuse with a new one h Tighten the screws with the specified tightening torque 8 2 3 Semiconductor fuses type 709065 X 0X...

Страница 83: ...8 Error messages and alarms h Replace the defective semiconductor fuse with a new one h Tighten the screws with the specified tightening torque Reassembling the housing h Push the plastic housing back...

Страница 84: ...8 Error messages and alarms 84 V1 00 EN 00709718 Thyristor power switch TYA S201...

Страница 85: ...8 at terminal X2_2 v Chapter 4 1 2 Darstellung von Messwerten Load break h Check load and load connections v Chapter 8 Fehler meldungen und Alarme Fuse LED is lit Semiconductor fuse defective due to s...

Страница 86: ...86 V1 00 EN 00709718 Thyristor power switch TYA S201 9 What to do if...

Страница 87: ...V 30 VA Load current IL rms AC 20 32 50 100 150 200 250 A Load type Resistive and resistive inductive loads Control section power consumption Max 20 VA Admissible load current depending on the ambien...

Страница 88: ...ntroller nominal data 10 4 Digital output fault signal output Current 0 4 to 20 mA Ri 50 Voltage 0 2 to 10 V Ri 25 k 0 1 to 5 V Ri 25 k Mains voltage 2 5 Load current 1 Load voltage 1 Analog input Vol...

Страница 89: ...erating conditions The power controller is designed as a built in device according to EN 50178 pollution degree 2 overvoltage category III Electromagnetic compatibility According to DIN 61326 1 Interf...

Страница 90: ...pply current circuit and SELV circuits for type 709065 X 0X 020 12 7 mm between supply current circuit and SELV circuits from type 709065 X 0X 032 SELV Separate Extra Low Voltage safe low voltage Hous...

Страница 91: ...508 Category NRNT pollution degree 2 C22 2 NO 14 10 Industrial Control Equipment Category NRNT7 709065 X XX 020 Load current 20 A UL 508 Category NRNT C22 2 NO 14 10 Industrial Control Equipment Categ...

Страница 92: ...Q HOLYHU DGGUHVV 0DFNHQURGWVWUD H XOGD HUPDQ 3RVWDO DGGUHVV XOGD HUPDQ 3KRQH D PDLO PDLO MXPR QHW QWHUQHW ZZZ MXPR QHW 802 RXVH 7HPSOH DQN 5LYHUZD DUORZ VVH 0 8 3KRQH D PDLO VDOHV MXPR FR XN QWHUQHW Z...

Отзывы: