3 Operation - Configuration - Parameterization

14

3.1.4

Level concept

The parameters for device setting are organized at different 

levels

.

The various levels are also accessible in manual mode.

Level inhibit

 (factory-setting: all levels are free):

3.1.5

Operator level (OPr)

Depending on the configuration, the following parameters are available:

(1) Changeover from 

normal display

 to the levels

(2) Changeover between levels

(3) Changeover to the 

operator level

 (setpoints, 

process values, timer value and time)

(4) Changeover to the 

parameter level

 (controller 

parameters)

(5) Changeover to 

configuration level

 (analog input, 

controller, ramp function, limit value monitoring, 
timer, outputs, binary functions, display and 
operation, interface)

(6) Return to the normal display 

(10)

Navigation principle

:

If no key is pressed for 180 s (factory-
setting), the device will return to its 
normal display. This time period can 
be configured.

(11) - one level deeper

(12) - next parameter / increase value

(13) - previous parameter / reduce value

(14) - one level back

Code

Operator 
level

Parameter 
level

Configura-
tion level

1. Simultaneously press (A) and (B) (> 5 s)

2. Press (A) (display flashes)

3. Enter code using (B) or (C)

4. Use (D) to return to the normal display

(or automatically after 180 s)

(key designation in brackets; 

see chapter 3.1.1)

0

free

free

free

1

free

free

inhibited

2

free

inhibited

inhibited

3

inhibited

inhibited

inhibited

Symbol Description

Symbol Description

SP1

Setpoint 1 (can be edited)

rASL

Ramp rate (for firing curve; can be 
edited)

SP2

Setpoint 2 (can be edited)

SPr

Current ramp setpoint (for ramp 
function or firing curve)

t1

Timer value (if timer or firing curve 
are inactive; can be edited)

InP1

Measured value at analog input

tL

Timer run time (if timer or firing 
curve are active)

y

Output level

tr

Residual timer run time (if timer or 
firing curve are active)

ConF

> 2s

PArA

(11)

OPr

(1)

(3)

(4)

(2)

(5)

(6)

(14)

(12)

(10)

(13)

Содержание Quantrol LC100

Страница 1: ...JUMO Quantrol LC100 LC200 LC300 Universal PID Controller Series B 702030 0 Operating Manual 2013 06 24 00600571 ...

Страница 2: ......

Страница 3: ... 1 5 Operator level OPr 14 3 2 Configuration ConF 15 3 2 1 Analog input InP 15 3 2 2 Controller Cntr 16 3 2 3 Ramp function firing curve rAFC 17 3 2 4 Limit value monitoring Li1 Li2 17 3 2 5 Timer tFCt 18 3 2 6 Outputs OutL OutA 19 3 2 7 Binary functions binF 20 3 2 8 Display and operation diSP 20 3 2 9 Interface IntF 21 3 3 Parameterization PArA 22 4 Supplement 23 4 1 Additional information about...

Страница 4: ...Content 4 4 2 7 Self optimization TUNE 30 4 3 Error messages 33 4 4 Technical Data 34 ...

Страница 5: ...ommunication with other devices All PDF documents can be downloaded under www jumo net 1 2 Safety information This manual contains information that must be observed in the interest of your own safety and to avoid damage to assets This information is supported by symbols which are used in this manual as follows Please read this manual before starting up the device Keep the manual in a place accessi...

Страница 6: ...ing seal and fastening elements Brief instructions B 702030 7 in DIN A6 format TIP This symbol refers to Important information about the product or its handling or additional use REFERENCE This symbol refers to Further information in other sections chapters or manuals ...

Страница 7: ...0 0 0 0 1 1 1 1 1 relay output N O 2 2 2 2 1 logic output 3 1 analog output configurable 4 1 RS485 interface Voltage supply 23 AC 110 to 240 V 10 15 48 to 63 Hz 25 AC DC 20 to 30 V 48 to 63 Hz Order code 702034 8 3 4 1 2 23 Example Case type Plastic case for panel mounting as per IEC 61554 indoor use Dimensions front LC100 48 mm x 48 mm LC200 48 mm x 96 mm portrait format LC300 96 mm x 96 mm Panel...

Страница 8: ... DC 20 to 30V 48 to 63Hz Electrical safety as per DIN EN 61010 part 1 overvoltage category III pollution degree 2 Power consumption max 14 VA Electrical connection on the rear via screw terminals with core end ferrule of a pipe shape open cable lug or pin cable lug Conductor cross section fine strand 0 25 to 1 5 mm2 Tightening torque 0 5 Nm Electromagnetic compatibility as per DIN EN 61326 1 Inter...

Страница 9: ...ront into the panel cut out and ensure that the seal is correctly positioned 2 Push the fastening frame from the panel rear onto the device and press the springs against the panel rear until the lugs engage in their slots and it is sufficiently fastened 2 Slide the mounting brackets from the panel rear into the lateral openings and push to the rear against the stop 3 Place the mounting brackets ag...

Страница 10: ...ervicing repairing a Disconnecting Device shall be provided to disconnect all conduc tors The load circuit must be fused for the maximum relay current in order to prevent the output relay contacts from becoming welded in the event of a short circuit occurring at that point The electromagnetic compatibility EMC meets the standards and regulations cited in the technical data Run input output and sup...

Страница 11: ...r cross section LC100 LC200 LC300 TIP The USB interface socket Mini B 5 pole is labeled on the device with SETUP and is located on the case top of the LC100 and on the case bottom of the LC200 and LC300 It is used for connection to a PC that is running the setup program 13 14 7 6 12 11 10 9 8 N L 5 L1 L 4 USB N L L1 L 14 15 16 17 18 19 5 11 10 13 12 4 7 8 9 USB N L L1 L 5 11 10 4 7 8 9 14 15 16 17...

Страница 12: ...e 10 9 8 11 RTD temperature probe 3 wire 10 9 9 10 8 11 Voltage DC 0 to 10 V 12 7 11 8 Current DC 0 4 to 20 mA 9 10 8 11 Binary input for potential free contact 11 7 12 8 Output 1 2 3 1 2 3 4 5 Analog output DC 0 to 10 V DC 0 4 to 20 mA 13 12 14 13 Relay output N O max 3 A at AC 230 V resistive load 4 13 6 4 12 14 16 18 5 14 7 5 13 15 17 19 Logic output DC 0 14 V 13 7 12 14 16 18 14 6 13 15 17 19 ...

Страница 13: ...on Simultane ously press keys B and C 2 s tUnE flashes in the lower display Abort of self optimization Simulta neously press keys B and C No parameters are changed by the abort Change setpoint using keys B and C The longer the key is kept pressed the faster the set point value changes The value will be automatically applied Function key D 2 s is used to Change over to manual mode and to exit the m...

Страница 14: ...vice will return to its normal display This time period can be configured 11 one level deeper 12 next parameter increase value 13 previous parameter reduce value 14 one level back Code Operator level Parameter level Configura tion level 1 Simultaneously press A and B 5 s 2 Press A display flashes 3 Enter code using B or C 4 Use D to return to the normal display or automatically after 180 s key des...

Страница 15: ...evel display 100 to 100 2 Actual value 9 Controller output 1 e g heating output level 0 to 100 3 Current setpoint 10 Controller output 2 e g cooling output level 0 to 100 4 Ramp end value 11 Timer run time time unit of the timer 5 reserved 12 Timer residual time time unit of the timer 6 Setpoint 1 Parameters Value Description Value Description Probe type SEnS RTD temperature probe Thermocouples 0 ...

Страница 16: ... at 25 C Parameters Value Description Controller type CtyP 1 2 state controller 2 3 state controller 3 Continuous controller Action CACt 0 Direct The output level of the controller is 0 when the actual value exceeds the setpoint e g cooling 1 Inverse The output level of the controller is 0 when the actual value is smaller than the setpoint e g heating Output value manual mode HAnd 100 0 101 Output...

Страница 17: ...ring curve Kelvin Day Ramp rate rASL 0 999 Value of the ramp rate only for function 1 to 6 Setup program For the firing curve timer value time unit and setpoint can also be set here Parameters Value Description Alarm function FnCt 0 Limit value monitoring switched off 1 AF1 Limit value above and below the setpoint monitoring range symmetric or asymmetric 2 AF2 As AF1 output signal inverted 3 AF3 L...

Страница 18: ...elay of the output signal in seconds Actual value AFPr 2 Signal to be monitored 2 actual value Ö Ö Analog selector page 15 Setpoint value AFSP 3 Setpoint for limit value monitoring reference signal for AF1 to AF6 3 current setpoint Ö Analog selector page 15 Parameters Value Description Function FnCt 0 Timer switched off 1 Timer signal is high while the timer is running 2 Timer signal is low while ...

Страница 19: ...ut output 2 ConF OutA Parameters Value Description Output 1 5 Out1 Out2 Out3 Out4 Out5 0 Output not active factory setting for Out2 Out5 1 Controller output 1 factory setting for Out1 2 Controller output 2 3 Binary input 4 Limit value monitoring 1 5 Limit value monitoring 2 6 Timer signal Setup program The output signal can be inverted Parameters Value Description Function FnCt 9 Function of the o...

Страница 20: ...n 1 Start self optimization 2 Abort self optimization Limit value monito ring 1 and 2 LiI Li2 3 Change to manual mode 4 Switch off controller controller outputs inactive 5 Switch on controller 6 Inhibit manual mode Timer signal tF1 7 Stop ramp firing curve 8 Abort ramp firing curve 9 Restart ramp start abort firing curve 10 Switch over from setpoint 1 to setpoint 2 11 Lock keypad 12 Inhibit parame...

Страница 21: ... 0 No display change 1 Residual timer time 2 Timer run time Time out tout 0 180 255 Time period in seconds after which the device automatically returns to its normal display if no key is pressed 0 Function switched off Decimal place dECP 0 No decimal place 1 One decimal place 2 Two decimal places Function key press briefly 2 s tAS 0 No function 1 Start timer firing curve 2 Abort timer firing curve...

Страница 22: ... effectiveness of the I portion 0 reset time switched off no I portion Cycle time Cy1 Cy2 1 0 0 20 0 999 9 s When using a switched output the cycle time should be cho sen so that the energy flow to the process is as continuous as is practicable without overloading the switching elements Contact spacing db 0 0 999 9 Spacing between the two control contacts of a 3 state control ler Hysteresis HyS1 H...

Страница 23: ...e areas Ex areas 4 1 1 Device representation including dimensions LC100 TIP The information given in this chapter is exclusively contained in this operating manual provided as PDF document It supplements the information contained in the previous chapters of this operating manual as well as in the brief instructions added to every device as a print out 1 Setup interface USB on the device top 2 Pane...

Страница 24: ...4 Supplement 24 LC200 1 Setup interface USB on the device bottom 2 Panel cut out 92 0 8 45 0 8 1 2 ...

Страница 25: ...d resistance to organic solvents such as ethyl alcohol turpentine substitute P1 xylol and similar Do not use high pressure cleaning equipment 1 Setup interface USB on the device bottom 2 Panel cut out Type without USB cable with USB cable horizontal vertical horizontal vertical LC100 11 mm 30 mm 11 mm 65 mm LC200 22 mm 30 mm 22 mm 65 mm LC300 22 mm 30 mm 22 mm 65 mm 92 0 8 92 0 8 1 2 ...

Страница 26: ...s operating manual as well as in the brief instructions added to every device as a print out 1 Select parameter lower display green 2 Change value upper display red 3 Parameter flashes 1 Select parameter lower display green 2 Change value upper display red 3 Parameter flashes 1 Select parameter with key B or C 2 Change over to the input mode with key A The lower display flashes 3 Change value with...

Страница 27: ...limit frequency 4 2 3 Analog output Zero point and end value The factory setting corresponds to an output level of 0 100 for the continuous controller con troller output 1 zero point 0 end value 100 If the analog output is used as controller output 2 for the 3 state controller e g for cooling the following setting is required zero point 0 end value 100 If for example the actual value is to be put ...

Страница 28: ...s used to control LED Ramp H Is lit with active ramp function until it is cancelled TIP The ramp function is interrupted in the event of a probe break probe short circuit overrange underrange or changeover to manual mode Once the event is remedied or after switching to automatic mode the ramp function continues at the current actual value After the power supply is restored the ramp function starts...

Страница 29: ...aborted in the event of a probe break probe short circuit over range underrange or change over to manual mode controller switched off After the power supply is restored the firing curve is not active controller switched off When the firing curve is not active OFF appears in the lower display A Without tolerance band B With tolerance band SP1 Setpoint 1 tOLt Tolerance band t1 Timer value S Start ma...

Страница 30: ...optimum pa rameters for a PID or PI controller The following parameters are optimized depending on the controller type configured 2 state 3 state continuous controller and the controller structure parameterization Proportional band Pb1 Pb2 derivative time dt reset time rt cycle time Cy1 Cy2 filter time constant dF parameter of the analog input AF1 symmetric AF2 symmetric AF1 asymmetric AF2 asymmet...

Страница 31: ... it possible to sufficiently influence the actual value in the manual mode Only for continuous controller The function of the output OutP OutA must be configured as controller output 1 and scaled to 0 100 This means Function FnCt Controller output 1 9 Zero point 0Pnt 0 End value End 100 Depending on the controller type and parameter setting the controller structures and specific pa rameters are op...

Страница 32: ... flashes in the lower display Self optimization is completed when the display automatically changes to the normal display The duration of self optimization depends on the control process Abort of self optimization Simultaneously press keys B and C No parameters are changed by the abort ...

Страница 33: ...y Cause Fault remedy 1999 flashing Underrange of the dis played value Is the medium being measured within the range too hot too cold Check probe for break and short circuit Check the probe connection and the termi nals Check cable Check that the connected probe complies with the configured probe type 9999 flashing Overrange of the displayed value PErr Firing curve start is impos sible because the ...

Страница 34: ... ppm K d 100 ppm K d 100 ppm K d 100 ppm K d 100 ppm K d 100 ppm K d 100 ppm K Cold junction KTY internal Designation connection type Measuring range Measuring accuracya a The accuracy values refer to the measuring range Ambient temperature influence Pt100 DIN EN 60751 2 wire connection 3 wire connection 200 to 650 C d 0 4 d 0 4 d 50 ppm K Pt1000 DIN EN 60751 2 wire connection 3 wire connection 20...

Страница 35: ...Input for potential free contact open inactive closed active Measuring probe Overrange underrange Probe cable short circuit Probe cable break Thermocouple RTD temperature probe Voltage 0 to 10V Current 4 to 20 mA Current 0 to 20 mA detected not detected Relay N O Contact rating Contact life max 3 A at 230 V AC resistive load 150 000 operations at nominal load 350 000 operations at 1A 310 000 opera...

Страница 36: ...nly for industrial use Interference immunity Industrial requirements Setup interface USB socket type Mini B 5 pole Core end ferrule pipe shape without plastic sheath as per DIN 46228 part 1 with plastic sheath as per DIN 46228 part 4 Cable lug open crimp cable lug dimensionally adapted to DIN 46237 for closed crimp cable lugs Pin cable lug as per DIN 46231 With UL applications use of the cable lug...

Страница 37: ...19200 Data format 8 data bits no parity bit 1 stop bit Device address 0 to 254 No of subscribers max 32 Digit height LC100 LC200 upper display 10 mm lower display 7 mm LC300 upper display 20 mm lower display 13 mm Color upper display red lower display green Places 4 including decimal places Decimal places 0 1 2 configurable Display range 1999 to 9999 Approval marks Inspection authority Certificate...

Страница 38: ...4 Supplement 38 ...

Страница 39: ......

Страница 40: ...s 36035 Fulda Germany Phone 49 661 6003 0 Fax 49 661 6003 607 E mail mail jumo net Internet www jumo net JUMO House Temple Bank Riverway Harlow Essex CM20 2DY UK Phone 44 1279 63 55 33 Fax 44 1279 63 52 62 E mail sales jumo co uk Internet www jumo co uk 6733 Myers Road East Syracuse NY 13057 USA Phone 315 437 5866 1 800 554 5866 Fax 315 437 5860 E mail info us jumo net Internet www jumousa com ...

Отзывы: