4 Configuration parameters
60
4.2 Table of configuration parameters
The table below lists all the instrument parameters. The order in which the
parameters are explained corresponds to the order in which they appear on
the instrument (in the menu structure).
The first column describes the path to the particular parameter, via the menus
and windows.
The second column lists the possible settings for the parameters or the
possible selections. The factory default setting in this column is shown bold.
The third column contains a description of the parameter, or the possible
selections, if the parameter and its function or selection is not self-evident.
4.2.1 Parameterization
Parameter
Value/Selection
Description
Contrast
Parameterization
➔
Contrast
0 — 16 — 31
Display contrast
Speed indication
Parameterization
➔
Speed indic. mode
in mm/h,
time/div,
storage rate
The selected display mode
is shown in the diagram
representation
Switch-off event
Parameterization
➔
Display off
➔
Switch-off event
Waiting time,
Cntrl signal
The type of display
switch-off (screen saving)
is selected here
Waiting time
Parameterization
➔
Display off
➔
Waiting time
0 — 32767min
Time after which the
display is switched off. Any
key stroke will re-activate
the display. The parameter
can only be entered if the
parameter Switch-off event
is set to “Waiting time”.
0 = display not off
Control signal
Parameterization
➔
Display off
➔
Ctrl signal
Off,
Bin. inp. 1 — 4,
Logic channel 1 — 6,
Low alarm 1 — 6,
Low comb.al.,
High alarm 1 — 6,
High comb.al.,
Count/Int/Al 1 — 6,
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,
If one of the 4 binary inputs
(extra code) or one of the
other control signals is set
to “off” and activated, then
the display will be switched
off. The parameter can only
be entered if the parameter
Switch-off event is set to
“Control signal”.
Signal type
Parameterization
➔
Diagram view
➔
Signal type
Analog inp.,
Analog&Event
This determines which
measurements are
graphically displayed
Содержание LOGOSCREEN 550 cf
Страница 1: ...Paperless Recorder B 70 6510 0 Operating Manual 03 08 00467986 cf...
Страница 2: ......
Страница 30: ...2 Device description 30...