119
8 Parameterization
8.4.3
Menu: Device Setup
Italics = Parameter can only be viewed in the "Advanced" password level
Italics = Parameter can only be viewed in the "Advanced" password level
Q
max
2
You toggle between the measuring ranges using the digital input or via the "Device Setup/...Sensor/Dual
ranges" menu
Menu/parameter
Value range
Description
Device Setup
... Access Control
Selection of "... Access Control" submenu
... Sensor
Selection of "... Sensor" submenu
... Transmitter
Selection of "... Transmitter" submenu
Menu/parameter
Value range
Description
Device Setup/
... Access Control
Standard Password
Alphanumeric
Enter/change the password for the "Standard" access
level
Advanced Password
Alphanumeric
Enter/change the password for the "Advanced" ac-
cess level
Read Only Switch
Display only (ON/OFF)
Display of the BR902 switch position (hardware write
protection)
Custody Switch
Display only (ON/OFF)
Display of the custody switch position (the switch
must be enabled for the calibrated device)
Menu/parameter
Value range
Description
Device Setup/
... Sensor
Q
max
DN
Display only
The displayed value indicates the flow at a flow veloc-
ity of 10 m/s.
The value is automatically set via the selected nomi-
nal width.
Q
max
Min. measuring range:
0 to 0.2 m/s
(0 to 0.2 × Q
max
DN)
Setting of measuring range end value (measuring
range 1) for supply and return side
Default setting: 1 × Q
max
DN
Max. measuring range:
0 to 0.2 m/s
(0 to 2 × Q
max
DN)
Q
max
2
See Q
max
Setting of measuring range end value (measuring
range 2) for supply and return side (see note)
Default setting: 1 × Q
max
DN, measuring range 2 is
disabled
Range Mode
Q
max
enabled
Manual toggling between the measuring ranges Q
max
and Q
max
2
Q
max
2 enabled
Sensor Location TAG
Alphanumeric,
max. 20 characters
Entry of the measuring point identifier of the sensor
(the measuring point identifier is displayed on the top
left of the process display)
Sensor TAG
Alphanumeric,
max. 20 characters
Entry of the TAG number of the sensor
?
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......